| ***Spare part*** SIMATIC S7-300, CPU 313C-2 PTP Compact CPU with MPI, 16 DI/16 DO, 3 high-speed counters (30 kHz), integrated interface RS485, Integr. power supply 24 V DC, work memory 64 KB, Front connector (1x 40-pole) and Micro Memory Card required |
General information |
HW functional status | 01 |
Firmware version | V2.6 |
Engineering with |
Programming package | STEP 7 V5.3 SP2 or higher with HW update |
Supply voltage |
Rated value (DC) | |
24 V DC | Yes |
permissible range, lower limit (DC) | 20.4 V |
permissible range, upper limit (DC) | 28.8 V |
external protection for power supply lines (recommendation) | Miniature circuit breaker, type C; min. 2 A; miniature circuit breaker type B, min. 4 A |
Load voltage L+ |
Rated value (DC) | 24 V |
permissible range, lower limit (DC) | 20.4 V |
permissible range, upper limit (DC) | 28.8 V |
Digital inputs |
— Rated value (DC) | 24 V |
— Reverse polarity protection | Yes |
Digital outputs |
— Rated value (DC) | 24 V |
— Reverse polarity protection | No |
Input current |
Current consumption (rated value) | 700 mA |
Current consumption (in no-load operation), typ. | 100 mA |
Inrush current, typ. | 11 A |
I²t | 0.7 A²·s |
Digital inputs |
from load voltage L+ (without load), max. | 70 mA |
Digital outputs |
from load voltage L+, max. | 100 mA |
Power loss |
Power loss, typ. | 10 W |
Memory |
Work memory |
integrated | 64 kbyte |
expandable | No |
Load memory |
Plug-in (MMC) | Yes |
Plug-in (MMC), max. | 8 Mbyte |
Data management on MMC (after last programming), min. | 10 y |
Backup |
present | Yes; Guaranteed by MMC (maintenance-free) |
without battery | Yes; Program and data |
CPU processing times |
for bit operations, typ. | 0.1 µs |
for bit operations, max. | 0.2 µs |
for word operations, typ. | 0.2 µs |
for fixed point arithmetic, typ. | 2 µs |
for floating point arithmetic, typ. | 3 µs |
CPU-blocks |
Number of blocks (total) | 1 024; (DBs, FCs, FBs); the maximum number of loadable blocks can be reduced by the MMC used. |
DB |
Number, max. | 511; Number range: 1 to 511 |
Size, max. | 16 kbyte |
FB |
Number, max. | 1 024; Number range: 0 to 2047 |
Size, max. | 16 kbyte |
FC |
Number, max. | 1 024; Number range: 0 to 2047 |
Size, max. | 16 kbyte |
OB |
Size, max. | 16 kbyte |
Number of free cycle OBs | 1; OB 1 |
Number of time alarm OBs | 1; OB 10 |
Number of delay alarm OBs | 1; OB 20 |
Number of cyclic interrupt OBs | 1; OB 35 |
Number of process alarm OBs | 1; OB 40 |
Number of startup OBs | 1; OB 100 |
Number of asynchronous error OBs | 4; OB 80, 82, 85, 87 |
Number of synchronous error OBs | 2; OB 121, 122 |
Nesting depth |
per priority class | 8 |
additional within an error OB | 4 |
Counters, timers and their retentivity |
S7 counter |
Number | 256 |
Retentivity |
— adjustable | Yes |
— lower limit | 0 |
— upper limit | 255 |
— preset | 8 |
Counting range |
— lower limit | 0 |
— upper limit | 999 |
IEC counter |
present | Yes |
Type | SFB |
Number | Unlimited (limited only by RAM capacity) |
S7 times |
Number | 256 |
Retentivity |
— adjustable | Yes |
— lower limit | 0 |
— upper limit | 255 |
— preset | No retentivity |
Time range |
— lower limit | 10 ms |
— upper limit | 9 990 s |
IEC timer |
present | Yes |
Type | SFB |
Number | Unlimited (limited only by RAM capacity) |
Data areas and their retentivity |
retentive data area in total | all |
Flag |
Number, max. | 256 byte |
Retentivity available | Yes; MB 0 to MB 255 |
Retentivity preset | MB 0 to MB 15 |
Number of clock memories | 8; 1 memory byte |
Data blocks |
Retentivity adjustable | Yes; via non-retain property on DB |
Retentivity preset | Yes |
Local data |
per priority class, max. | 510 byte |
Address area |
I/O address area |
Inputs | 1 kbyte |
Outputs | 1 kbyte |
of which distributed |
— Inputs | none |
— Outputs | none |
Process image |
Inputs | 128 byte |
Outputs | 128 byte |
Default addresses of the integrated channels |
— Digital inputs | 124.0 to 125.7 |
— Digital outputs | 124.0 to 125.7 |
Digital channels |
Inputs | 1 008 |
— of which central | 1 008 |
Outputs | 1 008 |
— of which central | 1 008 |
Analog channels |
Inputs | 248 |
— of which central | 248 |
Outputs | 248 |
— of which central | 248 |
Hardware configuration |
Number of expansion units, max. | 3 |
Number of DP masters |
integrated | No |
via CP | 4 |
Number of operable FMs and CPs (recommended) |
FM | 8 |
CP, PtP | 8 |
