| ***Spare part*** SIMATIC DP, Expansion module EM 142 for ET 200X, 8 DO DC 24V/1,2A, 5-pole M12, IP66/67 for all basic modules |
Input current |
from load voltage 2L+ (without load), max. | 12 mA |
from backplane bus 5 V DC, max. | 35 mA |
Power loss |
Power loss, typ. | 1.5 W |
Digital outputs |
Number of digital outputs | 8 |
Short-circuit protection | Yes; Electronic |
Response threshold, typ. | 1.8 A |
Limitation of inductive shutdown voltage to | Typ. (2L+) -47 V |
Controlling a digital input | Yes |
Switching capacity of the outputs |
on lamp load, max. | 10 W |
Load resistance range |
lower limit | 21 Ω |
upper limit | 4 kΩ |
Output voltage |
for signal "1", min. | 2L+ (-1,2 V) |
Output current |
for signal "1" rated value | 1.2 A |
for signal "1" permissible range, min. | 5 mA |
for signal "1" permissible range, max. | 1.3 A |
for signal "0" residual current, max. | 0.5 mA |
Parallel switching of two outputs |
for uprating | No |
for redundant control of a load | Yes; only outputs of the same group |
Switching frequency |
with resistive load, max. | 100 Hz |
with inductive load (acc. to IEC 60947-5-1, DC13), max. | 0.5 Hz |
on lamp load, max. | 1 Hz |
Total current of the outputs (per module) |
all mounting positions |
— up to 20 °C, max. | 7 A |
— up to 55 °C, max. | 5 A; Up to 50 °C |
Cable length |
unshielded, max. | 30 m |
Interrupts/diagnostics/status information |
Alarms | No |
Diagnostics indication LED |
Status indicator digital output (green) | Yes |
Potential separation |
between backplane bus and all other circuit components | Yes |
Potential separation digital outputs |
between the channels | No |
Permissible potential difference |
between different circuits | 75 V DC/60 V AC |
Isolation |
Isolation tested with | 500 V DC |
Dimensions |
Width | 87 mm; Width module 60 mm |
Height | 180 mm |
Depth | 55 mm |
Weights |
Weight, approx. | 350 g |
last modified: | 02/21/2020 |