6ES7313-5BE01-0AB0
CPU313C, 24DI/16DO/4AI/2AO, 32KB

From SIEMENS

SIMATIC S7-300, CPU 313C COMPACT CPU WITH MPI, 24 DI/16 DO, 4AI, 2AO 1 PT100, 3 FAST COUNTERS (30 KHZ), INTEGRATED 24V DC POWER SUPPLY, 32 KBYTE WORKING MEMORY, FRONT CONNECTOR (2 X 40PIN) AND MICRO MEMORY CARD REQUIRED
General information
HW functional status01
Firmware versionV2.0.0
Engineering with
Programming packageSTEP 7 V5.2 SP1 or higher
Supply voltage
Rated value (DC)
24 V DCYes
permissible range, lower limit (DC)20.4 V
permissible range, upper limit (DC)28.8 V
Load voltage L+
Rated value (DC)24 V
permissible range, lower limit (DC)20.4 V
permissible range, upper limit (DC)28.8 V
Input current
Current consumption (rated value)700 mA
Current consumption (in no-load operation), typ.150 mA
Inrush current, typ.11 A
Power loss
Power loss, typ.14 W
Memory
Work memory
integrated32 kbyte; For program and data
expandableNo
Load memory
Plug-in (MMC)Yes
Plug-in (MMC), max.8 Mbyte
Data management on MMC (after last programming), min.10 y
Backup
presentYes; Guaranteed by MMC (maintenance-free)
without batteryYes; Program and data
CPU processing times
for bit operations, typ.0.1 µs
for bit operations, max.0.2 µs
for word operations, typ.0.2 µs
for fixed point arithmetic, typ.2 µs
for floating point arithmetic, typ.3 µs
CPU-blocks
Number of blocks (total)1 024; (DBs, FCs, FBs OBs, SDBs); the maximum number of loadable blocks can be reduced by the MMC being used.
DB
Number, max.511; Number range: 1 to 511
Size, max.16 kbyte
FB
Number, max.512; Number range: 0 to 2047
Size, max.16 kbyte
FC
Number, max.512; Number range: 0 to 2047
Size, max.16 kbyte
OB
Number, max.see instruction list
Size, max.16 kbyte
Number of free cycle OBs1; OB 1
Number of time alarm OBs1; OB 10
Number of delay alarm OBs1; OB 20
Number of cyclic interrupt OBs1; OB 35
Number of process alarm OBs1; OB 40
Number of startup OBs1; OB 100
Number of asynchronous error OBs1; OB 80
Number of synchronous error OBs2; OB 121, 122
Nesting depth
per priority class8
additional within an error OB4
Counters, timers and their retentivity
S7 counter
Number256
Retentivity
— adjustableYes
— lower limit0
— upper limit256
Counting range
— lower limit0
— upper limit999
IEC counter
presentYes
TypeSFB
S7 times
Number256
Retentivity
— adjustableYes
— lower limit0
— upper limit256
— presetNo retentivity
Time range
— lower limit10 ms
— upper limit9 990 s
IEC timer
presentYes
TypeSFB
NumberUnlimited (limited only by RAM capacity)
Data areas and their retentivity
retentive data area in totalall
Flag
Number, max.256 byte
Retentivity availableYes; MB 0 to MB 255
Retentivity presetMB 0 to MB 15
Number of clock memories8; 1 memory byte
Data blocks
Retentivity adjustableNo
Retentivity presetYes
Local data
per priority class, max.510 byte
Address area
I/O address area
Inputs1 kbyte
Outputs1 kbyte
Process image
Inputs128 byte
Outputs128 byte
Default addresses of the integrated channels
— Digital inputs124.0 to 126.7
— Digital outputs124.0 to 125.7
— Analog inputs752 to 761
— Analog outputs752 to 755
Digital channels
Inputs992
— of which central992
Outputs992
— of which central992
Analog channels
Inputs248
— of which central248
Outputs124
— of which central248
Hardware configuration
Number of expansion units, max.3
Number of DP masters
integratednone
via CP4
Number of operable FMs and CPs (recommended)
FM8
CP, PtP8
CP, LAN6
Rack
Racks, max.4
Modules per rack, max.8; In rack 3 max. 7
Time of day
Clock
Hardware clock (real-time)Yes
retentive and synchronizableYes
Backup time6 wk; At 40 °C ambient temperature
Deviation per day, max.10 s
Operating hours counter
Number1