CP, LAN | 6 |
Rack |
Racks, max. | 4 |
Modules per rack, max. | 8; In rack 3 max. 7 |
Time of day |
Clock |
Hardware clock (real-time) | Yes |
retentive and synchronizable | Yes |
Backup time | 6 wk; At 40 °C ambient temperature |
Deviation per day, max. | 10 s |
Operating hours counter |
Number | 1 |
Number/Number range | 0 |
Range of values | 0 to 2^31 hours (when using SFC 101) |
Granularity | 1 h |
retentive | Yes; Must be restarted at each restart |
Clock synchronization |
supported | Yes |
to MPI, master | Yes |
to MPI, slave | Yes |
in AS, master | Yes |
Digital inputs |
Number of digital inputs | 16 |
of which inputs usable for technological functions | 12 |
integrated channels (DI) | 16 |
Input characteristic curve in accordance with IEC 61131, type 1 | Yes |
Number of simultaneously controllable inputs |
horizontal installation |
— up to 40 °C, max. | 16 |
— up to 60 °C, max. | 8 |
vertical installation |
— up to 40 °C, max. | 8 |
Input voltage |
Rated value (DC) | 24 V |
for signal "0" | -3 to +5V |
for signal "1" | +15 to +30V |
Input current |
for signal "1", typ. | 9 mA |
Input delay (for rated value of input voltage) |
for standard inputs |
— parameterizable | Yes; 0.1 / 0.3 / 3 / 15 ms |
— Rated value | 3 ms |
for technological functions |
— at "0" to "1", max. | 16 µs |
Cable length |
shielded, max. | 1 000 m; 100 m for technological functions |
unshielded, max. | 600 m; For technological functions: No |
for technological functions |
— shielded, max. | 100 m |
— unshielded, max. | not allowed |
Digital outputs |
Number of digital outputs | 16 |
of which high-speed outputs | 4 |
integrated channels (DO) | 16 |
Short-circuit protection | Yes; Clocked electronically |
Response threshold, typ. | 1 A |
Limitation of inductive shutdown voltage to | L+ (-48 V) |
Controlling a digital input | Yes |
Switching capacity of the outputs |
on lamp load, max. | 5 W |
Load resistance range |
lower limit | 48 Ω |
upper limit | 4 kΩ |
Output voltage |
for signal "1", min. | L+ (-0.8 V) |
Output current |
for signal "1" rated value | 500 mA |
for signal "1" permissible range, min. | 5 mA |
for signal "1" permissible range, max. | 0.6 A |
for signal "1" minimum load current | 5 mA |
for signal "0" residual current, max. | 0.5 mA |
Parallel switching of two outputs |
for uprating | No |
for redundant control of a load | Yes |
Switching frequency |
with resistive load, max. | 100 Hz |
with inductive load, max. | 0.5 Hz |
on lamp load, max. | 100 Hz |
of the pulse outputs, with resistive load, max. | 2.5 kHz |
Total current of the outputs (per group) |
horizontal installation |
— up to 40 °C, max. | 3 A |
— up to 60 °C, max. | 2 A |
vertical installation |
— up to 40 °C, max. | 2 A |
Cable length |
shielded, max. | 1 000 m |
unshielded, max. | 600 m |
Analog inputs |
integrated channels (AI) | none |
Analog outputs |
integrated channels (AO) | none |
Encoder |
Connectable encoders |
2-wire sensor | Yes |
— permissible quiescent current (2-wire sensor), max. | 1.5 mA |
Interfaces |
Number of industrial Ethernet interfaces | 0 |
Number of PROFINET interfaces | 0 |
Number of RS 485 interfaces | 1; MPI |
Number of RS 422 interfaces | 1; RS 422 / 485 combined |
MPI |
Cable length, max. | 50 m; without repeater |
Point-to-point connection |
Cable length, max. | 1 200 m |
Integrated protocol driver |
— 3964 (R) | Yes |
— ASCII | Yes |
— RK512 | No |
Transmission rate, RS 422/485 |
— with 3964 (R) protocol, max. | 38.4 kbit/s half duplex; 19.2 kbit/s full duplex |
— with ASCII protocol, max. | 38.4 kbit/s half duplex; 19.2 kbit/s full duplex |
1. Interface |
Interface type | Integrated RS 485 interface |
Physics | RS 485 |
Isolated | No |
Power supply to interface (15 to 30 V DC), max. | 200 mA |
Protocols |
MPI | Yes |
PROFIBUS DP master | No |
PROFIBUS DP slave | No |
Point-to-point connection | No |
MPI |
Number of connections | 8 |
Transmission rate, max. | 187.5 kbit/s |
Services |
— PG/OP communication | Yes |
— Routing | No |
— Global data communication | Yes |
— S7 basic communication | Yes |
— S7 communication | Yes |
— S7 communication, as client | No |
— S7 communication, as server | Yes |
2. Interface |
Interface type | Integrated RS 422/ 485 interface |
Physics | RS 422 / 485 (X.27) |
Isolated | Yes |
Power supply to interface (15 to 30 V DC), max. | No |
Number of connection resources | none |
Protocols |
MPI | No |
