6ES7313-5BE00-0AB0
CPU313C, 24DI/16DO, 4AI, 2AO, 32KB

From SIEMENS

SIMATIC S7-300, CPU 313C COMPACT CPU WITH MPI, 24 DI/16 DO, 4AI, 2AO 1 PT100, 3 FAST COUNTERS (30 KHZ), INTEGRATED 24V DC POWER SUPPLY, 32 KBYTE WORKING MEMORY, MICRO MEMORY CARD REQUIRED
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)20.4 V
permissible range, upper limit (DC)28.8 V
Load voltage L+
Rated value (DC)24 V
permissible range, lower limit (DC)20.4 V
permissible range, upper limit (DC)28.8 V
Input current
Current consumption (rated value)700 mA
Inrush current, typ.11 A
Power loss
Power loss, typ.14 W
Memory
Work memory
integrated32 kbyte; For program and data
expandableNo
Load memory
expandable FEPROMYes; with Micro Memory Card (MMC)
expandable FEPROM, max.4 Mbyte
Backup
presentYes; Guaranteed by MMC (maintenance-free)
without batteryYes; Program and data
CPU processing times
for bit operations, typ.0.1 µs
for bit operations, max.0.2 µs
for word operations, typ.0.5 µs
for fixed point arithmetic, typ.1 µs
for floating point arithmetic, typ.15 µs
CPU-blocks
DB
Number, max.127; DB 0 reserved
Size, max.16 kbyte
FB
Number, max.128
Size, max.16 kbyte
FC
Number, max.128
Size, max.16 kbyte
OB
Size, max.16 kbyte
Number of time alarm OBs1
Number of delay alarm OBs1
Number of cyclic interrupt OBs1
Number of process alarm OBs1
Nesting depth
per priority class8
additional within an error OB4
Counters, timers and their retentivity
S7 counter
Number256
Retentivity
— adjustableYes
— lower limit0
— upper limit256
Counting range
— lower limit1
— upper limit999
IEC counter
presentYes
TypeSFB
S7 times
Number256
Retentivity
— adjustableYes
— lower limit0
— upper limit256
Time range
— lower limit10 ms
— upper limit9 990 s
IEC timer
presentYes
TypeSFB
Data areas and their retentivity
Flag
Number, max.256 byte
Retentivity availableYes; MB 0 to MB 255
Address area
I/O address area
Inputs1 kbyte
Outputs1 kbyte
Process image
Inputs128 byte
Outputs128 byte
Digital channels
Inputs992
Outputs992
Analog channels
Inputs248
Outputs124
Hardware configuration
Number of expansion units, max.3
Number of DP masters
via CP1
Number of operable FMs and CPs (recommended)
FM8
CP, PtP4
CP, LAN2
Rack
Modules per rack, max.31
Time of day
Clock
Hardware clock (real-time)Yes
retentive and synchronizableYes
Operating hours counter
Number1
Clock synchronization
supportedYes
Digital inputs
Number of digital inputs24
Input voltage
Rated value (DC)24 V
for signal "0"-3 to +5V
for signal "1"+15 to +30V
Input current
for signal "1", typ.8 mA
Input delay (for rated value of input voltage)
for standard inputs
— parameterizableYes; 0.1 / 0.3 / 3 / 15 ms
— at "0" to "1", max.15 ms
for technological functions
— at "0" to "1", max.16 µs
Cable length
shielded, max.1 000 m; 100 m for technological functions
unshielded, max.600 m
Digital outputs
Number of digital outputs16
Short-circuit protectionYes; Clocked electronically
Limitation of inductive shutdown voltage toL+ (-48 V)
Output voltage
for signal "1", min.L+ (-0.8 V)
Output current
for signal "1" permissible range for 0 to 60 °C, max.500 mA
for signal "1" minimum load current5 mA
for signal "0" residual current, max.0.5 mA
Switching frequency
with resistive load, max.100 Hz
with inductive load, max.0.5 Hz
Total current of the outputs (per group)
all mounting positions
— up to 40 °C, max.8 A
— up to 60 °C, max.4 A
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Analog inputs
Number of analog inputs4
For voltage/current measurement4
