6GK1500-3AA00
OPTICAL BUS TERMINAL

From SIEMENS

Product type designationPROFIBUS OBT
PROFIBUS OBT; opt. bus terminal for connection of a PROFIBUS nodes without integr. opt. interface to the opt. PROFIBUS DP; without Simplex plug
Transmission rate
Transfer rate / with PROFIBUS9.6 kbit/s ... 12 Mbit/s
Transfer rate / with PROFIBUS PA45.45 kbit/s
Interfaces
Number of electrical/optical connections / for network components or terminal equipment / maximum3
Number of electrical connections
for network components or terminal equipment1
for power supply1
Type of electrical connection
for network components or terminal equipment9-pin Sub-D socket
for power supply3-pole terminal block
for power supply and signaling contact-
Number of optical interfaces / for fiber optic cable2
Design of the optical interface / for fiber optic cableDuplex port
Optical data
Damping ratio / of the FOC transmission link
for PCF FOC with 200/230 µm / at 10 dB/km3 dB
for POF FOC with 980/1000 µm / at 230 dB/km13 dB
propagation delay [bit]6.5 bit
Connectable optical power relative to 1 mW
of the FOC transmission link / for PCF FOC with 200/230 µm / at 10 dB/km-16 dB
of the FOC transmission link / for POF FOC with 980/1000 µm / at 230 dB/km-5.9 dB
Optical sensitivity relating to 1 mW
of the FOC transmission link / for PCF FOC with 200/230 µm / at 10 dB/km-22 dB
of the FOC transmission link / for POF FOC with 980/1000 µm / at 230 dB/km-20 dB
Wavelength
of the FOC transmission link / for PCF FOC with 200/230 µm / at 10 dB/km660 nm
of the FOC transmission link / for POF FOC with 980/1000 µm / at 230 dB/km660 nm
Wire length
for PCF FOC with 200/230 µm / at 10 dB/km / maximum300 m
for POF FOC with 980/1000 µm / at 230 dB/km / maximum50 m
Supply voltage, current consumption, power loss
Type of voltage / of the supply voltageDC
Supply voltage / at DC / Rated value24 V
Supply voltage / at DC19.2 ... 28.8 V
Permitted ambient conditions
Ambient temperature
during operation0 ... 60 °C
during storage-40 ... +70 °C
during transport-40 ... +70 °C
Relative humidity / at 25 °C / without condensation / during operation / maximum95 %
Protection class IPIP30
Design, dimensions and weight
Designcompact
Width50.5 mm
Height138 mm
Depth78 mm
Net weight400 g
Mounting type
35 mm DIN rail mountingYes
wall mountingYes
Product functions / Redundancy
Product function / Ring redundancyNo
Standards, specifications, approvals
Standard
for FMFM3611: Class 1, Division 2, Group A, B, C, D / T4, Class 1, Zone 2, Group IIC, T4
for hazardous zoneEN 60079-0: 2006, EN60079-15: 2005, II 3 G Ex nA II T4 KEMA 07 ATEX 0145X
for safety / from CSA and ULUL 60950-1, CSA C22.2 Nr. 60950-1
for hazardous zone / from CSA and ULUL 1604 and UL 2279-15 (Hazardous Location), CSA C22.2 No. 213-M1987, Class 1 / Division 2 / Group A, B, C, D / T4, Class 1 / Zone 2 / Group IIC / T11
for emitted interferenceEN 61000-6-4 (Class A)
for interference immunityEN 61000-6-2
Certificate of suitabilityEN 61000-6-2, EN 61000-6-4
CE markingYes
C-TickYes
Marine classification association
American Bureau of Shipping Europe Ltd. (ABS)No
Bureau Veritas (BV)No
Det Norske Veritas (DNV)No
Germanische Lloyd (GL)No
Lloyds Register of Shipping (LRS)No
Nippon Kaiji Kyokai (NK)No