PROFINET IO Controller | No |
PROFINET CBA | No |
PROFIBUS DP master | No |
PROFIBUS DP slave | No |
Point-to-point connection | Yes |
Point-to-point connection |
Transmission rate, max. | 38.4 kbit/s half duplex; 19.2 kbit/s full duplex |
Interface controllable from the user program | Yes |
Interface can trigger alarm/interrupt in the user program | Yes; Message on break - identification |
Communication functions |
PG/OP communication | Yes |
Global data communication |
supported | Yes |
Number of GD loops, max. | 4 |
Number of GD packets, max. | 4 |
Number of GD packets, transmitter, max. | 4 |
Number of GD packets, receiver, max. | 4 |
Size of GD packets, max. | 22 byte |
Size of GD packet (of which consistent), max. | 22 byte |
S7 basic communication |
supported | Yes; Server |
User data per job, max. | 76 byte |
User data per job (of which consistent), max. | 76 byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET as server) |
S7 communication |
supported | Yes |
as server | Yes |
as client | Yes; Via CP and loadable FB |
User data per job, max. | 180 byte; With PUT/GET |
User data per job (of which consistent), max. | 64 byte |
S5 compatible communication |
supported | Yes; via CP and loadable FC |
Number of connections |
overall | 8 |
usable for PG communication | 7 |
— reserved for PG communication | 1 |
— adjustable for PG communication, min. | 1 |
— adjustable for PG communication, max. | 7 |
usable for OP communication | 7 |
— reserved for OP communication | 1 |
— adjustable for OP communication, min. | 1 |
— adjustable for OP communication, max. | 7 |
usable for S7 basic communication | 4 |
— reserved for S7 basic communication | 0 |
— adjustable for S7 basic communication, min. | 0 |
— adjustable for S7 basic communication, max. | 4 |
usable for routing | No |
S7 message functions |
Number of login stations for message functions, max. | 8; Depending on the configured connections for PG/OP and S7 basic communication |
Process diagnostic messages | Yes |
simultaneously active Alarm-S blocks, max. | 20 |
Test commissioning functions |
Status block | Yes |
Single step | Yes |
Number of breakpoints | 2 |
Status/control |
Status/control variable | Yes |
Variables | Inputs, outputs, memory bits, DB, times, counters |
Number of variables, max. | 30 |
— of which status variables, max. | 30 |
— of which control variables, max. | 14 |
Forcing |
Forcing | Yes |
Forcing, variables | Inputs, outputs |
Number of variables, max. | 10 |
Diagnostic buffer |
present | Yes |
Number of entries, max. | 100 |
Interrupts/diagnostics/status information |
Diagnostics indication LED |
Status indicator digital input (green) | Yes |
Status indicator digital output (green) | Yes |
Integrated Functions |
Number of counters | 3; 3 channels (see "Technological Functions" manual) |
Counting frequency (counter) max. | 30 kHz |
Frequency measurement | Yes |
Number of frequency meters | 3; 3 channels up to max. 30 kHz (see "Technological Functions" manual) |
controlled positioning | No |
integrated function blocks (closed-loop control) | PID controller (see "Technological Functions" manual) |
PID controller | Yes |
Number of pulse outputs | 3; 3 channels pulse width modulation up to max. 2.5 kHz (see "Technological Functions" manual) |
Limit frequency (pulse) | 2.5 kHz |
Potential separation |
Potential separation digital inputs |
Potential separation digital inputs | Yes |
between the channels | No |
between the channels and backplane bus | Yes |
Potential separation digital outputs |
Potential separation digital outputs | Yes |
between the channels | Yes |
between the channels, in groups of | 8 |
between the channels and backplane bus | Yes |
Permissible potential difference |
between different circuits | 75 V DC/60 V AC |
Isolation |
Isolation tested with | 600 V DC |
Configuration |
Configuration software |
STEP 7 | Yes; V5.2 SP1 with HW update |
Programming |
Command set | see instruction list |
Nesting levels | 8 |
System functions (SFC) | see instruction list |
System function blocks (SFB) | see instruction list |
Programming language |
— LAD | Yes |
— FBD | Yes |
— STL | Yes |
— SCL | Yes |
— GRAPH | Yes |
— HiGraph® | Yes |
Know-how protection |
User program protection/password protection | Yes |
Dimensions |
Width | 120 mm |
Height | 125 mm |
Depth | 130 mm |
Weights |
Weight, approx. | 566 g |
last modified: | 03/13/2019 |