Number/Number range0
Range of values0 to 2^31 hours (when using SFC 101)
Granularity1 h
retentiveYes; Must be restarted at each restart
Clock synchronization
supportedYes
to MPI, masterYes
to MPI, slaveYes
in AS, masterYes
Digital inputs
Number of digital inputs24
integrated channels (DI)24
Input voltage
Rated value (DC)24 V
for signal "0"-3 to +5V
for signal "1"+15 to +30V
Input current
for signal "1", typ.8 mA
Input delay (for rated value of input voltage)
for standard inputs
— parameterizableYes; 0.1 / 0.3 / 3 / 15 ms
for technological functions
— at "0" to "1", max.16 µs
Cable length
shielded, max.1 000 m; 100 m for technological functions
unshielded, max.600 m
Digital outputs
Number of digital outputs16
integrated channels (DO)16
Short-circuit protectionYes; Clocked electronically
Limitation of inductive shutdown voltage toL+ (-48 V)
Output voltage
for signal "1", min.L+ (-0.8 V)
Output current
for signal "1" permissible range, max.500 mA
for signal "1" permissible range for 0 to 60 °C, max.500 mA
for signal "1" minimum load current5 mA
for signal "0" residual current, max.0.5 mA
Switching frequency
with resistive load, max.100 Hz
with inductive load, max.0.5 Hz
Total current of the outputs (per group)
all mounting positions
— up to 40 °C, max.8 A
— up to 60 °C, max.4 A
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Analog inputs
Number of analog inputs
For voltage/current measurement4
For resistance/resistance thermometer measurement1
integrated channels (AI)4+1
permissible input voltage for current input (destruction limit), max.5 V; Permanent
permissible input current for voltage input (destruction limit), max.0.5 mA; Permanent
Technical unit for temperature measurement adjustableYes; Degrees Celsius / degrees Fahrenheit / Kelvin
Input ranges
CurrentYes
Resistance thermometerYes
ResistanceYes
Input ranges (rated values), voltages
0 to +10 VYes
Input resistance (0 to 10 V)100 kΩ
Input ranges (rated values), currents
0 to 20 mAYes
Input resistance (0 to 20 mA)100 Ω
-20 mA to +20 mAYes
Input resistance (-20 mA to +20 mA)100 Ω
4 mA to 20 mAYes
Input resistance (4 mA to 20 mA)100 Ω
Input ranges (rated values), resistance thermometer
Pt 100Yes
Input resistance (Pt 100)10 MΩ
Input ranges (rated values), resistors
0 to 600 ohmsYes
Input resistance (0 to 600 ohms)10 MΩ
Analog outputs
Number of analog outputs2
integrated channels (AO)2
Output ranges, voltage
0 to 10 VYes
-10 V to +10 VYes
Output ranges, current
0 to 20 mAYes
-20 mA to +20 mAYes
4 mA to 20 mAYes
Analog value generation for the inputs
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.12 bit
Integration time, parameterizableYes; 2,5 / 16,6 / 20 ms
Analog value generation for the outputs
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.12 bit
Conversion time (per channel)1 ms
Encoder
Connectable encoders
2-wire sensorYes
— permissible quiescent current (2-wire sensor), max.1.5 mA
Errors/accuracies
Basic error limit (operational limit at 25 °C)
Voltage, relative to input range, (+/-)0.7 %
Current, relative to input range, (+/-)0.7 %
Resistance, relative to input range, (+/-)3 %
Resistance thermometer, relative to input range, (+/-)3 %
Voltage, relative to output range, (+/-)0.7 %
Current, relative to output range, (+/-)0.7 %
Interfaces
MPI
Cable length, max.50 m; without repeater
1. Interface
Interface typeIntegrated RS 485 interface
PhysicsRS 485
IsolatedNo
Power supply to interface (15 to 30 V DC), max.200 mA
Protocols
MPIYes
PROFIBUS DP masterNo
PROFIBUS DP slaveNo
Point-to-point connectionNo
MPI
Number of connections8
Transmission rate, max.187.5 kbit/s
Services
