6ES7148-1FA10-0XB0
ET200X, EM148-FC, Frequency Conv. 1.5 KW

From SIEMENS

***Spare part*** SIMATIC DP, distributed I/O ET 200X: EM148-FC, frequency Converter, 1.5 kW, Integrated Line filter, Connection method according to DESINA, IP65
General information
Protection function
Undervoltage protectionYes
Overvoltage protectionYes
Ground-fault protectionYes
Short-circuit protectionYes
Stall protectionYes
Temperature monitor for motorYes
Temperature monitor for converterYes
Input voltage
Input voltage acc. to VDE
permissible range, lower limit (AC)340 V
permissible range, upper limit (AC)500 V
Input voltage acc. to UL
permissible range, lower limit (AC)340 V
permissible range, upper limit (AC)480 V
Line frequency
Input frequency, min.47 Hz
Input frequency, max.63 Hz
Mains filter
presentYes; Type A (to EN 55011)
Operations for mains buffering time (20 ms)
Maximum current for Ue < 380 V1.85 A; at 3.8 A approx. 8 ms
Maximum current for Ue >= 380 V2.1 A; at 3.8 A approx. 8 ms
Input current
from load voltage L+ (without load), max.125 mA
from backplane bus 5 V DC, max.50 mA
Continuous rated current, max.16 A
Output current
Continuous output current at 40 °C
at 2 kHz and 4 kHz, max.3.8 A; Continuous currents > 1.9 A are only permissible if at least one of the following conditions is met: - Ambient temperature < 50 °C - Input continuous current when looping through the load supply voltage < 8 A
at 8 kHz, max.3 A; Continuous currents > 1.9 A are only permissible if at least one of the following conditions is met: - Ambient temperature < 50 °C - Input continuous current when looping through the load supply voltage < 8 A
at 16 kHz, max.1.45 A
Continuous output current at 55 °C
at 2 kHz and 4 kHz, max.2.1 A; Continuous currents > 1.9 A are only permissible if at least one of the following conditions is met: - Ambient temperature < 50 °C - Input continuous current when looping through the load supply voltage < 8 A
at 8 kHz, max.1.7 A
at 16 kHz, max.1.05 A
Power
Efficiency97 %
Power loss
in intermittent operation, max.70 W
in continuous operation, max.42 W
Interrupts/diagnostics/status information
Diagnostics functionYes
Alarms
Diagnostic alarmYes
Diagnostics indication LED
Group error SF (red)Yes
Status indicator STAT (yellow)Yes
Monitoring the power supply, power module PWR (green)Yes
Drive technology
Motor output, cable length max.10 m
Overload capability150 %; for 60 s, relative to rated current
Output frequency, min.0 Hz
Output frequency, max.300 Hz
Output frequency, resolution0.01 Hz
Control/mode
V/f characteristicYes
four quadrantsYes
Motor
Power factor (cos phi), min.0.7
Number of poles2, 4 or 6
Motor brakeAC (rated voltage according to infeed supply voltage) / max. 1 A
short-circuit proofNo; internal fuse 4 A provided
ThermistorResponse range about 4 to 5 kohms; channel-related error message: overload
Rated motor power at 3 x 400 V AC
acc. to VDE, max.1.5 kW
acc. to UL, max.2 hp
Potential separation
between the load voltagesYes
between load voltage and all other switching componentsYes
Dimensions
Width120 mm
Height265 mm
Depth181 mm
Weights
Weight, approx.3 kg
last modified:03/25/2019