| SIMATIC S7, analog output SM 332, isolated, 4 AA; 0/4 to 20 mA, 20-pole, for signals from the hazardous area, diagnostics-capable, PTB tested |
Supply voltage |
Load voltage L+ |
Rated value (DC) | 24 V |
Reverse polarity protection | Yes |
Input current |
from load voltage L+ (without load), max. | 200 mA |
from backplane bus 5 V DC, max. | 80 mA |
Power loss |
Power loss, typ. | 4 W |
Analog outputs |
Number of analog outputs | 4 |
Voltage output, short-circuit protection | Yes |
Voltage output, short-circuit current, max. | 70 mA |
Current output, no-load voltage, max. | 14 V |
Output ranges, current |
0 to 20 mA | Yes |
4 mA to 20 mA | Yes |
Connection of actuators |
for current output two-wire connection | Yes |
Load impedance (in rated range of output) |
with current outputs, max. | 500 Ω |
Cable length |
shielded, max. | 200 m |
Analog value generation for the outputs |
Integration and conversion time/resolution per channel |
Resolution with overrange (bit including sign), max. | 15 bit |
Basic conversion time (ms) | 2.5 ms |
Errors/accuracies |
Operational error limit in overall temperature range |
Current, relative to output range, (+/-) | 0.55 % |
Basic error limit (operational limit at 25 °C) |
Current, relative to output range, (+/-) | 0.2 % |
Interrupts/diagnostics/status information |
Diagnostics function | Yes |
Diagnostic messages |
Diagnostic information readable | Yes |
Overrange | Yes |
Wire-break in actuator cable | Yes |
Diagnostics indication LED |
Group error SF (red) | Yes |
Channel fault indicator F (red) | Yes |
Ex(i) characteristics |
Module for Ex(i) protection | Yes |
Maximum values of output circuits (per channel) |
Co (permissible external capacity), max. | 850 nF |
Io (short-circuit current), max. | 70 mA |
Lo (permissible external inductivity), max. | 6.6 mH |
Po (power of load), max. | 440 mW |
Uo (output no-load voltage), max. | 14 V |
Potential separation |
Potential separation analog outputs |
Potential separation analog outputs | Yes |
Permissible potential difference |
between the outputs (UCM) | 60 V DC/30 V AC when used in the hazardous area; 400 V DC/250 V AC when used in NON-hazardous area |
Between the outputs and MANA (UCM) | 60 V DC/30 V AC when used in the hazardous area; 400 V DC/250 V AC when used in NON-hazardous area |
Standards, approvals, certificates |
Use in hazardous areas |
Type of protection acc. to EN 50020 (CENELEC) | [EEx ib] IIC |
Type of protection acc. to FM | Class I, Division 2, Group A, B, C, D T4 |
Test number PTB | Ex-96.D.2026X |
Ambient conditions |
Ambient temperature during operation |
max. | 60 °C |
Connection method |
required front connector | 20-pin |
Weights |
Weight, approx. | 280 g |
last modified: | 03/04/2019 |