| SIMATIC DP, basic module BM 142 ET 200ECO: 16 DO 24 V DC/0.5A, 8xM12, Duplicate assignment, IP65/67, Connection block 6ES7194-3AA00-0.A0 order separately |
General information |
Vendor identification (VendorID) | 80FBh |
Supply voltage |
Rated value (DC) | 24 V |
Reverse polarity protection | Yes |
Load voltage 2L+ |
Rated value (DC) | 24 V |
Reverse polarity protection | Yes |
Input current |
from supply voltage 1L+, max. | 70 mA; Typical |
from load voltage 2L+ (without load), max. | 80 mA; Typical |
Power loss |
Power loss, typ. | 4 W |
Digital outputs |
Number of digital outputs | 16 |
Short-circuit protection | Yes |
Response threshold, typ. | 1.4 A; Per channel |
Limitation of inductive shutdown voltage to | 2L+ (-47 V) |
Controlling a digital input | Yes |
Switching capacity of the outputs |
on lamp load, max. | 5 W |
Load resistance range |
lower limit | 12 Ω |
upper limit | 4 kΩ |
Output voltage |
for signal "1", min. | 2L+ (-0,8 V) |
Output current |
for signal "1" rated value | 0.5 A |
for signal "1" permissible range for 0 to 55 °C, min. | 5 mA |
for signal "1" permissible range for 0 to 55 °C, max. | 1 A |
for signal "0" residual current, max. | 0.1 mA |
Parallel switching of two outputs |
for uprating | No |
for redundant control of a load | Yes |
Switching frequency |
with resistive load, max. | 100 Hz |
with inductive load, max. | 0.5 Hz; According to IEC 60947-5-1, DC-13 |
on lamp load, max. | 1 Hz |
Total current of the outputs (per group) |
all mounting positions |
— up to 55 °C, max. | 4 A; Please note the current carrying capacity of the cable! |
Cable length |
unshielded, max. | 30 m |
Interfaces |
PROFIBUS DP |
Transmission rate, max. | 12 Mbit/s; 9,6 / 19,2 / 45,45 / 93,75 / 187,5 / 500 kbit/s; 1,5 / 3 / 6 / 12 Mbit/s |
Protocols |
PROFIBUS DP | Yes |
Interrupts/diagnostics/status information |
Alarms | No |
Diagnostic messages |
Diagnostic information readable | Yes |
Diagnostics indication LED |
Group error SF (red) | Yes |
Status indicator digital output (green) | Yes |
Channel fault indicator F (red) | No |
Potential separation |
between PROFIBUS DP and all other circuit components | Yes |
Potential separation digital outputs |
between the channels | No |
Permissible potential difference |
between different circuits | 75 V DC/60 V AC |
Isolation |
Isolation tested with | 500 V DC |
Degree and class of protection |
IP degree of protection | IP65/67 |
Connection method |
Design of electrical connection | 4/5-pin M12 circular connectors |
Dimensions |
Width | 60 mm |
Height | 210 mm |
Depth | 28 mm |
Weights |
Weight, approx. | 210 g |
last modified: | 03/13/2019 |