SIMATIC DP, Interface module IM151-1 High Feature f. ET200S; Transmission rate to 12 Mbit/s; data volume 244 bytes each for I/O max. 63 modules can be connected; isochronous mode Bus connection via 9-pin D-sub incl. termination module | ||
General information | ||
Product type designation | IM 151-1 HF | |
Supply voltage | ||
Mains buffering | ||
Mains/voltage failure stored energy time | 20 ms | |
Input current | ||
from supply voltage 1L+, max. | 200 mA | |
Power loss | ||
Power loss, typ. | 3.3 W | |
Address area | ||
Addressing volume | ||
Inputs | 244 byte | |
Outputs | 244 byte | |
Interfaces | ||
Interface physics, RS 485 | Yes | |
PROFIBUS DP | ||
Transmission rate, max. | 12 Mbit/s | |
SYNC capability | Yes | |
FREEZE capability | Yes | |
Direct data exchange (slave-to-slave communication) | Yes | |
Protocols | ||
Supports protocol for PROFINET IO | No | |
PROFIBUS DP | Yes | |
Protocols (Ethernet) | ||
TCP/IP | No | |
Isochronous mode | ||
Isochronous operation (application synchronized up to terminal) | Yes | |
Interrupts/diagnostics/status information | ||
Alarms | Yes | |
Diagnostics function | Yes | |
Diagnostics indication LED | ||
Bus fault BF (red) | Yes | |
Group error SF (red) | Yes | |
Monitoring 24 V voltage supply ON (green) | Yes | |
Potential separation | ||
between backplane bus and electronics | No | |
between electronic block and PROFIBUS DP | Yes | |
between supply voltage and electronics | No | |
Permissible potential difference | ||
between different circuits | 75 V DC/60 V AC | |
Isolation | ||
Isolation tested with | 500 V DC | |
Standards, approvals, certificates | ||
CE mark | Yes | |
UL approval | Yes | |
Ambient conditions | ||
Ambient temperature during operation | ||
min. | 0 °C | |
max. | 60 °C | |
Dimensions | ||
Width | 45 mm | |
Height | 119.5 mm | |
Depth | 75 mm | |
Weights | ||
Weight, approx. | 150 g | |
last modified: | 03/23/2019 |