| SIMATIC DP, Electronics module f. ET200SP, F-RQ 1x 24 V DC/24..230VAC/5A ST, 20 mm overall width, 1 relay output (2 NO) Summation output current 5 A, load voltage 24 V DC and 24.. 230 V AC, Can be used up to PL E (ISO 13849-1: 2008)/ SIL 3 (IEC 61508: 2010) if control takes place by (e.g. 6ES7136-6DB00-0CA0) F-DQ |
General information |
Product type designation | F-RQ 1x24 V DC/24 ... 230 V AC/5 A |
usable BaseUnits | BU type F0 |
Color code for module-specific color identification plate | CC42 |
Product function |
I&M data | Yes; I&M0 to I&M3 |
Engineering with |
STEP 7 TIA Portal configurable/integrated as of version | V13 |
STEP 7 configurable/integrated as of version | V5.5 SP4 and higher |
Supply voltage |
Rated value (DC) | 24 V; Coil voltage |
permissible range, lower limit (DC) | 20.4 V |
permissible range, upper limit (DC) | 28.8 V |
Power |
Power available from the backplane bus | 100 mW |
Power loss |
Power loss, typ. | 1 W |
Address area |
Address space per module |
Inputs | 1 byte |
Digital outputs |
Number of digital outputs | 1 |
Limitation of inductive shutdown voltage to | No |
Controlling a digital input | Yes |
Switching capacity of the outputs |
with resistive load, max. | 5 A |
on lamp load, max. | 25 W |
Switching frequency |
with resistive load, max. | 2 Hz |
with inductive load, max. | 0.1 Hz; See data in manual |
with inductive load (acc. to IEC 60947-5-1, DC13), max. | 0.1 Hz |
with inductive load (acc. to IEC 60947-5-1, AC15), max. | 2 Hz |
Total current of the outputs (per module) |
horizontal installation |
— up to 40 °C, max. | 5 A; Note derating data in the manual |
— up to 50 °C, max. | 4 A; Note derating data in the manual |
— up to 60 °C, max. | 3 A; Note derating data in the manual |
vertical installation |
— up to 50 °C, max. | 3 A; Note derating data in the manual |
Relay outputs |
Number of relay outputs | 1; 2 NO contacts |
Rated supply voltage of relay coil L+ (DC) | 24 V |
Current consumption of relays (coil current of all relays), max. | 70 mA |
external protection for relay outputs | yes; 6 A, see data in manual |
Relay approved acc. to UL 508 | Yes; Pilot Duty B300, R300 |
Switching capacity of contacts |
— with inductive load, max. | see additional description in the manual |
— with resistive load, max. | see additional description in the manual |
— Thermal continuous current, max. | 5 A |
— Switching current, min. | 1 mA |
— Switching current after exceeding 300 mA, min. | 10 mA |
— Switching current after exceeding 300 mA, max. | 5 A |
— Rated switching voltage (DC) | 24 V |
— Rated switching voltage (AC) | 230 V |
Cable length |
shielded, max. | 500 m; for load contacts |
unshielded, max. | 300 m; for load contacts |
Control cable (input), max. | 10 m |
Interrupts/diagnostics/status information |
Diagnostics function | yes, firmware update |
Diagnostics indication LED |
RUN LED | Yes; green/red DIAG LED |
Channel status display | Yes; Green LED |
Potential separation |
Potential separation channels |
between the channels | Yes; for SELV / PELV only |
between the channels and backplane bus | Yes |
between the channels and the power supply of the electronics | Yes |
Permissible potential difference |
between channels and backplane bus/supply voltage | 250 V AC (reinforced insulation) |
Isolation |
Isolation tested with | 2 545 V DC/2 s (routine test) |
Overvoltage category | III |
tested with |
between channels and backplane bus/supply voltage | DC 2 545 V 2 s (routine test), impulse voltage test DC 7 200 V / 5 positive and 5 negative pulses (type test) |
between backplane bus and supply voltage | 707 V DC (type test) |
Standards, approvals, certificates |
Suitable for safety functions | Yes |
Highest safety class achievable in safety mode |
Performance level according to ISO 13849-1 | PLe |
SIL acc. to IEC 61508 | SIL 3 |
Probability of failure (for service life of 20 years and repair time of 100 hours) |
— Low demand mode: PFDavg in accordance with SIL2 | < 1.00E-04, function test 1x per year |
— Low demand mode: PFDavg in accordance with SIL3 | < 1.00E-05, function test 1x per month |
— High demand/continuous mode: PFH in accordance with SIL2 | < 1.00E-08 1/h, function test 1x per year |
— High demand/continuous mode: PFH in accordance with SIL3 | < 6.00E-09 1/h, function test 1x per month |
Dimensions |
Width | 20 mm |
Height | 73 mm |
Depth | 58 mm |
Weights |
Weight, approx. | 56 g |