6ES7232-4HB30-0XB0
Analog Output SM 1232, 2AO

From SIEMENS

***Spare part*** SIMATIC S7-1200, Analog output, SM 1232, 2 AO, +/-10 V, 14-bit resolution, or 0-20 mA, 13-bit resolution
General information
Product type designationSM 1232, AQ 2x14 bit
Supply voltage
Rated value (DC)
24 V DCYes
Input current
Current consumption, typ.45 mA
from backplane bus 5 V DC, typ.80 mA
Power loss
Power loss, typ.1.5 W
Analog outputs
Number of analog outputs2; Current or voltage
Output ranges, voltage
-10 V to +10 VYes
Output ranges, current
0 to 20 mAYes
Load impedance (in rated range of output)
with voltage outputs, min.1 000 Ω
with current outputs, max.600 Ω
Analog value generation for the outputs
Integration and conversion time/resolution per channel
Resolution (incl. overrange)Voltage: 14 bit; Current : 13 bit
Errors/accuracies
Temperature error (relative to output range), (+/-)25 °C ±0.3%, to 55 °C ±0.6% total measurement range
Basic error limit (operational limit at 25 °C)
Voltage, relative to output range, (+/-)0.3 %
Current, relative to output range, (+/-)0.3 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
Common mode voltage, max.12 V
Interrupts/diagnostics/status information
AlarmsYes
Diagnostics functionYes
Alarms
Diagnostic alarmYes
Diagnostic messages
Monitoring the supply voltageYes
Wire-breakYes
Short-circuitYes
Diagnostics indication LED
for status of the outputsYes
for maintenanceYes
Degree and class of protection
Degree of protection acc. to EN 60529
IP20Yes
Standards, approvals, certificates
CE markYes
FM approvalYes
RCM (formerly C-TICK)Yes
Ambient conditions
Free fall
Fall height, max.0.3 m; five times, in product package
Ambient temperature during operation
min.0 °C
max.55 °C
horizontal installation, min.0 °C
horizontal installation, max.55 °C
vertical installation, min.0 °C
vertical installation, max.45 °C
Ambient temperature during storage/transportation
min.-40 °C
max.70 °C
Air pressure acc. to IEC 60068-2-13
Operation, min.795 hPa
Operation, max.1 080 hPa
Storage/transport, min.660 hPa
Storage/transport, max.1 080 hPa
Relative humidity
Operation at 25 ℃ without condensation, max.95 %
Pollutant concentrations
SO2 at RH < 60% without condensationS02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free
Connection method
required front connectorYes
Mechanics/material
Enclosure material (front)
PlasticYes
Dimensions
Width45 mm
Height100 mm
Depth75 mm
Weights
Weight, approx.180 g
last modified:03/13/2019