| SIMATIC DP, Electronic modules for ET 200 PRO 8 DO 24 V DC, 0.5 A Module diagnostics; incl. bus module, Connection module IO 6ES7194-4..00-0AA0 order separately |
Supply voltage |
Load voltage 2L+ |
Rated value (DC) | 24 V |
Short-circuit protection | Yes; per channel, electronic |
Reverse polarity protection | Yes; against destruction; load increasing |
Input current |
from load voltage 2L+ (without load), max. | 30 mA |
from backplane bus 3.3 V DC, max. | 30 mA |
Power loss |
Power loss, typ. | 2 W |
Address area |
Address space per module |
Address space per module, max. | 1 byte |
Digital outputs |
Number of digital outputs | 8 |
Short-circuit protection | Yes |
Response threshold, typ. | 0.7 A |
Limitation of inductive shutdown voltage to | 2L+ (-47 V) |
Controlling a digital input | Yes; Isolation between 1L+ and 2L+ is no longer provided, as 1M and 2M are jumpered |
Switching capacity of the outputs |
on lamp load, max. | 5 W |
Load resistance range |
lower limit | 48 Ω |
upper limit | 4 kΩ |
Output voltage |
for signal "1", min. | 2L+ (-0,8 V) |
Output current |
for signal "1" rated value | 0.5 A |
for signal "0" residual current, max. | 0.5 mA |
Parallel switching of two outputs |
for uprating | No |
for redundant control of a load | Yes |
Switching frequency |
with resistive load, max. | 100 Hz |
with inductive load, max. | 0.5 Hz |
on lamp load, max. | 1 Hz |
Total current of the outputs (per group) |
all mounting positions |
— up to 55 °C, max. | 4 A |
Cable length |
shielded, max. | 30 m |
unshielded, max. | 30 m |
Interrupts/diagnostics/status information |
Diagnostics function | Yes |
Alarms |
Diagnostic alarm | Yes |
Diagnostic messages |
Diagnostic information readable | Yes |
Short-circuit | Yes; Short-circuit of outputs to ground; module by module |
Diagnostics indication LED |
Group error SF (red) | Yes |
Status indicator digital output (green) | Yes |
Potential separation |
between backplane bus and all other circuit components | Yes |
Potential separation digital outputs |
between the channels | No |
between the channels and backplane bus | Yes |
Isolation |
Isolation tested with | 707 V DC (type test) |
Standards, approvals, certificates |
Suitable for safety-related tripping of standard modules | Yes |
Highest safety class achievable for safety-related tripping of standard modules |
Performance level according to ISO 13849-1 | PL d |
Category according to ISO 13849-1 | Cat. 3 |
SILCL according to IEC 62061 | SILCL 2 |
Dimensions |
Width | 45 mm |
Height | 130 mm |
Depth | 35 mm |
Weights |
Weight, approx. | 140 g |
last modified: | 03/13/2019 |