7MH4134-6LB00-0DA0
ET 200SP AI 2 X SG 4-/6-WIRE HS

From SIEMENS

SIMATIC ET 200SP, ANALOG INPUT MODULE, AI 2 X SG 4-/6-WIRE HIGH SPEED, FITS TO BU-TYPE A0, COLOR CODE CC00, CHANNEL DIAGNOSIS, 28/16BIT, +/-0,05%, FOR STRAIN GAUGE FULL BRIDGES
General information
Product type designationAI 2xSG 4-/6-wire HS
HW functional status01
Firmware versionV1.0.0
FW update possibleYes
usable BaseUnitsBU type A0
Color code for module-specific color identification plateCC00
Product function
I&M dataYes; I&M0 to I&M3
Measuring range scalableYes
Scalable measured valuesNo
Adjustment of measuring rangeYes; ±0.5 ... 320 mV/V
Engineering with
STEP 7 TIA Portal configurable/integrated as of versionV14 SP1
STEP 7 configurable/integrated as of versionV5.6
PROFIBUS as of GSD version/GSD revisionV03.01.105
PROFINET as of GSD version/GSD revisionGSDML V2.33
Operating mode
OversamplingYes; 2 channels per module
MSINo
CiR – Configuration in RUN
Reparameterization possible in RUNYes
Calibration possible in RUNNo
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Input current
Current consumption (rated value)70 mA
Encoder supply
Output voltage (DC)4.85 V
Short-circuit protectionYes
Output current
Rated value60 mA; Per channel
Power
Power available from the backplane bus65 mW
Power loss
Power loss, typ.1.5 W
Address area
Address space per module
Address space per module, max.32 byte
Inputs32 byte
Outputs8 byte
Hardware configuration
Automatic encoding
Mechanical coding elementYes
Analog inputs
Number of analog inputs2; Differential inputs
Cycle time (all channels), min.100 µs
Analog input with oversamplingYes
Values per cycle, max.14
Resolution, min.100 µs
Input ranges
Strain gauges (full bridges)Yes
Cable length
shielded, max.500 m
Analog value generation for the inputs
Measurement principleSigma Delta
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.28 bit; 16 bits with oversampling
Integration time, parameterizableYes
Interference voltage suppression for interference frequency f1 in Hz60 / 50 Hz / no
Conversion time (per channel)100 µs
Smoothing of measured values
IIR low-pass filter frequency0.01 ... 600 Hz
IIR low-pass filter ordinal number1 ... 4
Notch filter frequency0.1 ... 1 000 Hz
Notch filter quality5.00 ... 250.00
Average value filter0.1 ... 655.3 ms
Encoder
Connection of signal encoders
For strain gauges (full bridges) with 4-conductor connectionYes
For strain gauges (full bridges) with 6-conductor connectionYes
Resistance of full bridge, min.80 Ω
Resistance of full bridge, max.5 000 Ω
Errors/accuracies
Linearity error (relative to input range), (+/-)0.025 %
Temperature error (relative to input range), (+/-)0.0005 %/°C; Strain gauge full bridge, 6-conductor connection
Temperature coefficient, zero point≤ ±0.25 μV/K
Temperature coefficient, span, 4-conductor connection (referred to end value)≤ ±5 ppm/K
Temperature coefficient, span, 6-conductor connection (referred to end value)≤ ±10 ppm/K
Basic error limit (operational limit at 25 °C)
Voltage, relative to input range, (+/-)0.05 %; See manual for details
Isochronous mode
Isochronous operation (application synchronized up to terminal)Yes
Filtering and processing time (TCI), min.87 µs
Bus cycle time (TDP), min.125 µs
Interrupts/diagnostics/status information
Diagnostics functionYes
Alarms
Diagnostic alarmYes
Limit value alarmYes; two upper and two lower limit values in each case
Diagnostic messages
Monitoring the supply voltageYes
Wire-breakYes
Short-circuitYes
Group errorYes
Overflow/underflowYes
Diagnostics indication LED
Monitoring of the supply voltage (PWR-LED)Yes; green PWR LED
Channel status displayYes; Green LED
for channel diagnosticsYes; Red LED
for module diagnosticsYes; green/red DIAG LED
Potential separation
Potential separation channels
between the channelsNo
between the channels and backplane busYes
between the channels and the power supply of the electronicsYes
Isolation
Isolation tested with707 V DC (type test)
Ambient conditions
Ambient temperature during operation
horizontal installation, min.-25 °C
horizontal installation, max.60 °C
vertical installation, min.-25 °C
vertical installation, max.50 °C
Altitude during operation relating to sea level
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax – 1 K/100 m) at 795 hPa ... 701 hPa (+2 000 m ... +3 000 m)
Dimensions
Width15 mm
Height73 mm
Depth58 mm
Weights
Weight, approx.45 g
last modified:03/13/2019