| SIMATIC PCS 7, CPU 410-5H Process Automation, central processing unit for S7-400 and S7-400H/F/FH, 5 interfaces: 2x PN, 1x DP, 2x for sync modules for using as spare part, without System Expansion Card |
General information |
Product type designation | CPU 410-5H |
HW functional status | 2 |
Firmware version | V8.2 |
Design of PLC basic unit | With Conformal Coating (ISA-S71.04 severity level G1; G2; G3) and operating temperature to 70 °C |
Product function |
SysLog | Yes; via TCP; up to 4 receivers can be parameterized; buffer capacity max. 3 200 entries |
Field interface security | Yes |
Engineering with |
Programming package | SIMATIC PCS 7 V9.0 or higher |
CiR – Configuration in RUN |
CiR synchronization time, basic load | 60 ms |
CiR synchronization time, time per I/O byte | 0 µs |
Input current |
from backplane bus 5 V DC, typ. | 2 A |
from backplane bus 5 V DC, max. | 2.4 A |
from backplane bus 24 V DC, max. | 150 mA; DP interface |
from interface 5 V DC, max. | 90 mA; At the DP interface |
Power loss |
Power loss, typ. | 10 W |
Processor |
CPU speed | 450 MHz; Multi-processor system |
Memory |
PCS 7 process objects | 100 ... approx. 2 600, adjustable with System Expansion Card |
Work memory |
integrated | 32 Mbyte; max., dependent on the System Expansion Card used |
integrated (for program) | Dependent on the System Expansion Card used |
integrated (for data) | Dependent on the System Expansion Card used |
expandable | Dependent on the System Expansion Card used |
Load memory |
integrated RAM, max. | 48 Mbyte |
expandable RAM | No |
Backup |
present | Yes |
with battery | Yes; all data |
without battery | Yes; Program and data of the load memory |
Battery |
Backup battery |
Backup current, typ. | 370 µA; Valid up to 40°C |
Backup current, max. | 2.1 mA |
Backup time, max. | Dealt with in the module data manual with the secondary conditions and the factors of influence |
Feeding of external backup voltage to CPU | No |
CPU processing times |
for bit operations, typ. | 7.5 ns |
for word operations, typ. | 7.5 ns |
for fixed point arithmetic, typ. | 7.5 ns |
for floating point arithmetic, typ. | 15 ns |
average processing time of PCS 7 typicals | 110 µs; with APL Typicals |
Process tasks, max. | 9; Individually adjustable from 10 ms to 5 s |
CPU-blocks |
DB |
Number, max. | 16 000; Number range: 1 to 16 000 (= Instances) |
Size, max. | Dependent on the System Expansion Card used |
FB |
Number, max. | 8 000; Number range: 0 to 7999 |
Size, max. | 64 kbyte |
FC |
Number, max. | 8 000; Number range: 0 to 7999 |
Size, max. | 64 kbyte |
OB |
Number, max. | see instruction list |
Size, max. | 64 kbyte |
Number of free cycle OBs | 1; OB 1 |
Number of time alarm OBs | 8; OB 10-17 |
Number of delay alarm OBs | 4; OB 20-23 |
Number of cyclic interrupt OBs | 9; OB 30-38 (= Process Tasks) |
Number of process alarm OBs | 8; OB 40-47 |
Number of DPV1 alarm OBs | 3; OB 55-57 |
Number of startup OBs | 2; OB 100, 102 |
Number of asynchronous error OBs | 9; OB 80-88 |
Number of synchronous error OBs | 2; OB 121, 122 |
Nesting depth |
per priority class | 24 |
additional within an error OB | 2 |
Counters, timers and their retentivity |
S7 counter |
Number | 2 048 |
Retentivity |
— adjustable | Yes |
Counting range |
— lower limit | 0 |
— upper limit | 999 |
IEC counter |
present | Yes |
Type | SFB |
Number | Unlimited (limited only by RAM capacity) |
S7 times |
Number | 2 048 |
Retentivity |
— adjustable | Yes |
Time range |
— lower limit | 10 ms |
— upper limit | 9 990 s |
IEC timer |
present | Yes |
Type | SFB |
Number | Unlimited (limited only by RAM capacity) |
Data areas and their retentivity |
retentive data area in total | Total working and load memory (with backup battery) |
Flag |
Number, max. | 16 384 byte |
Retentivity available | Yes |
Number of clock memories | 8; in 1 memory byte |
Local data |
adjustable, max. | 64 kbyte |
preset | 64 kbyte |
Address area |
I/O address area |
Inputs | 16 kbyte; max., dependent on the System Expansion Card used |