For resistance/resistance thermometer measurement1
Input ranges
VoltageYes
CurrentYes
Resistance thermometerYes
ResistanceYes
Input ranges (rated values), voltages
0 to +10 VYes
Input ranges (rated values), currents
0 to 20 mAYes
-20 mA to +20 mAYes
4 mA to 20 mAYes
Input ranges (rated values), resistance thermometer
Pt 100Yes
Input ranges (rated values), resistors
0 to 600 ohmsYes
Analog outputs
Number of analog outputs2
Output ranges, voltage
0 to 10 VYes
-10 V to +10 VYes
Output ranges, current
0 to 20 mAYes
-20 mA to +20 mAYes
4 mA to 20 mAYes
Analog value generation for the inputs
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.12 bit
Integration time, parameterizableYes; 2,5 / 16,6 / 20 ms
Analog value generation for the outputs
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.12 bit
Conversion time (per channel)1 ms
Encoder
Connectable encoders
2-wire sensorYes
— permissible quiescent current (2-wire sensor), max.1.5 mA
Errors/accuracies
Basic error limit (operational limit at 25 °C)
Voltage, relative to input range, (+/-)0.7 %
Current, relative to input range, (+/-)0.7 %
Resistance, relative to input range, (+/-)3 %
Resistance thermometer, relative to input range, (+/-)3 %
Voltage, relative to output range, (+/-)0.7 %
Current, relative to output range, (+/-)0.7 %
Interfaces
MPI
Cable length, max.50 m; without repeater
1. Interface
IsolatedNo
Protocols
MPIYes
PROFIBUS DP masterNo
PROFIBUS DP slaveNo
MPI
Number of connections8
Transmission rate, max.187.5 kbit/s
Services
— PG/OP communicationYes
— Global data communicationYes
— S7 communicationYes
— S7 communication, as clientNo
— S7 communication, as serverYes
Communication functions
PG/OP communicationYes
Global data communication
Number of GD packets, transmitter, max.4
Number of GD packets, receiver, max.4
Size of GD packets, max.22 byte
S7 basic communication
supportedYes
User data per job, max.76 byte
S7 communication
supportedYes
as serverYes
as clientNo
User data per job, max.64 kbyte
Number of connections
overall8
usable for PG communication7
— reserved for PG communication1
— adjustable for PG communication, max.7
usable for OP communication7
— reserved for OP communication1
— adjustable for OP communication, max.7
usable for S7 basic communication4
— reserved for S7 basic communication4
— adjustable for S7 basic communication, max.4
S7 message functions
Number of login stations for message functions, max.5
Integrated Functions
Number of counters3
Counting frequency (counter) max.30 kHz
Frequency measurementYes
PID controllerYes
Number of pulse outputs3
Limit frequency (pulse)2.5 kHz
Potential separation
Potential separation digital inputs
Potential separation digital inputsYes
between the channels, in groups of16; 16 and 8
between the channels and backplane busYes
Potential separation digital outputs
between the channels, in groups of8
between the channels and backplane busYes
Potential separation analog inputs
Potential separation analog inputsYes; common for analog I/O
between the channels and backplane busYes
Potential separation analog outputs
Potential separation analog outputsYes
Configuration
Configuration software
STEP 7Yes; V5.1 SP2
Programming
Nesting levels8
Programming language
— LADYes
— FBDYes
— STLYes
— SCLYes
— GRAPHYes
— HiGraph®Yes
Know-how protection
User program protection/password protectionYes
Dimensions
Width120 mm
Height125 mm
Depth130 mm
Weights
Weight, approx.660 g
last modified:03/13/2019