6ES7157-0AG82-0XA0
ACTIVE FIELD DISTRIBUTOR AFD8

From SIEMENS

Active field distributor AFD8 for PROFIBUS PA for foundation Fieldbus H1, 8 short circuit-proof spur lines with bounce protection logic Automatic bus termination for line and ring topology for extended temperature range Degree of protection IP66
General information
Product type designationActive Field Distributor AFD8
HW functional status01
Product function
Repeater functionNo
Supply voltage
permissible range, lower limit (DC)16 V
permissible range, upper limit (DC)32 V
Reverse polarity protectionYes; only in conjunction with FDC 157
Overvoltage protectionNo
Input current
Current consumption (in no-load operation), typ.34 mA; 64 mA at the end of the cable
Current consumption, max.514 mA
Power loss
Power loss, typ.544 mW
Power loss, max.4.1 W
Interfaces
PROFIBUS PA
Transmission rate, max.31.25 kbit/s
Number of connectable PA field devices8
Current output to PA field devices, max.480 mA
permissible current per spur line60 mA
Protocols
PROFIBUS DPNo
PROFIBUS PAYes
AS-InterfaceNo
FOUNDATION Fieldbus H1Yes
Interrupts/diagnostics/status information
Status indicatorYes
AlarmsNo
Diagnostics functionYes
Diagnostics indication LED
Main line statusYes
Main line failureYes
Spur line status/faultYes
automatic bus terminationYes
Potential separation
between main line and spur linesNo
Degree and class of protection
Degree of protection acc. to EN 60529
IP66Yes
Standards, approvals, certificates
Use in hazardous areas
ATEX Zone 1No
ATEX Zone 21No
ATEX Zone 2Yes
ATEX Zone 22Yes
FM Class I Zone 1No
FM Class I Zone 2, Division 2Yes
Ambient conditions
Ambient temperature during operation
min.-40 °C
max.70 °C
Ambient temperature during storage/transportation
min.-40 °C
max.85 °C
Relative humidity
Operation, max.95 %
Connection method
Main line
Number of main lines2
Design of terminalsScrew terminal block
Type of connection (enclosure cable gland)M16
Type of cableType A
Cable diameter, min.4 mm
Cable diameter, max.9 mm
Conductor cross-section, min.0.2 mm²
Conductor cross-section, max.2.5 mm²
automatic bus terminationYes
permissible main line current1 A
Spur line
Number of spur lines8
Design of terminalsScrew terminal block
Type of connection (enclosure cable gland)M16
Type of cableType A
Cable diameter, min.4 mm
Cable diameter, max.9 mm
Conductor cross-section, min.0.2 mm²
Conductor cross-section, max.2.5 mm²
total current output to field devices, max.480 mA
Number of connectable field devices8
Current limitation per field device, max.60 mA
Short-circuit current (test current); max.6 mA
intrinsically safe according to FISCO modelNo
Debounce logicYes
Dimensions
Width360 mm
Height120 mm; without screw glands
Depth83 mm
Weights
Weight, approx.3 000 g
last modified:03/13/2019