| SIPLUS HCS724I Network voltage compensation module NE724 for central connection ZA724I |
General information |
Product type designation | Line voltage compensating module NE724 |
Installation type/mounting |
Mounting position | vertical |
Type of ventilation | Self ventilation or forced ventilation |
Supply voltage |
Design of the power supply | Power supply via central connection |
Connection method |
Design of electrical connection for supply voltage | 4 connecting cables with ring cable lug |
Interfaces |
Interfaces/bus type | system interface |
Integrated Functions |
Measuring functions |
Voltage measurement | Yes |
Current measurement | No |
Measuring inputs for voltage |
— Operational voltage at 50 Hz AC, min. | 187 V |
— Operational voltage at 50 Hz AC, max. | 264 V |
— Operational voltage at 60 Hz AC, min. | 187 V |
— Operational voltage at 60 Hz AC, max. | 264 V |
— Relative measuring accuracy voltage | 3 % |
— Operating frequency, min. | 50 Hz |
— Operating frequency, max. | 60 Hz |
— Design of electrical connection at the measuring inputs for voltage | Ring cable lug M6 |
Isolation |
Overvoltage category | III |
Degree of pollution | 2 |
EMC |
EMC interference emission | Limit value class A to EN 55011 group 1 |
Electrostatic discharge acc. to IEC 61000-4-2 | 4 kV contact discharge / 8 kV air discharge |
Field-related interference acc. to IEC 61000-4-3 | 10 V/m (80 ... 1 000 MHz), 3 V/m (1.4 ... 2.0 GHz), 1 V/m (2.0 ... 2.7 GHz) |
Conducted interference due to burst acc. to IEC 61000-4-4 | 2 kV voltage supply cables / 2 kV signal cables |
Conducted interference due to surge acc. to IEC 61000-4-5 | on power supply and signal cables: 1 kV symmetrical, 2 kV unsymmetrical |
Conducted interference due to high-frequency radiation acc. to IEC 61000-4-6 | 10 V (0.15 ... 80 MHz) |
Degree and class of protection |
IP degree of protection | IP20 |
Standards, approvals, certificates |
Certificate of suitability | CE, KCC |
CE mark | Yes |
KC approval | Yes |
EAC (formerly Gost-R) | Yes |
China RoHS compliance | Yes |
Reference designation according to DIN EN 81346-2 | T |
Ambient conditions |
Ambient temperature during operation |
min. | 0 °C |
max. | 55 °C |
Ambient temperature during storage/transportation |
Storage, min. | -40 °C |
Storage, max. | 70 °C |
Transportation, min. | -40 °C |
Transportation, max. | 70 °C |
Air pressure acc. to IEC 60068-2-13 |
Operation, min. | 860 hPa |
Operation, max. | 1 080 hPa |
Storage, min. | 660 hPa |
Storage, max. | 1 080 hPa |
Altitude during operation relating to sea level |
Installation altitude above sea level, max. | 2 000 m |
Relative humidity |
Operation at 25 ℃, max. | 95 % |
Vibrations |
Vibration resistance during operation acc. to IEC 60068-2-6 | 10 ... 58 Hz / 0.15 mm, 58 ... 150 Hz / 1 g |
Vibration resistance during storage acc. to IEC 60068-2-6 | 5 ... 9 Hz / 3.5 mm, 9 ... 500 Hz / 1 g |
Shock testing |
Shock resistance during operation acc. to IEC 60068-2-27 | 15 g / 11 ms / 3 shocks/axis |
Shock resistance during storage acc. to IEC 60068-2-29 | 25 g / 6 ms / 1 000 shocks/axis |
Dimensions |
Width | 86 mm |
Height | 22 mm |
Depth | 160 mm |