BVP:254211 LXC0962-1W*-1AD*
From SIEMENS
LXC0962-1W*-1AD* ANC.EQUIPM.UNIT,OPT.LENGTH, 1 O UTGOER | ||
Model | ||
Product designation | trunking unit for LX busbar trunking system | |
Product type designation | LXC0962-1W*-1AD* | |
General technical data | ||
Configuration of the busbars | L1,L2,L3,N,N,PE | |
Voltage | ||
Insulation voltage | ||
at AC / rated value | 690 V | |
at DC / rated value | 800 V | |
Protection class | ||
Protection class IP | IP54, IP55 | |
Electricity | ||
Number of circuits / in a trunking unit | 1 | |
Short-time current resistance (Icw) / at 1000 V / limited to 1 s / rated value | 150 kA | |
Surge current resistance / at 1000 V / rated value | 255 kA | |
Main circuit | ||
Operating frequency / rated value | ||
minimum | 50 Hz | |
maximum | 50 Hz | |
Operating voltage / at AC | ||
at 50 Hz / rated value / maximum | 690 V | |
Operating current | ||
for circuit 1 / at AC / at 50 Hz / rated value / maximum | 5 000 A | |
for circuit 2 / at AC / at 50 Hz / rated value / maximum | 5 000 A | |
Appearance | ||
Color | light grey | |
Product details | ||
Product component / Fire shielding | No | |
Number | ||
Number of conductors | 12 | |
Number of conductors / without PE | 10 | |
Connections | ||
Conductor cross section / of the (PE)N | 4 768 mm² | |
Tap-off points | ||
Arrangement of the outgoing points | single-sided | |
Number of outgoing points / maximum | 1 | |
Mechanical Design | ||
Height | 599 mm | |
Width | 145 mm | |
Mounting position / of the busbar trunking unit | horizontal / vertical | |
Length | 1 750 mm | |
Length | ||
of the busbar trunking unit | 1.75 m | |
of the busbar trunking unit / customized / maximum | 2 m | |
of the busbar trunking unit / customized / minimum | 1.5 m | |
Mounting type | ceiling / wall | |
Material / of the busbar | copper |