Product type designation | CP 343-1 Advanced |
| Communications processor CP 343-1 Advanced for connection of SIMATIC S7-300 to Industrial Ethernet: PROFINET IO Controller, PROFINET CBA, ISO, TCP/IP and UDP, S7 communication, fetch/write, SEND/RECEIVE, with and without RFC1006, HTTP with JAVA, Multicast, chargeable Communication modules, HTML diagnostics, FTP Client/Server Email, SNMP, DHCP, NTP-CPU Sync, 10/100 MBit, nur RJ45 connection |
Transmission rate |
Transfer rate | |
at the 1st interface | 10 ... 100 Mbit/s |
Interfaces |
Number of interfaces / acc. to Industrial Ethernet | 1 |
Number of electrical connections | |
at the 1st interface / acc. to Industrial Ethernet | 1 |
for power supply | 1 |
Type of electrical connection | |
at the 1st interface / acc. to Industrial Ethernet | RJ45 port |
of Industrial Ethernet interface | RJ45 port |
for power supply | 2-pole plugable terminal block |
design of the removable storage / C-PLUG | Yes |
Supply voltage, current consumption, power loss |
Type of voltage / of the supply voltage | DC |
Supply voltage / 1 / from backplane bus | 5 V |
Supply voltage | 24 V |
Supply voltage / external | 24 V |
Supply voltage / external / at DC / Rated value | 24 V |
Relative positive tolerance / at DC / at 24 V | 20 % |
Relative negative tolerance / at DC / at 24 V | 15 % |
Consumed current | |
from backplane bus / at DC / at 5 V / typical | 0.14 A |
Power loss [W] | 14.7 W |
Permitted ambient conditions |
Ambient temperature | |
for vertical installation / during operation | 0 ... 40 °C |
for horizontally arranged busbars / during operation | 0 ... 60 °C |
during storage | -40 ... +70 °C |
during transport | -40 ... +70 °C |
Relative humidity / at 25 °C / without condensation / during operation / maximum | 95 % |
Protection class IP | IP20 |
Design, dimensions and weight |
Module format | Compact module S7-300 double width |
Width | 80 mm |
Height | 125 mm |
Depth | 120 mm |
Net weight | 0.8 kg |
Mounting type | |
S7-300 rail mounting | Yes |
Performance data / open communication |
Number of possible connections / for open communication / by means of SEND/RECEIVE blocks / maximum | 16 |
Amount of data | |
as user data per ISO connection / for open communication / by means of SEND/RECEIVE blocks / maximum | 8 Kibyte |
as user data per ISO on TCP connection / for open communication / by means of SEND/RECEIVE blocks / maximum | 8 Kibyte |
as user data per TCP connection / for open communication / by means of SEND/RECEIVE blocks / maximum | 8 Kibyte |
as user data per UDP connection / for open IE communication / by means of SEND/RECEIVE blocks / maximum | 2 Kibyte |
Number of Multicast stations | 16 |
Performance data / S7 communication |
Number of possible connections / for S7 communication | |
maximum | 16 |
Performance data / multi-protocol mode |
Number of active connections / with multi-protocol mode | 48 |
Performance data / IT functions |
Number of possible connections | |
as client / by means of FTP / maximum | 10 |
as server / by means of FTP / maximum | 2 |
Number of possible connections | |
as server / by means of HTTP / maximum | 4 |
as e-mail client / maximum | 1 |
Amount of data / as user data for email / maximum | 8 Kibyte |
Storage capacity / of the user memory | |
as flash memory file system | 28 Mibyte |
as RAM | 30 Mibyte |
Number of possible write cycles / of the flash memory cells | 100000 |
Performance data / PROFINET communication / as PN IO-Controller |
Number of PN IO devices / on PROFINET IO controller / usable / total | 125 |
Number of external PN IO lines / with PROFINET / per rack | 1 |
Amount of data | |
as user data for input variables / as PROFINET IO controller / maximum | 4 Kibyte |
as user data for input variables / as PROFINET IO controller / maximum | 4 Kibyte |
as user data for input variables per PN IO device / as PROFINET IO controller / maximum | 1433 byte |
as user data for output variables per PN IO device / as PROFINET IO controller / maximum | 1433 byte |
Performance data / PROFINET CBA |
Number of remote connection partners / with PROFINET CBA | 64 |
Number of connections / with PROFINET CBA / total | 1000 |
Amount of data | |
