| SIMATIC S7-300, CPU 313C COMPACT CPU WITH MPI, 24 DI/16 DO, 4AI, 2AO 1 PT100, 3 FAST COUNTERS (30 KHZ), INTEGRATED 24V DC POWER SUPPLY, 32 KBYTE WORKING MEMORY, MICRO MEMORY CARD REQUIRED |
Supply voltage |
Rated value (DC) | 24 V |
permissible range, lower limit (DC) | 20.4 V |
permissible range, upper limit (DC) | 28.8 V |
Load voltage L+ |
Rated value (DC) | 24 V |
permissible range, lower limit (DC) | 20.4 V |
permissible range, upper limit (DC) | 28.8 V |
Input current |
Current consumption (rated value) | 700 mA |
Inrush current, typ. | 11 A |
Power loss |
Power loss, typ. | 14 W |
Memory |
Work memory |
integrated | 32 kbyte; For program and data |
expandable | No |
Load memory |
expandable FEPROM | Yes; with Micro Memory Card (MMC) |
expandable FEPROM, max. | 4 Mbyte |
Backup |
present | Yes; Guaranteed by MMC (maintenance-free) |
without battery | Yes; Program and data |
CPU processing times |
for bit operations, typ. | 0.1 µs |
for bit operations, max. | 0.2 µs |
for word operations, typ. | 0.5 µs |
for fixed point arithmetic, typ. | 1 µs |
for floating point arithmetic, typ. | 15 µs |
CPU-blocks |
DB |
Number, max. | 127; DB 0 reserved |
Size, max. | 16 kbyte |
FB |
Number, max. | 128 |
Size, max. | 16 kbyte |
FC |
Number, max. | 128 |
Size, max. | 16 kbyte |
OB |
Size, max. | 16 kbyte |
Number of time alarm OBs | 1 |
Number of delay alarm OBs | 1 |
Number of cyclic interrupt OBs | 1 |
Number of process alarm OBs | 1 |
Nesting depth |
per priority class | 8 |
additional within an error OB | 4 |
Counters, timers and their retentivity |
S7 counter |
Number | 256 |
Retentivity |
— adjustable | Yes |
— lower limit | 0 |
— upper limit | 256 |
Counting range |
— lower limit | 1 |
— upper limit | 999 |
IEC counter |
present | Yes |
Type | SFB |
S7 times |
Number | 256 |
Retentivity |
— adjustable | Yes |
— lower limit | 0 |
— upper limit | 256 |
Time range |
— lower limit | 10 ms |
— upper limit | 9 990 s |
IEC timer |
present | Yes |
Type | SFB |
Data areas and their retentivity |
Flag |
Number, max. | 256 byte |
Retentivity available | Yes; MB 0 to MB 255 |
Address area |
I/O address area |
Inputs | 1 kbyte |
Outputs | 1 kbyte |
Process image |
Inputs | 128 byte |
Outputs | 128 byte |
Digital channels |
Inputs | 992 |
Outputs | 992 |
Analog channels |
Inputs | 248 |
Outputs | 124 |
Hardware configuration |
Number of expansion units, max. | 3 |
Number of DP masters |
via CP | 1 |
Number of operable FMs and CPs (recommended) |
FM | 8 |
CP, PtP | 4 |
CP, LAN | 2 |
Rack |
Modules per rack, max. | 31 |
Time of day |
Clock |
Hardware clock (real-time) | Yes |
retentive and synchronizable | Yes |
Operating hours counter |
Number | 1 |
Clock synchronization |
supported | Yes |
Digital inputs |
Number of digital inputs | 24 |
Input voltage |
Rated value (DC) | 24 V |
for signal "0" | -3 to +5V |
for signal "1" | +15 to +30V |
Input current |
for signal "1", typ. | 8 mA |
Input delay (for rated value of input voltage) |
for standard inputs |
— parameterizable | Yes; 0.1 / 0.3 / 3 / 15 ms |
— at "0" to "1", max. | 15 ms |
for technological functions |
— at "0" to "1", max. | 16 µs |
Cable length |
shielded, max. | 1 000 m; 100 m for technological functions |
unshielded, max. | 600 m |
Digital outputs |
Number of digital outputs | 16 |
Short-circuit protection | Yes; Clocked electronically |
Limitation of inductive shutdown voltage to | L+ (-48 V) |
Output voltage |
for signal "1", min. | L+ (-0.8 V) |
Output current |
for signal "1" permissible range for 0 to 60 °C, max. | 500 mA |
for signal "1" minimum load current | 5 mA |
for signal "0" residual current, max. | 0.5 mA |
Switching frequency |
with resistive load, max. | 100 Hz |
with inductive load, max. | 0.5 Hz |
Total current of the outputs (per group) |
all mounting positions |
— up to 40 °C, max. | 8 A |
— up to 60 °C, max. | 4 A |
Cable length |
shielded, max. | 1 000 m |
unshielded, max. | 600 m |
Analog inputs |
Number of analog inputs | 4 |
For voltage/current measurement | 4 |
For resistance/resistance thermometer measurement | 1 |
