Product type designation | CP 5711 |
| Communications processor CP 5711 USB adapter (USB V2.0) for connection of a PG or Notebook to PROFIBUS or MPI; contain 2 m USB cable |
Transmission rate |
Transfer rate | |
at the 1st interface / acc. to PROFIBUS | 9.6 kbit/s ... 12 Mbit/s |
Interfaces |
Number of electrical connections | |
at the 1st interface / acc. to PROFIBUS | 1 |
for power supply | 1 |
Number of interfaces / acc. to USB | 1 |
Type of electrical connection | |
at the 1st interface / acc. to PROFIBUS | 9-pin Sub-D socket (RS 485) |
for power supply | 2-pole terminal block |
of the USB interface | Standard-B socket with mechanical interlock |
Standard for interfaces / USB 2.0 | Yes |
Supply voltage, current consumption, power loss |
Type of voltage / of the supply voltage | DC |
Type of voltage supply / optional external supply | Yes |
Supply voltage | |
from USB | 5 V |
external | 24 V |
external | 18 ... 30 V |
Note | Supplied directly from USB provided that supply from PC is adequate; alternative external supply is possible |
Relative symmetrical tolerance / at DC | |
at 5 V | 5 % |
at 24 V | 5 % |
Consumed current | |
from USB | 0.5 A |
from external supply voltage / at DC / at 24 V / maximum | 0.3 A |
Power loss [W] | 2.5 W |
Permitted ambient conditions |
Ambient temperature | |
during operation | 0 ... 60 °C |
during storage | -40 ... +60 °C |
during transport | -40 ... +60 °C |
Relative humidity / at 25 °C / without condensation / during operation / maximum | 85 % |
Protection class IP | IP20 |
Design, dimensions and weight |
Module format | USB V2.0 adapter |
Width | 85 mm |
Height | 137 mm |
Depth | 35 mm |
Net weight | 300 g |
Mounting type | Mounting on DIN rail with optional mounting rail support |
Mounting type / 35 mm DIN rail mounting | Yes |
Number of plug-in cards of same design / plug-in / per PC station | 1 |
Number of units / Note | - |
Performance data |
Performance data / open communication |
Software / for open communication / by means of SEND/RECEIVE / required | Yes, SOFTNET-PB DP / SOFTNET-PB DP Slave / SOFTNET-PB S7 |
Number of possible connections / for open communication / by means of SEND/RECEIVE / maximum | 50 |
Performance data / PROFIBUS DP |
Software / for DP master function / required | Yes, SOFTNET-PB DP |
Service / as DP master | |
DPV0 | Yes |
DPV1 | No |
DPV2 | No |
Number of DP slaves / on DP master / usable | 64 |
Amount of data | |
of the address area of the inputs / as DP master / total | 15616 byte |
of the address area of the outputs / as DP master / total | 15616 byte |
of the address area of the inputs / per DP slave | 244 byte |
of the address area of the outputs / per DP slave | 244 byte |
of the address area of the diagnostic data / per DP slave | 244 byte |
Software / for DP slave function / required | Yes, SOFTNET-PB DP slave |
Service / as DP slave | |
DPV0 | Yes |
DPV1 | No |
Amount of data | |
of the address area of the inputs / as DP slave / total | 122 byte |
of the address area of the outputs / as DP slave / total | 122 byte |
Performance data / S7 communication |
Software / for S7 communication / required | Yes, SOFTNET-PB S7 |
Number of possible connections / for S7/PG communication / maximum | 8 |
Performance data / multi-protocol mode |
Number of configurable connections / per PC station | 207 |
Product functions / management, configuration |
Configuration software / required | Included in the scope of delivery of the required software product |
Product functions / Diagnosis |
Product function | |
Port diagnostics | Yes |
Standards, specifications, approvals |
Standard | |
for EMC | 2004/108/EC |
for safety / from CSA and UL | CAN/CSA C22.2 & UL 60950-1 |
for emitted interference | EN 61000-6-3, EN 61000-6-4 |
for interference immunity | EN 61000-6-1, EN 61000-6-2 |
Certificate of suitability | |
CE marking | Yes |
C-Tick | Yes |
Accessories |
accessories | optional: MPI cable, mounting rail support |