6ES7142-6BF00-0AB0
ET200eco PN, 8DO, DC24V/1,3A, 4xM12

From SIEMENS

SIMATIC DP, ET 200ECO PN, 8 DO 24 V DC/1.3 A; 4xM12, Duplicate assignment, Degree of protection IP67
General information
Vendor identification (VendorID)002AH
Device identifier (DeviceID)0306H
Supply voltage
Rated value (DC)24 V
Reverse polarity protectionYes
Load voltage 2L+
Rated value (DC)24 V
Reverse polarity protectionYes
Input current
Current consumption, typ.100 mA
from supply voltage 1L+, max.4 A
from load voltage 2L+, max.4 A
Power loss
Power loss, typ.5.5 W
Digital outputs
Number of digital outputs8
in groups of4
Short-circuit protectionYes
Response threshold, typ.1.8 A
Limitation of inductive shutdown voltage toTyp. (L1+, L2+) -47 V
Controlling a digital inputYes
Switching capacity of the outputs
on lamp load, max.5 W
Output current
for signal "1" rated value1.3 A; Maximum
for signal "0" residual current, max.1.5 mA
Parallel switching of two outputs
for upratingNo
for redundant control of a loadYes
Switching frequency
with resistive load, max.100 Hz
with inductive load, max.0.5 Hz
on lamp load, max.1 Hz
Total current of the outputs (per group)
all mounting positions
— up to 55 °C, max.3.9 A
— up to 60 °C, max.2.6 A
Cable length
unshielded, max.30 m
Interfaces
Transmission procedure100BASE-TX
Number of PROFINET interfaces1
1. Interface
Interface types
integrated switchYes
M12 portYes
Interface types
M12 port
Transmission procedure100BASE-TX
AutonegotiationYes
AutocrossingYes
Transmission rate, max.100 Mbit/s
Protocols
Supports protocol for PROFINET IOYes
PROFINET CBANo
PROFIsafeNo
PROFINET IO Device
Services
— IRT with the option "high flexibility"Yes
— Prioritized startupYes
Open IE communication
TCP/IPNo
SNMPYes
DCPYes
LLDPYes
pingYes
ARPYes
Interrupts/diagnostics/status information
Diagnostics functionYes
Alarms
Diagnostic alarmYes
Diagnostic messages
Diagnostic information readableYes
Monitoring the supply voltageYes; Green "ON" LED
Wire-break in actuator cableYes
Short-circuitYes
Group errorYes; Red/yellow "SF/MT" LED
Potential separation
between the load voltagesYes
between load voltage and all other switching componentsNo
between Ethernet and electronicsYes
Potential separation channels
between the channelsNo
Isolation
tested with
24 V DC circuits707 V DC (type test)
Test voltage for interface, rms value [Vrms]1 500 V; According to IEEE 802.3
Degree and class of protection
IP degree of protectionIP65/67
Standards, approvals, certificates
Suitable for safety-related tripping of standard modulesYes
Highest safety class achievable for safety-related tripping of standard modules
Performance level according to ISO 13849-1PL d
Category according to ISO 13849-1Cat. 3
SILCL according to IEC 62061SILCL 2
Connection method
Design of electrical connection4/5-pin M12 circular connectors
Dimensions
Width30 mm
Height200 mm
Depth49 mm
Weights
Weight, approx.550 g
last modified:03/13/2019