Input ranges |
Voltage | Yes |
Current | Yes |
Resistance thermometer | Yes |
Resistance | Yes |
Input ranges (rated values), voltages |
0 to +10 V | Yes |
Input ranges (rated values), currents |
0 to 20 mA | Yes |
-20 mA to +20 mA | Yes |
4 mA to 20 mA | Yes |
Input ranges (rated values), resistance thermometer |
Pt 100 | Yes |
Input ranges (rated values), resistors |
0 to 600 ohms | Yes |
Analog outputs |
Number of analog outputs | 2 |
Output ranges, voltage |
0 to 10 V | Yes |
-10 V to +10 V | Yes |
Output ranges, current |
0 to 20 mA | Yes |
-20 mA to +20 mA | Yes |
4 mA to 20 mA | Yes |
Analog value generation for the inputs |
Integration and conversion time/resolution per channel |
Resolution with overrange (bit including sign), max. | 12 bit |
Integration time, parameterizable | Yes; 2,5 / 16,6 / 20 ms |
Analog value generation for the outputs |
Integration and conversion time/resolution per channel |
Resolution with overrange (bit including sign), max. | 12 bit |
Conversion time (per channel) | 1 ms |
Encoder |
Connectable encoders |
2-wire sensor | Yes |
— permissible quiescent current (2-wire sensor), max. | 1.5 mA |
Errors/accuracies |
Basic error limit (operational limit at 25 °C) |
Voltage, relative to input range, (+/-) | 0.7 % |
Current, relative to input range, (+/-) | 0.7 % |
Resistance, relative to input range, (+/-) | 3 % |
Resistance thermometer, relative to input range, (+/-) | 3 % |
Voltage, relative to output range, (+/-) | 0.7 % |
Current, relative to output range, (+/-) | 0.7 % |
Interfaces |
MPI |
Cable length, max. | 50 m; without repeater |
1. Interface |
Isolated | No |
Protocols |
MPI | Yes |
PROFIBUS DP master | No |
PROFIBUS DP slave | No |
MPI |
Number of connections | 8 |
Transmission rate, max. | 187.5 kbit/s |
Services |
— PG/OP communication | Yes |
— Global data communication | Yes |
— S7 communication | Yes |
— S7 communication, as client | No |
— S7 communication, as server | Yes |
Communication functions |
PG/OP communication | Yes |
Global data communication |
Number of GD packets, transmitter, max. | 4 |
Number of GD packets, receiver, max. | 4 |
Size of GD packets, max. | 22 byte |
S7 basic communication |
supported | Yes |
User data per job, max. | 76 byte |
S7 communication |
supported | Yes |
as server | Yes |
as client | No |
User data per job, max. | 64 kbyte |
Number of connections |
overall | 8 |
usable for PG communication | 7 |
— reserved for PG communication | 1 |
— adjustable for PG communication, max. | 7 |
usable for OP communication | 7 |
— reserved for OP communication | 1 |
— adjustable for OP communication, max. | 7 |
usable for S7 basic communication | 4 |
— reserved for S7 basic communication | 4 |
— adjustable for S7 basic communication, max. | 4 |
S7 message functions |
Number of login stations for message functions, max. | 5 |
Integrated Functions |
Number of counters | 3 |
Counting frequency (counter) max. | 30 kHz |
Frequency measurement | Yes |
PID controller | Yes |
Number of pulse outputs | 3 |
Limit frequency (pulse) | 2.5 kHz |
Potential separation |
Potential separation digital inputs |
Potential separation digital inputs | Yes |
between the channels, in groups of | 16; 16 and 8 |
between the channels and backplane bus | Yes |
Potential separation digital outputs |
between the channels, in groups of | 8 |
between the channels and backplane bus | Yes |
Potential separation analog inputs |
Potential separation analog inputs | Yes; common for analog I/O |
between the channels and backplane bus | Yes |
Potential separation analog outputs |
Potential separation analog outputs | Yes |
Configuration |
Configuration software |
STEP 7 | Yes; V5.1 SP2 |
Programming |
Nesting levels | 8 |
Programming language |
— LAD | Yes |
— FBD | Yes |
— STL | Yes |
— SCL | Yes |
— GRAPH | Yes |
— HiGraph® | Yes |
Know-how protection |
User program protection/password protection | Yes |
Dimensions |
Width | 120 mm |
Height | 125 mm |
Depth | 130 mm |
Weights |
Weight, approx. | 660 g |
last modified: | 03/13/2019 |