Outputs | 16 kbyte; max., dependent on the System Expansion Card used |
Process image |
Inputs, adjustable | 16 kbyte |
Outputs, adjustable | 16 kbyte |
Inputs, default | 16 kbyte; Total peripheral address range, cannot be changed |
Outputs, default | 16 kbyte; Total peripheral address range, cannot be changed |
consistent data, max. | 244 byte |
Access to consistent data in process image | Yes |
Subprocess images |
Number of subprocess images, max. | 15 |
Digital channels |
Inputs | 131 072; max., dependent on the System Expansion Card used |
— of which central | 131 072; max., dependent on the System Expansion Card used |
Outputs | 131 072; max., dependent on the System Expansion Card used |
— of which central | 131 072; max., dependent on the System Expansion Card used |
Analog channels |
Inputs | 8 192; max., dependent on the System Expansion Card used |
— of which central | 8 192; max., dependent on the System Expansion Card used |
Outputs | 8 192; max., dependent on the System Expansion Card used |
— of which central | 8 192; max., dependent on the System Expansion Card used |
Hardware configuration |
Number of expansion units, max. | 21; S7-400 expansion devices |
connectable OPs | 119 |
Multicomputing | No |
Interface modules |
Number of connectable IMs (total), max. | 6 |
Number of connectable IM 460s, max. | 6 |
Number of connectable IM 463s, max. | 4; Single mode only |
Number of DP masters |
integrated | 1 |
via CP | 10; CP 443-5 Extended |
Number of IO Controllers |
integrated | 2 |
via CP | 0 |
Number of operable FMs and CPs (recommended) |
PROFIBUS and Ethernet CPs | 11; Of which max. 10 CP as DP master |
Slots |
required slots | 2 |
Time of day |
Clock |
Hardware clock (real-time) | Yes |
retentive and synchronizable | Yes |
Resolution | 1 ms |
Deviation per day (buffered), max. | 1.7 s; Power off |
Deviation per day (unbuffered), max. | 8.6 s; Power on |
Operating hours counter |
Number | 16 |
Number/Number range | 0 to 15 |
Range of values | SFCs 2, 3 and 4: 0 to 32767 hours SFC 101: 0 to 2^31 - 1 hours |
Granularity | 1 h |
retentive | Yes |
Clock synchronization |
supported | Yes |
to DP, master | Yes |
to DP, slave | Yes |
in AS, master | Yes |
in AS, slave | Yes |
on Ethernet via NTP | Possible as client and master/slave via SIMATIC process |
Interfaces |
Number of PROFINET interfaces | 2 |
Number of RS 485 interfaces | 1; PROFIBUS DP |
Number of other interfaces | 2; 2x synchronization |
1. Interface |
Interface type | Integrated |
Physics | RS 485 / PROFIBUS |
Isolated | Yes |
Power supply to interface (15 to 30 V DC), max. | 150 mA |
Number of connection resources | 16 |
Protocols |
PROFIBUS DP master | Yes |
PROFIBUS DP slave | No |
PROFIBUS DP master |
Number of connections, max. | 16 |
Transmission rate, max. | 12 Mbit/s |
Number of DP slaves, max. | 96 |
Number of slots per interface, max. | 1 632 |
Services |
— PG/OP communication | Yes |
— Routing | Yes; S7 routing |
— Global data communication | No |
— S7 basic communication | No |
— S7 communication | Yes |
— S7 communication, as client | Yes |
— S7 communication, as server | Yes |
— Equidistance | No |
— Isochronous mode | No |
— SYNC/FREEZE | No |
— Activation/deactivation of DP slaves | Yes; Approved for stand-alone operation only, not in conjunction with CiR (Configuration in Run) |
— Direct data exchange (slave-to-slave communication) | No |
— DPV1 | Yes |
Address area |
— Inputs, max. | 6 kbyte; up to 2 800 IOs (channels) |
— Outputs, max. | 6 kbyte; up to 2 800 IOs (channels) |
User data per DP slave |
— User data per DP slave, max. | 244 byte |
— Inputs, max. | 244 byte |
— Outputs, max. | 244 byte |
— Slots, max. | 244 |
— per slot, max. | 128 byte |
2. Interface |
Interface type | PROFINET |
Physics | Ethernet RJ45 |
Isolated | Yes |
automatic detection of transmission rate | Yes; Autosensing |
Autonegotiation | Yes |
Autocrossing | Yes |
System redundancy | Yes |
Redundant subnetworks | Yes |
Change of IP address at runtime, supported | No |