— PG/OP communicationYes
— RoutingNo
— Global data communicationYes
— S7 basic communicationYes
— S7 communicationYes
— S7 communication, as clientNo
— S7 communication, as serverYes
Communication functions
PG/OP communicationYes
Global data communication
supportedYes
Number of GD loops, max.4
Number of GD packets, max.4
Number of GD packets, transmitter, max.4
Number of GD packets, receiver, max.4
Size of GD packets, max.22 byte
Size of GD packet (of which consistent), max.22 byte
S7 basic communication
supportedYes
User data per job, max.76 byte
User data per job (of which consistent), max.76 byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET as server)
S7 communication
supportedYes
as serverYes
as clientYes; Via CP and loadable FB
User data per job, max.180 byte
User data per job (of which consistent), max.64 byte
S5 compatible communication
supportedYes; via CP and loadable FC
Number of connections
overall8
usable for PG communication7
— reserved for PG communication1
— adjustable for PG communication, min.1
— adjustable for PG communication, max.7
usable for OP communication7
— reserved for OP communication1
— adjustable for OP communication, min.1
— adjustable for OP communication, max.7
usable for S7 basic communication4
— reserved for S7 basic communication4
— adjustable for S7 basic communication, min.0
— adjustable for S7 basic communication, max.4
usable for routingNo
S7 message functions
Number of login stations for message functions, max.8; Depending on the configured connections for PG/OP and S7 basic communication
Process diagnostic messagesYes
simultaneously active Alarm-S blocks, max.20
Test commissioning functions
Status blockYes
Single stepYes
Number of breakpoints2
Status/control
Status/control variableYes
VariablesInputs, outputs, memory bits, DB, times, counters
Number of variables, max.30
— of which status variables, max.30
— of which control variables, max.14
Forcing
ForcingYes
Forcing, variablesInputs, outputs
Number of variables, max.10
Integrated Functions
Number of counters3; 3 channels (see "Technological Functions" manual)
Counting frequency (counter) max.30 kHz
Frequency measurementYes
Number of frequency meters3; 3 channels up to max. 30 kHz (see "Technological Functions" manual)
controlled positioningNo
integrated function blocks (closed-loop control)Yes; PID controller (see "Technological Functions" manual)
PID controllerYes
Number of pulse outputs3; 3 channels pulse width modulation up to max. 2.5 kHz (see "Technological Functions" manual)
Limit frequency (pulse)2.5 kHz
Potential separation
Potential separation digital inputs
Potential separation digital inputsYes
between the channels, in groups of16; and 8
between the channels and backplane busYes
Potential separation digital outputs
Potential separation digital outputsYes
between the channels, in groups of8
between the channels and backplane busYes
Potential separation analog inputs
Potential separation analog inputsYes; common for analog I/O
between the channels and backplane busYes
Potential separation analog outputs
Potential separation analog outputsYes; common for analog I/O
between the channels and backplane busYes
Configuration
Configuration software
STEP 7Yes; V5.1 SP2
Programming
Command setsee instruction list
Nesting levels8
System functions (SFC)see instruction list
System function blocks (SFB)see instruction list
Programming language
— LADYes
— FBDYes
— STLYes
— SCLYes
— GRAPHYes
— HiGraph®Yes
Know-how protection
User program protection/password protectionYes
Dimensions
Width120 mm
Height125 mm
Depth130 mm
Weights
Weight, approx.660 g
last modified:03/13/2019