| SIMATIC DP, ELECTRONIC MODULE 2 AO HIGH FEATURE I FOR ET 200S, 15 MM WIDE, +/-20MA; 15 BIT + SIGN, 4 .. 20MA; 15 BIT, OPERATIONAL LIMITS +/-0.05% WITH LED SF (GROUP FAULT) |
Supply voltage |
Load voltage L+ |
Rated value (DC) | 24 V; From power module |
Reverse polarity protection | Yes |
Input current |
from load voltage L+ (without load), max. | 150 mA |
from backplane bus 3.3 V DC, max. | 10 mA |
Power loss |
Power loss, max. | 3 W |
Address area |
Address space per module |
Address space per module, max. | 4 byte |
Analog outputs |
Number of analog outputs | 2 |
Current output, no-load voltage, max. | 18 V |
Cycle time (all channels) max. | 1.5 ms |
Output ranges, current |
-20 mA to +20 mA | Yes |
4 mA to 20 mA | Yes |
Connection of actuators |
for current output two-wire connection | Yes |
for current output four-wire connection | No |
Load impedance (in rated range of output) |
with current outputs, max. | 500 Ω |
with current outputs, inductive load, max. | 1 mH |
Destruction limits against externally applied voltages and currents |
Voltages at the outputs towards MANA | 15 V; max. 15 V continuous; 75 V for max. 1 s (mark to space ratio 1:20) |
Current, max. | 50 mA |
Cable length |
shielded, max. | 200 m |
Analog value generation for the outputs |
Integration and conversion time/resolution per channel |
Resolution with overrange (bit including sign), max. | 16 bit; ±20 mA: 15 bit, 4 to 20 mA: 15 bit + sign |
Settling time |
for resistive load | 0.25 ms |
for capacitive load | 1 ms |
for inductive load | 0.5 ms |
Errors/accuracies |
Output ripple (relative to output range, bandwidth 0 to 50 kHz), (+/-) | 0.02 % |
Linearity error (relative to output range), (+/-) | 0.02 % |
Temperature error (relative to output range), (+/-) | 0.001 %/K |
Repeat accuracy in steady state at 25 °C (relative to output range), (+/-) | 0.01 % |
Operational error limit in overall temperature range |
Current, relative to output range, (+/-) | 0.05 % |
Basic error limit (operational limit at 25 °C) |
Current, relative to output range, (+/-) | 0.01 % |
Interrupts/diagnostics/status information |
Substitute values connectable | Yes; 0 to 65535 (range of values must be within the rated range) |
Diagnostic messages |
Wire-break | Yes |
Group error | Yes |
Diagnostics indication LED |
Group error SF (red) | Yes |
Parameter |
Remark | 7 byte |
Diagnostics wire break | Disable / enable |
Output type/range | deactivated / ±20 mA / 4 to 20 mA |
Group diagnostics | Disable / enable |
Response to CPU/master STOP | Output current and de-energized/substitute a value/keep last value |
Potential separation |
Potential separation analog outputs |
between the channels | No |
between the channels and backplane bus | Yes |
Between the channels and load voltage L+ | Yes |
Permissible potential difference |
between MANA and M internally (UISO) | 75 V DC/60 V AC |
Dimensions |
Width | 15 mm |
Height | 81 mm |
Depth | 52 mm |
Weights |
Weight, approx. | 40 g |
last modified: | 04/06/2019 |