Number of connection resources | 120 |
Interface types |
Number of ports | 2 |
integrated switch | Yes |
Media redundancy |
supported | Yes |
Switchover time on line break, typ. | < 200 ms |
Number of stations in the ring, max. | 50 |
Protocols |
PROFINET IO Controller | Yes |
PROFINET IO Device | No |
PROFINET CBA | No |
Open IE communication | Yes |
Web server | No |
PROFINET IO Controller |
Transmission rate, max. | 100 Mbit/s |
Services |
— PG/OP communication | Yes |
— S7 routing | Yes |
— S7 communication | Yes |
— Open IE communication | Yes |
— Shared device | No; however, usable as part of S7 |
— Prioritized startup | No |
— Number of connectable IO Devices, max. | 250 |
— Number of connectable IO Devices for RT, max. | 250 |
— of which in line, max. | 250 |
— Activation/deactivation of IO Devices | Yes; Approved for stand-alone operation only, not in conjunction with CiR (Configuration in Run) |
— IO Devices changing during operation (partner ports), supported | No |
— Device replacement without swap medium | Yes |
— Send cycles | 250 µs, 500 µs, 1 ms, 2 ms, 4 ms |
— Updating time | 250 µs to 512 ms, minimum value depends on the number of configured user data and the configured single or redundant mode |
Address area |
— Inputs, max. | 8 kbyte; up to 3 800 IOs (channels) |
— Outputs, max. | 8 kbyte; up to 3 800 IOs (channels) |
— User data consistency, max. | 1 024 byte |
Open IE communication |
Number of connections, max. | 118 |
Local port numbers used at the system end | 0, 20, 21, 25, 102, 135, 161, 34962, 34963, 34964, 65532, 65533, 65534, 65535 |
Keep-alive function, supported | Yes |
3. Interface |
Interface type | PROFINET |
Physics | Ethernet RJ45 |
Isolated | Yes |
automatic detection of transmission rate | Yes; Autosensing |
Autonegotiation | Yes |
Autocrossing | Yes |
System redundancy | Yes |
Redundant subnetworks | Yes |
Number of connection resources | 120 |
Interface types |
Number of ports | 2 |
integrated switch | Yes |
Media redundancy |
supported | Yes |
Switchover time on line break, typ. | < 200 ms |
Number of stations in the ring, max. | 50 |
Protocols |
PROFINET IO Controller | Yes |
PROFINET IO Device | No |
PROFINET CBA | No |
Open IE communication | Yes |
Web server | No |
PROFINET IO Controller |
Transmission rate, max. | 100 Mbit/s |
Services |
— PG/OP communication | Yes |
— S7 routing | Yes |
— S7 communication | Yes |
— Open IE communication | Yes |
— Shared device | No; however, usable as part of S7 |
— Prioritized startup | No |
— Number of connectable IO Devices, max. | 250 |
— Number of connectable IO Devices for RT, max. | 250 |
— of which in line, max. | 250 |
— Activation/deactivation of IO Devices | Yes; Approved for stand-alone operation only, not in conjunction with CiR (Configuration in Run) |
— IO Devices changing during operation (partner ports), supported | No |
— Device replacement without swap medium | Yes |
— Send cycles | 250 µs, 500 µs, 1 ms, 2 ms, 4 ms |
— Updating time | 250 µs to 512 ms, minimum value depends on the number of configured user data and the configured single or redundant mode |
Address area |
— Inputs, max. | 8 kbyte; up to 3 800 IOs (channels) |
— Outputs, max. | 8 kbyte; up to 3 800 IOs (channels) |
— User data consistency, max. | 1 024 byte |
Open IE communication |
Number of connections, max. | 118 |
Local port numbers used at the system end | 0, 20, 21, 25, 102, 135, 161, 34962, 34963, 34964, 65532, 65533, 65534, 65535 |
Keep-alive function, supported | Yes |
4. Interface |
Interface type | Pluggable synchronization submodule (FO) |
Plug-in interface modules | Synchronization module 6ES7960-1AA06-0XA0, 6ES7960-1AB06-0XA0 or 6ES7960-1AA08-0XA0 |
5. Interface |
Interface type | Pluggable synchronization submodule (FO) |
Plug-in interface modules | Synchronization module 6ES7960-1AA06-0XA0, 6ES7960-1AB06-0XA0 or 6ES7960-1AA08-0XA0 |
Protocols |
Supports protocol for PROFINET IO | Yes |
PROFINET CBA | No |
PROFIsafe | Yes |
PROFIBUS | Yes |
AS-Interface | Yes; Via add-on |
