6ES7234-4HE30-0XB0
Analog I/O SM 1234, 4AI/2AO

From SIEMENS

***Spare part*** SIMATIC S7-1200, analog I/O SM 1234, 4 AI/2 AO, +/-10 V, 14-bit resolution, or 0-20 mA, 13-bit resolution
General information
Product type designationSM 1234, AI 4x13 bit/AQ 2x14 bit
Supply voltage
Rated value (DC)
24 V DCYes
Input current
Current consumption, typ.60 mA
from backplane bus 5 V DC, typ.80 mA
Power loss
Power loss, typ.2 W
Analog inputs
Number of analog inputs4; Current or voltage differential inputs
permissible input voltage for voltage input (destruction limit), max.35 V
permissible input current for current input (destruction limit), max.40 mA
Cycle time (all channels) max.625 µs
Input ranges
VoltageYes; ±10V, ±5V, ±2.5V
CurrentYes; 0 to 20 mA
ThermocoupleNo
Resistance thermometerNo
ResistanceNo
Input ranges (rated values), voltages
-10 V to +10 VYes
Input resistance (-10 V to +10 V)≥9 MOhm
-2.5 V to +2.5 VYes
Input resistance (-2.5 V to +2.5 V)≥9 MOhm
-5 V to +5 VYes
Input resistance (-5 V to +5 V)≥9 MOhm
Input ranges (rated values), currents
0 to 20 mAYes
Input resistance (0 to 20 mA)280 Ω
Analog outputs
Number of analog outputs2; Current or voltage
Output ranges, voltage
-10 V to +10 VYes
Output ranges, current
0 to 20 mAYes
Load impedance (in rated range of output)
with voltage outputs, min.1 000 Ω
with current outputs, max.600 Ω
Analog value generation for the inputs
Measurement principleDifferential
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.12 bit; + sign
Integration time, parameterizableYes
Interference voltage suppression for interference frequency f1 in Hz40 dB, DC to 60 V for interference frequency 50 / 60 Hz
Smoothing of measured values
parameterizableYes
Step: NoneYes
Step: lowYes
Step: MediumYes
Step: HighYes
Analog value generation for the outputs
Integration and conversion time/resolution per channel
Resolution (incl. overrange)Voltage: 14 bit; Current : 13 bit
Errors/accuracies
Temperature error (relative to input range), (+/-)25 °C ±0.1%, to 55 °C ±0.2% total measurement range
Temperature error (relative to output range), (+/-)25 °C ±0.3%, to 55 °C ±0.6% total measurement range
Basic error limit (operational limit at 25 °C)
Voltage, relative to input range, (+/-)0.1 %
Current, relative to input range, (+/-)0.1 %
Voltage, relative to output range, (+/-)0.3 %
Current, relative to output range, (+/-)0.3 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
Common mode voltage, max.12 V
Interrupts/diagnostics/status information
AlarmsYes
Diagnostics functionYes
Alarms
Diagnostic alarmYes
Diagnostic messages
Monitoring the supply voltageYes
Wire-breakYes
Short-circuitYes
Diagnostics indication LED
for status of the inputsYes
for status of the outputsYes
for maintenanceYes
Potential separation
Potential separation analog outputs
between the channels and the power supply of the electronicsNo
Degree and class of protection
Degree of protection acc. to EN 60529
IP20Yes
Standards, approvals, certificates
CE markYes
FM approvalYes
RCM (formerly C-TICK)Yes
Ambient conditions
Free fall
Fall height, max.0.3 m; five times, in product package
Ambient temperature during operation
min.0 °C
max.55 °C
horizontal installation, min.0 °C
horizontal installation, max.55 °C
vertical installation, min.0 °C
vertical installation, max.45 °C
Ambient temperature during storage/transportation
min.-40 °C
max.70 °C
Air pressure acc. to IEC 60068-2-13
Operation, min.795 hPa
Operation, max.1 080 hPa
Storage/transport, min.660 hPa
Storage/transport, max.1 080 hPa
Relative humidity
Operation at 25 ℃ without condensation, max.95 %
Pollutant concentrations
SO2 at RH < 60% without condensationS02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free
Connection method
required front connectorYes
Mechanics/material
Enclosure material (front)
PlasticYes
Dimensions
Width45 mm
Height100 mm
Depth75 mm
Weights
Weight, approx.220 g
last modified:03/13/2019