6ES7135-7TD00-0AB0
ET200ISP, EL-MOD., 4 AO, 4-20MA, HART

From SIEMENS

SIMATIC DP, electronics module for ET200iSP, 4 AQ HART, 4 ... 20 mA, for connecting HART field devices Supported HART protocol Version 6.0
Input current
Current consumption, typ.295 mA
from load voltage L+ (without load), max.330 mA
Power loss
Power loss, typ.2.7 W
Analog outputs
Number of analog outputs4
Cycle time (all channels) max.3.6 ms
Output ranges, current
0 to 20 mAYes
4 mA to 20 mAYes
Connection of actuators
for current output two-wire connectionYes
Load impedance (in rated range of output)
with current outputs, max.750 Ω
Cable length
shielded, max.500 m
Analog value generation for the outputs
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.14 bit
Settling time
for resistive load4 ms
for capacitive load40 ms
for inductive load40 ms
Errors/accuracies
Linearity error (relative to output range), (+/-)0.015 %
Temperature error (relative to output range), (+/-)0.005 %/K
Crosstalk between the outputs, min.-50 dB
Repeat accuracy in steady state at 25 °C (relative to output range), (+/-)0.01 %
Operational error limit in overall temperature range
Current, relative to output range, (+/-)0.15 %
Basic error limit (operational limit at 25 °C)
Current, relative to output range, (+/-)0.1 %
Interrupts/diagnostics/status information
Substitute values connectableYes
Alarms
Diagnostic alarmYes
Diagnostic messages
Diagnostic information readableYes
Wire-breakYes
Short-circuitYes
Diagnostics indication LED
Group error SF (red)Yes
Potential separation
Potential separation analog outputs
between the channelsNo
between the channels and backplane busYes
Standards, approvals, certificates
CE markYes
Use in hazardous areas
Type of protection acc. to EN 50020 (CENELEC)II2 G (1) GD Ex ib[ia] IIC T4 and I M2 Ex ib[ia] I
Type of protection acc. to KEMA04 ATEX 1250
Dimensions
Width30 mm
Height129 mm
Depth136.5 mm
Weights
Weight, approx.265 g
last modified:03/13/2019

External links