| SIMATIC DP, ET 200ECO PN, 8 DO 24 V DC/1.3 A; 4xM12, Duplicate assignment, Degree of protection IP67 |
General information |
Vendor identification (VendorID) | 002AH |
Device identifier (DeviceID) | 0306H |
Supply voltage |
Rated value (DC) | 24 V |
Reverse polarity protection | Yes |
Load voltage 2L+ |
Rated value (DC) | 24 V |
Reverse polarity protection | Yes |
Input current |
Current consumption, typ. | 100 mA |
from supply voltage 1L+, max. | 4 A |
from load voltage 2L+, max. | 4 A |
Power loss |
Power loss, typ. | 5.5 W |
Digital outputs |
Number of digital outputs | 8 |
in groups of | 4 |
Short-circuit protection | Yes |
Response threshold, typ. | 1.8 A |
Limitation of inductive shutdown voltage to | Typ. (L1+, L2+) -47 V |
Controlling a digital input | Yes |
Switching capacity of the outputs |
on lamp load, max. | 5 W |
Output current |
for signal "1" rated value | 1.3 A; Maximum |
for signal "0" residual current, max. | 1.5 mA |
Parallel switching of two outputs |
for uprating | No |
for redundant control of a load | Yes |
Switching frequency |
with resistive load, max. | 100 Hz |
with inductive load, max. | 0.5 Hz |
on lamp load, max. | 1 Hz |
Total current of the outputs (per group) |
all mounting positions |
— up to 55 °C, max. | 3.9 A |
— up to 60 °C, max. | 2.6 A |
Cable length |
unshielded, max. | 30 m |
Interfaces |
Transmission procedure | 100BASE-TX |
Number of PROFINET interfaces | 1 |
1. Interface |
Interface types |
integrated switch | Yes |
M12 port | Yes |
Interface types |
M12 port |
Transmission procedure | 100BASE-TX |
Autonegotiation | Yes |
Autocrossing | Yes |
Transmission rate, max. | 100 Mbit/s |
Protocols |
Supports protocol for PROFINET IO | Yes |
PROFINET CBA | No |
PROFIsafe | No |
PROFINET IO Device |
Services |
— IRT with the option "high flexibility" | Yes |
— Prioritized startup | Yes |
Open IE communication |
TCP/IP | No |
SNMP | Yes |
DCP | Yes |
LLDP | Yes |
ping | Yes |
ARP | Yes |
Interrupts/diagnostics/status information |
Diagnostics function | Yes |
Alarms |
Diagnostic alarm | Yes |
Diagnostic messages |
Diagnostic information readable | Yes |
Monitoring the supply voltage | Yes; Green "ON" LED |
Wire-break in actuator cable | Yes |
Short-circuit | Yes |
Group error | Yes; Red/yellow "SF/MT" LED |
Potential separation |
between the load voltages | Yes |
between load voltage and all other switching components | No |
between Ethernet and electronics | Yes |
Potential separation channels |
between the channels | No |
Isolation |
tested with |
24 V DC circuits | 707 V DC (type test) |
Test voltage for interface, rms value [Vrms] | 1 500 V; According to IEEE 802.3 |
Degree and class of protection |
IP degree of protection | IP65/67 |
Standards, approvals, certificates |
Suitable for safety-related tripping of standard modules | Yes |
Highest safety class achievable for safety-related tripping of standard modules |
Performance level according to ISO 13849-1 | PL d |
Category according to ISO 13849-1 | Cat. 3 |
SILCL according to IEC 62061 | SILCL 2 |
Connection method |
Design of electrical connection | 4/5-pin M12 circular connectors |
Dimensions |
Width | 30 mm |
Height | 200 mm |
Depth | 49 mm |
Weights |
Weight, approx. | 550 g |
last modified: | 03/13/2019 |