6ES7655-5PX11-0XX0
SIMATIC CFU PA

From SIEMENS

SIMATIC Compact Field Unit PA Edition with 16x I/O channels PROFINET interface V2.3 (RT) Use of PROFINET bus adapter Media redundancy (MRP) PROFINET system redundancy (S2) Configuration in Run (CiR) Process interfaces: 8x PROFIBUS PA and 8x freely configurable DIQ Installation up to hazardous zone 2 Temperature range -40 to +70 °C Conformal coating Mounting on 35 mm standard mounting rail
General information
Product type designationCompact Field Unit
HW functional statusE01
Firmware versionV1.0
FW update possibleYes
Vendor identification (VendorID)002AH
Device identifier (DeviceID)060DH
Number of channels16
Product function
I&M dataYes; I&M0 to I&M4
The user can configure digital channels as input/output as requiredYes
Digital channels can be parameterizedYes
Engineering with
STEP 7 TIA Portal configurable/integrated as of version- / -
STEP 7 configurable/integrated as of versionFrom STEP 7 V5.6 HF1 and higher
PCS 7 configurable/integrated as of versionV9.0
PROFIBUS as of GSD version/GSD revision- / -
Installation type/mounting
Mountingon 35 mm DIN rail, 2 spacing units wide
Mounting positionHorizontal, vertical
Supply voltage
Type of supply voltage24 V DC
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Short-circuit protectionYes
Redundant power supplyYes
Mains buffering
Mains/voltage failure stored energy time5 ms; Bridging for field devices and communication
Input current
Current consumption (rated value)2.5 A
Current consumption, max.2.55 A
Inrush current, max.8 A
I²t0.3 A²·s
Encoder supply
Number of outputs8
Output voltage encoder supply, min.18.2 V
Short-circuit protectionYes; Electronic
Output current
up to 60 °C, max.2 A
up to 70 °C, max.1 A
Power loss
Power loss, typ.8.2 W; Depending on the type of BusAdapter used (typ. RJ45)
Address area
Address space per station
Address space per station, max.1 440 byte; Dependent on configuration
Digital inputs
Number of digital inputs8
Source/sink inputYes; P-reading
Input characteristic curve in accordance with IEC 61131, type 1Yes
Input characteristic curve in accordance with IEC 61131, type 2No
Input characteristic curve in accordance with IEC 61131, type 3Yes
Pulse extensionNo
Number of simultaneously controllable inputs
horizontal installation
— up to 60 °C, max.8; Total current must be observed, see DQ
— up to 70 °C, max.8; Total current must be observed, see DQ
vertical installation
— up to 60 °C, max.8; Total current must be observed, see DQ
Input voltage
Rated value (DC)24 V
for signal "0"-30 to +5V
for signal "1"+11 to +30V
Input current
for signal "1", typ.2.5 mA; Typical
Input delay (for rated value of input voltage)
for standard inputs
— parameterizableNo
— at "0" to "1", max.3.2 ms
— at "1" to "0", max.3.2 ms
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Digital outputs
Type of digital outputTransistor
Number of digital outputs8
Current-sinkingNo
Current-sourcingYes
Short-circuit protectionYes
Response threshold, typ.0.7 to 1.3 A
Limitation of inductive shutdown voltage toTyp. L+ (-50 V)
Controlling a digital inputYes
Switching capacity of the outputs
on lamp load, max.5 W
Load resistance range
lower limit48 Ω
upper limit12 kΩ
Output voltage
Type of output voltageDC
for signal "1", min.Ue minus 1 V
Output current
for signal "1" rated value0.5 A
for signal "0" residual current, max.0.1 mA
Output delay with resistive load
"0" to "1", max.50 µs
"1" to "0", max.100 µs
Parallel switching of two outputs
for upratingNo
for redundant control of a loadNo
Switching frequency
with resistive load, max.100 Hz
with inductive load, max.2 Hz
on lamp load, max.10 Hz
Total current of the outputs
Current per channel, max.0.5 A
horizontal installation
— up to 60 °C, max.2 A
— up to 70 °C, max.1 A
vertical installation
— up to 60 °C, max.2 A
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Encoder
Connectable encoders
2-wire sensorYes
— permissible quiescent current (2-wire sensor), max.1.5 mA
Interfaces
Number of PROFINET interfaces1
Number of PROFIBUS interfaces0
PROFIBUS PA
Transmission rate, max.31.25 kbit/s
Number of connectable PA field devices8; Electrically isolated from other interfaces, isolation tested at 2 500 V DC
Current output to PA field devices, max.320 mA
permissible current per spur line40 mA
Automatic addressingYes
System-supported integration of field devices via PA profilesYes
Extended fieldbus diagnosticsYes
1. Interface
Interface typePROFINET
IsolatedYes
Interface types
Number of ports2
integrated switchYes
BusAdapter (PROFINET)Yes
Protocols
PROFINET IO DeviceYes
PROFIBUS DP slaveNo
Interface types
RJ 45 (Ethernet)
100 MbpsYes
AutonegotiationYes
AutocrossingYes
Protocols
Supports protocol for PROFINET IOYes
Redundancy mode
MRPYes
PROFINET system redundancy (S2)Yes; Type S2
Open IE communication
LLDPYes
Isochronous mode
Isochronous operation (application synchronized up to terminal)No
Interrupts/diagnostics/status information
Status indicatorYes
AlarmsYes
Diagnostics functionYes
Diagnostic messages
Monitoring of encoder power supplyYes
Wire-breakYes
Short-circuitYes
Diagnostics indication LED
RUN LEDYes; Green LED
ERROR LEDYes; Red LED
MAINT LEDYes; yellow LED
Monitoring of the supply voltage (PWR-LED)Yes
Digital input status indicatorYes
Digital output status indicatorYes
Spur line status/faultYes
Potential separation
between the channels and PROFINETYes
Potential separation digital inputs
between the channelsNo
between the channels and the power supply of the electronicsNo
Potential separation digital outputs
between the channelsNo
between the channels and the power supply of the electronicsNo
Isolation
Isolation tested with1 500 V AC between PROFINET and electronics
Degree and class of protection
Degree of protection acc. to EN 60529IP20
Ambient conditions
Ambient temperature during operation
min.-40 °C
max.70 °C
horizontal installation, min.-40 °C
horizontal installation, max.70 °C; Observe derating
vertical installation, min.-40 °C
vertical installation, max.60 °C; Observe derating
Ambient temperature during storage/transportation
min.-40 °C
max.85 °C
Relative humidity
Operation, max.95 %
Connection method
Design of electrical connectionConnection plug
Spur line
Number of spur lines8
Type of cableType A
Cable diameter, min.6 mm
Cable diameter, max.12 mm
Conductor cross-section, min.0.2 mm²
Conductor cross-section, max.2.5 mm²
Cable length, max.120 m
total current output to field devices, max.320 mA
Number of connectable field devices8
Current limitation per field device, max.40 mA
No-load voltage, max.15.3 V
short-circuit proofYes
Short-circuit current (test current); max.8 mA
intrinsically safe according to FISCO modelYes
Debounce logicYes
Dimensions
Width329 mm
Height123 mm
Depth74 mm
Weights
Weight, approx.580 g
last modified:03/08/2019