Product type designation | CP 1243-8 IRC |
| Communications processor CP 1243-8 IRC for operating a SIMATIC S7-1200 in the TeleControl system Professional; for SINAUT ST7; DNP3; IEC60870-5, Station type: RTU; WAN connections: 1) Ethernet 2) Additionally expandable with TS module RS232 or TS module modem or TS module GSM or TS module ISDN; Operation with TIM modules possible |
Transmission rate |
Transfer rate | |
at the 1st interface | 10 ... 100 Mbit/s |
at the 2nd interface | 0.3 ... 115.2 kbit/s |
Interfaces |
Number of interfaces / acc. to Industrial Ethernet | 1 |
Number of electrical connections | |
at the 1st interface / acc. to Industrial Ethernet | 1 |
for power supply | 1 |
Type of electrical connection | |
at the 1st interface / acc. to Industrial Ethernet | RJ45 port |
at interface 2 / for external data transmission | Interface to the TS Module |
for power supply | 3-pole terminal block |
Supply voltage, current consumption, power loss |
Type of voltage / of the supply voltage | DC |
Supply voltage / 1 / from backplane bus | 5 V |
Supply voltage / external | 24 V |
Supply voltage / external | 19.2 ... 28.8 V |
Supply voltage / external / at DC / Rated value | 24 V |
Supply voltage / external / at DC / rated value | 19.2 ... 28.8 V |
Consumed current | |
from backplane bus / at DC / at 5 V / typical | 0.25 A |
from external supply voltage / at DC / at 24 V / typical | 0.1 A |
Power loss [W] / Note | 1.25 W from S7-1200 backplane without TS module. 2.4 W from 24 V DC external with TS module |
Power loss [W] | 2.4 W |
Permitted ambient conditions |
Ambient temperature | |
for vertical installation / during operation | -20 ... +60 °C |
for horizontally arranged busbars / during operation | -20 ... +70 °C |
during storage | -40 ... -70 °C |
during transport | -40 ... +70 °C |
Relative humidity / at 25 °C / without condensation / during operation / maximum | 95 % |
Protection class IP | IP20 |
Design, dimensions and weight |
Module format | Compact module S7-1200 single width |
Width | 30 mm |
Height | 110 mm |
Depth | 75 mm |
Net weight | 0.122 kg |
Mounting type | |
35 mm DIN rail mounting | Yes |
S7-300 rail mounting | No |
wall mounting | Yes |
Product properties, functions, components / general |
Number of units | |
per CPU / maximum | 1 |
Note | One CP pluggable on left side of CPU, one TS Module pluggable left side of CP. |
Performance data / open communication |
Number of possible connections / for open communication | |
by means of T blocks / maximum | like CPU |
Performance data / S7 communication |
Number of possible connections / for S7 communication | |
with PG connections / maximum | 2 |
with OP connections / maximum | 1 |
Note | Configured S7-Connection for ST7-Communication |
Service | |
SINAUT ST7 via S7 communication | Yes |
Performance data / IT functions |
Number of possible connections | |
as e-mail client / maximum | 1 |
Performance data / telecontrol |
Suitability for use | |
Node station | No |
substation | Yes |
TIM control center | No |
Note | Ethernet and TS Module can be operated in parallel |
Control center connection | control center with ST7 function |
by means of a permanent connection | supported |
Protocol / is supported | |
DNP3 | Yes |
IEC 60870-5 | Yes |
SINAUT ST7 protocol | Yes |
Product function / data buffering if connection is aborted | Yes; 16,000 data messages |
Number of data points per station / maximum | 200 |
Transmission format | |
for SINAUT ST7 protocol with multi-master polling / 10-bit | Yes |
for SINAUT ST7 protocol with polling or spontaneous / 10-bit or 11-bit | Yes |
Operating mode for scanning of data transmission | |
with dedicated line/radio link / with SINAUT ST7 protocol | Polling |
with dial-up network / with SINAUT ST7 protocol | spontaneous |
Hamming distance | |
for SINAUT ST7 protocol | 4 |
Performance data / Teleservice |
Diagnostics function / online diagnostics with SIMATIC STEP 7 | Yes |
Product function | |
program download with SIMATIC STEP 7 | Yes |
Remote firmware update | Yes |
Product functions / management, configuration |
Protocol / is supported | |
SNMP v3 | Yes |
DCP | Yes |
Configuration software | |
required | SINAUT ES V5.5 and STEP7 V13 SP1 or higher |
for PG configuring / required / SINAUT ST7 configuration software for PG | Yes |
Product functions / Diagnosis |
Product function / Web-based diagnostics | Yes |
Product functions / Security |
Firewall version | stateful inspection |
Suitability for operation / Virtual Private Network | Yes |
Product function / with VPN connection | IPSec, SINEMA RC |
Type of encryption algorithms / with VPN connection | AES-256, AES-192, AES-128, 3DES-168, DES-56 |
Type of authentication procedure / with VPN connection | Preshared key (PSK), X.509v3 certificates |
Type of hashing algorithms / with VPN connection | MD5, SHA-1 |
Number of possible connections / with VPN connection | 8 |
Product function | |
password protection for teleservice access | No |
encrypted data transmission | Yes |
MSC client via GPRS modem with MSC capability | Yes |
Protocol | |
is supported / MSC protocol | Yes |
with Virtual Private Network MSC / is supported | TCP/IP |
Key length / for MSC / with Virtual Private Network | 128 bit |
Number of possible connections | |
as MSC client / with VPN connection | 1 |
as MSC server / with VPN connection | 0 |
Product functions / Time |
Protocol / is supported | |
NTP | Yes |
time synchronization | |
from NTP-server | Yes |
from control center | Yes |
Accessories |
accessories | TS Module RS232 or TS Module MODEM or TS Module ISDN or TS Module GSM pluggable |