6ES7211-1BD30-0XB0
CPU 1211C, AC/DC/Relay, 6DI/4DO/2AI

From SIEMENS

***Spare part*** SIMATIC S7-1200, CPU 1211C, compact CPU, AC/DC/relay, onboard I/O: 6 DI 24 V DC; 4 DO relay 2A; 2 AI 0-10 V DC, Power supply: AC 85-264 V AC at 47-63 Hz, Program/data memory 25 KB
General information
Product type designationCPU 1211C AC/DC/relay
Engineering with
Programming packageSTEP 7 V10.5 or higher
Supply voltage
Rated value (AC)
120 V ACYes
230 V ACYes
permissible range, lower limit (AC)85 V
permissible range, upper limit (AC)264 V
Line frequency
permissible range, lower limit47 Hz
permissible range, upper limit63 Hz
Input current
Current consumption (rated value)60 mA at 120 V AC; 30 mA at 240 V AC
Current consumption, max.180 mA at 120 V AC; 90 mA at 240 V AC
Inrush current, max.20 A; at 264 V
Output current
for backplane bus (5 V DC), max.750 mA; Max. 5 V DC for SM and CM
Encoder supply
24 V encoder supply
24 VPermissible range: 20.4V to 28.8V
Power loss
Power loss, typ.10 W
Memory
Work memory
integrated25 kbyte
expandableNo
Load memory
integrated1 Mbyte
Plug-in (SIMATIC Memory Card), max.24 Mbyte; with SIMATIC memory card
Backup
presentYes; Entire project maintenance-free in the integral EEPROM
without batteryYes
CPU processing times
for bit operations, typ.0.1 µs; / Operation
for word operations, typ.12 µs; / Operation
for floating point arithmetic, typ.18 µs; / Operation
CPU-blocks
Number of blocks (total)DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used
OB
Number, max.Limited only by RAM for code
Data areas and their retentivity
Retentive data area (incl. timers, counters, flags), max.2 048 byte
Flag
Number, max.4 kbyte; Size of bit memory address area
Address area
I/O address area
Inputs1 024 byte
Outputs1 024 byte
Process image
Inputs, adjustable1 kbyte
Outputs, adjustable1 kbyte
Hardware configuration
Number of modules per system, max.3 communication modules, 1 signal board
Time of day
Clock
Hardware clock (real-time)Yes
Backup time240 h; Typical
Deviation per day, max.±60 s/month at 25 °C
Digital inputs
Number of digital inputs6; Integrated
of which inputs usable for technological functions3; HSC (High Speed Counting)
Source/sink inputYes
Input voltage
Rated value (DC)24 V
for signal "0"5 V DC at 1 mA
for signal "1"15 V DC at 2.5 mA
Input current
for signal "1", typ.1 mA
Input delay (for rated value of input voltage)
for standard inputs
— parameterizable0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four
— at "0" to "1", min.0.2 ms
— at "0" to "1", max.12.8 ms
for interrupt inputs
— parameterizableYes
for technological functions
— parameterizableSingle phase : 3 at 100 kHz, differential: 3 at 80 kHz
Cable length
shielded, max.500 m; 50 m for technological functions
unshielded, max.300 m; For technological functions: No
Digital outputs
Number of digital outputs4; Relays
Short-circuit protectionNo; to be provided externally
Switching capacity of the outputs
with resistive load, max.2 A
on lamp load, max.30 W with DC, 200 W with AC
Output delay with resistive load
"0" to "1", max.10 ms; max.
"1" to "0", max.10 ms; max.
