6ES7321-1CH00-0AA0 SM321, 16 DI, AC/DC 24-48V, 1ch/common
From SIEMENS
SIMATIC S7-300, Digital input SM 321, isolated, 16 DI, 24-48 V AC/DC with single rooting, 1x 40-pole | ||
Supply voltage | ||
Load voltage L+ | ||
Rated value (DC) | 24 V | |
permissible range, lower limit (DC) | 24 V | |
permissible range, upper limit (DC) | 48 V | |
Load voltage L1 | ||
Rated value (AC) | 24 V | |
permissible range, lower limit (AC) | 24 V | |
permissible range, upper limit (AC) | 48 V | |
Input current | ||
from backplane bus 5 V DC, max. | 100 mA | |
Power loss | ||
Power loss, typ. | 1.5 W; at 24 V; 2,8 W at 48 V | |
Digital inputs | ||
Number of digital inputs | 16 | |
Input characteristic curve in accordance with IEC 61131, type 1 | Yes | |
Number of simultaneously controllable inputs | ||
horizontal installation | ||
— up to 40 °C, max. | 16 | |
— up to 60 °C, max. | 16 | |
vertical installation | ||
— up to 40 °C, max. | 16 | |
Input voltage | ||
Type of input voltage | AC/DC | |
Rated value (DC) | 24 V; DC 24 or 48 V | |
Rated value (AC) | 24 V; 24 V AC or 48 V AC (0 ... 63 Hz) | |
for signal "0" | -5V AC to +5V AC | |
for signal "1" | 14V AC to 60V AC | |
Input current | ||
for signal "1", typ. | 2.7 mA | |
Input delay (for rated value of input voltage) | ||
for standard inputs | ||
— parameterizable | No | |
— at "0" to "1", min. | 16 ms | |
— at "0" to "1", max. | 16 ms | |
— at "1" to "0", max. | 16 ms | |
Cable length | ||
shielded, max. | 1 000 m | |
unshielded, max. | 600 m | |
Encoder | ||
Connectable encoders | ||
2-wire sensor | Yes | |
— permissible quiescent current (2-wire sensor), max. | 1 mA | |
Isochronous mode | ||
Isochronous operation (application synchronized up to terminal) | No | |
Interrupts/diagnostics/status information | ||
Diagnostics function | No | |
Alarms | ||
Diagnostic alarm | No | |
Hardware interrupt | No | |
Diagnostics indication LED | ||
Group error SF (red) | No | |
Status indicator digital input (green) | Yes | |
Potential separation | ||
Potential separation digital inputs | ||
between the channels | Yes | |
between the channels, in groups of | 1 | |
between the channels and backplane bus | Yes; Optocoupler | |
Permissible potential difference | ||
between different circuits | 170 V DC/120 V AC | |
Isolation | ||
Isolation tested with | 1500 V AC | |
Connection method | ||
required front connector | 40-pin | |
Dimensions | ||
Width | 40 mm | |
Height | 125 mm | |
Depth | 120 mm | |
Weights | ||
Weight, approx. | 260 g | |