as user data for digital inputs / with PROFINET CBA / maximum | 8 Kibyte |
as user data for digital outputs / with PROFINET CBA / maximum | 8 Kibyte |
as user data for arrays and data types / in the case of acyclic transmission / with PROFINET CBA / maximum | 8 Kibyte |
as user data for arrays and data types / with PROFINET CBA / with cyclical transfer / maximum | 450 byte |
as user data for arrays and data types / with PROFINET CBA / in the case of local interconnection / maximum | 2400 byte |
Performance data / PROFINET CBA / remote connection / with acyclic transmission |
Refresh time / of the remote interconnections / in the case of acyclic transmission / with PROFINET CBA | 100 ms |
Number of remote connections to input variables / in the case of acyclic transmission / with PROFINET CBA / maximum | 128 |
Number of remote connections to output variables / in the case of acyclic transmission / with PROFINET CBA / maximum | 128 |
Amount of data | |
as user data for remote interconnections with input variables / in the case of acyclic transmission / with PROFINET CBA | 8 Kibyte |
as user data for remote interconnections with output variables / in the case of acyclic transmission / with PROFINET CBA | 8 Kibyte |
Performance data / PROFINET CBA / remote connection / with cyclic transmission |
Refresh time / of the remote interconnections / with PROFINET CBA / with cyclical transfer | 8 ms |
Number of remote connections to input variables / with PROFINET CBA / with cyclical transfer / maximum | 200 |
Number of remote connections to output variables / with PROFINET CBA / with cyclical transfer / maximum | 200 |
Amount of data | |
as user data for remote interconnections with input variables / with PROFINET CBA / with cyclical transfer / maximum | 2000 byte |
as user data for remote interconnections with output variables / with PROFINET CBA / with cyclical transfer / maximum | 2000 byte |
Performance data / PROFINET CBA / HMI variables via PROFINET / acyclic |
Number of connectable HMI stations / for HMI variables / in the case of acyclic transmission / with PROFINET CBA | 3 |
Refresh time / of the HMI variables / in the case of acyclic transmission / with PROFINET CBA | 500 ms |
Number of HMI variables / in the case of acyclic transmission / with PROFINET CBA / maximum | 200 |
Amount of data / as user data for HMI variables / in the case of acyclic transmission / with PROFINET CBA / maximum | 8 Kibyte |
Performance data / PROFINET CBA / device-internal connections |
Number of internal connections / with PROFINET CBA / maximum | 256 |
Amount of data / of the internal connections / with PROFINET CBA / maximum | 2400 byte |
Performance data / PROFINET CBA / connections to constants |
Number of connections with constants / with PROFINET CBA / maximum | 200 |
Amount of data / as user data for interconnections with constants / with PROFINET CBA / maximum | 4096 byte |
Performance data / PROFINET CBA / PROFIBUS proxy functionality |
Product function / with PROFINET CBA / PROFIBUS proxy functionality | No |
Performance data / telecontrol |
Protocol / is supported | |
TCP/IP | Yes |
Product functions / management, configuration |
Product function / MIB support | Yes |
Protocol / is supported | |
SNMP v1 | Yes |
DCP | Yes |
LLDP | Yes |
Configuration software | |
required | STEP 7 V5.3 SP2 or higher |
for PROFINET CBA / required | SIMATIC iMap V2.0 SP1 and higher |
Identification & maintenance function | |
I&M0 - device-specific information | Yes |
I&M1 – higher-level designation/location designation | Yes |
Product functions / Diagnosis |
Product function / Web-based diagnostics | Yes |
Product functions / switch |
Product feature / Switch | No |
Product functions / Redundancy |
Product function | |
Ring redundancy | No |
Product functions / Security |
Product function | |
ACL - IP-based | Yes |
ACL - IP-based for PLC/routing | No |
switch-off of non-required services | No |
Blocking of communication via physical ports | No |
log file for unauthorized access | No |
Product functions / Time |
Product function / SICLOCK support | Yes |
Product function / pass on time synchronization | Yes |
Protocol / is supported | |
NTP | Yes |