Parallel switching of two outputs
for upratingNo
Switching frequency
of the pulse outputs, with resistive load, max.1 Hz
Relay outputs
Number of relay outputs4
Number of operating cycles, max.mechanically 10 million, at rated load voltage 100 000
Cable length
shielded, max.500 m
unshielded, max.150 m
Analog inputs
Number of analog inputs2
For voltage/current measurement2
Input ranges
VoltageYes
Input ranges (rated values), voltages
0 to +10 VYes
Input resistance (0 to 10 V)≥100k ohms
Cable length
shielded, max.100 m; twisted and shielded
Analog outputs
Number of analog outputs0
Cable length
shielded, max.100 m; shielded, twisted pair
Analog value generation for the inputs
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.10 bit
Integration time, parameterizableYes
Conversion time (per channel)625 µs
Encoder
Connectable encoders
2-wire sensorYes
1. Interface
Interface typePROFINET
PhysicsEthernet
IsolatedYes
automatic detection of transmission rateYes
AutonegotiationYes
AutocrossingYes
Protocols
PROFINET IO ControllerYes
Protocols
Supports protocol for PROFINET IONo
PROFIBUSNo
AS-InterfaceNo
Protocols (Ethernet)
TCP/IPYes
Open IE communication
TCP/IPYes
ISO-on-TCP (RFC1006)Yes
Web server
supportedYes
User-defined websitesYes
Further protocols
MODBUSNo
Communication functions
S7 communication
supportedYes
as serverYes
Number of connections
overall15; dynamically
Test commissioning functions
Status/control
Status/control variableYes
VariablesInputs/outputs, memory bits, DBs, distributed I/Os, timers, counters
Forcing
ForcingYes
Integrated Functions
Number of counters3
Counting frequency (counter) max.100 kHz
Frequency measurementYes
controlled positioningYes
PID controllerYes
Number of alarm inputs4
Potential separation
Potential separation digital inputs
Potential separation digital inputsNo
between the channels, in groups of1
Potential separation digital outputs
Potential separation digital outputsYes; Relays
between the channelsNo
between the channels, in groups of1
Permissible potential difference
between different circuits500 V DC between 24 V DC and 5 V DC
EMC
Interference immunity against discharge of static electricity
Interference immunity against discharge of static electricity acc. to IEC 61000-4-2Yes
— Test voltage at air discharge8 kV
— Test voltage at contact discharge6 kV
Interference immunity to cable-borne interference
Interference immunity on supply lines acc. to IEC 61000-4-4Yes
Interference immunity on signal cables acc. to IEC 61000-4-4Yes
Interference immunity against voltage surge
on the supply lines acc. to IEC 61000-4-5Yes
Interference immunity against conducted variable disturbance induced by high-frequency fields
Interference immunity against high-frequency radiation acc. to IEC 61000-4-6Yes
Emission of radio interference acc. to EN 55 011
Limit class A, for use in industrial areasYes; Group 1
Limit class B, for use in residential areasYes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011
Degree and class of protection
Degree of protection acc. to EN 60529
IP20Yes
Standards, approvals, certificates
CE markYes
cULusYes
FM approvalYes
RCM (formerly C-TICK)Yes
Ambient conditions
Free fall
Fall height, max.0.3 m; five times, in product package
Ambient temperature during operation
min.0 °C
max.55 °C
horizontal installation, min.0 °C
horizontal installation, max.55 °C
vertical installation, min.0 °C
vertical installation, max.45 °C
permissible temperature change5°C to 55°C, 3°C / minute
Ambient temperature during storage/transportation
min.-40 °C
max.70 °C
Air pressure acc. to IEC 60068-2-13
Operation, min.795 hPa
Operation, max.1 080 hPa
Storage/transport, min.660 hPa
Storage/transport, max.1 080 hPa
Altitude during operation relating to sea level
Installation altitude, min.-1 000 m
Installation altitude, max.2 000 m
Relative humidity
Operation, max.95 %; no condensation
Vibrations
Vibration resistance during operation acc. to IEC 60068-2-62 g (m/s²) wall mounting, 1 g (m/s²) DIN rail
Operation, tested according to IEC 60068-2-6Yes
Shock testing
tested according to IEC 60068-2-27Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms
Pollutant concentrations
SO2 at RH < 60% without condensationS02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free
Configuration
Programming
Programming language
— LADYes
— FBDYes
— SCLYes
Cycle time monitoring
adjustableYes
Dimensions
Width90 mm
Height100 mm
Depth75 mm
Weights
Weight, approx.420 g
last modified:03/13/2019