SIMATIC communication |
S7 routing | Yes |
Open IE communication |
TCP/IP | Yes; via integrated PROFINET interface and loadable FBs |
— Number of connections, max. | 118 |
— Data length, max. | 32 kbyte |
— several passive connections per port, supported | Yes |
ISO-on-TCP (RFC1006) | Yes; Via integrated PROFINET interface or CP 443-1 and loadable FBs |
— Number of connections, max. | 118 |
— Data length, max. | 32 kbyte; 1452 bytes via CP 443-1 Adv. |
UDP | Yes; via integrated PROFINET interface and loadable FBs |
— Number of connections, max. | 118 |
— Data length, max. | 1 472 byte |
Further protocols |
Foundation Fieldbus | Yes; via DP/FF Link |
MODBUS | Yes; Via add-on |
Communication functions |
PG/OP communication | Yes |
Number of connectable OPs without message processing | 119 |
Number of connectable OPs with message processing | 119; When using Alarm_S/SQ and Alarm_D/DQ |
Data record routing | Yes |
S7 communication |
supported | Yes |
as server | Yes |
as client | Yes |
User data per job, max. | 64 kbyte |
User data per job (of which consistent), max. | 462 byte; 1 variable |
S5 compatible communication |
supported | Yes; via CP and FC AG_SEND and FC AG_RECV |
User data per job, max. | 8 kbyte |
User data per job (of which consistent), max. | 240 byte |
Number of simultaneous AG-SEND/AG-RECV orders per CPU, max. | 64/64 |
Standard communication (FMS) |
supported | Yes; Via CP and loadable FB |
Number of connections |
overall | 120 |
usable for PG communication | |
— reserved for PG communication | 1 |
usable for OP communication | |
— reserved for OP communication | 1 |
S7 message functions |
Number of login stations for message functions, max. | 119; Max. 119 with Alarm_S and Alarm_D (OPs); max. 12 with Alarm_8 and Alarm_P (e.g. WinCC) |
Program alarms | Yes |
Process diagnostic messages | Yes |
simultaneously active Alarm-S blocks, max. | 1 000; Simultaneously active alarm_S/SQ blocks or alarm_D/DQ blocks |
Alarm 8-blocks | Yes |
Number of instances for alarm 8 and S7 communication blocks, max. | 10 000 |
preset, max. | 10 000 |
Process control messages | Yes |
Number of archives that can log on simultaneously (SFB 37 AR_SEND) | 64 |
Test commissioning functions |
Status block | Yes |
Single step | Yes |
Number of breakpoints | 4 |
Status/control |
Status/control variable | Yes |
Variables | Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters |
Number of variables, max. | 70 |
Diagnostic buffer |
present | Yes |
Number of entries, max. | 3 200 |
Service data |
can be read out | Yes |
Standards, approvals, certificates |
CE mark | Yes |
CSA approval | Yes |
UL approval | Yes |
cULus | Yes |
FM approval | Yes |
RCM (formerly C-TICK) | Yes |
KC approval | Yes |
EAC (formerly Gost-R) | Yes |
Use in hazardous areas |
ATEX | ATEX II 3G Ex nA IIC T4 Gc |
Ambient conditions |
Ambient temperature during operation |
min. | 0 °C |
max. | 70 °C |
Configuration |
Programming |
Command set | see instruction list |
Nesting levels | 7 |
Access to consistent data in process image | Yes |
System functions (SFC) | see instruction list |
System function blocks (SFB) | see instruction list |
Programming language |
— SCL | Yes |
— CFC | Yes |
Number of simultaneously active SFCs |
— RD_REC | 8; SFC 59; per interface |
— WR_REC | 8; SFC 58; per interface |
— WR_PARM | 8; SFC 55; per interface |
— PARM_MOD | 1; SFC 57; per interface |
— WR_DPARM | 2; SFC 56; per interface |
— DPNRM_DG | 8; SFC 13; per interface |
— RDSYSST | 8; SFC 51 |
— DP_TOPOL | 1; SFC 103; per interface |
Number of simultaneously active SFBs |
— RDREC | 8; SFB 52; per interface, but not more than 32 across all external interfaces |
— WRREC | 8; SFB 53; per interface, but not more than 32 across all external interfaces |
Know-how protection |
User program protection/password protection | Yes |
Block encryption | Yes; With S7 block Privacy |
Dimensions |
Width | 50 mm |
Height | 290 mm |
Depth | 219 mm |
Weights |
Weight, approx. | 1.1 kg |
last modified: | 03/13/2019 |