6ES7135-4GB00-0AB0
ET200S, EL-MOD., 2AO I, +/-20MA, 4-20MA

From SIEMENS

SIMATIC DP, ELECTRONIC MODULE FOR ET 200S, 2 AO I 15 MM WIDE, +/-20 MA; 13 BIT + SIGN, 4 . .20 MA; 12 BIT CYCLE TIME < 1 MS WITH LED SF (GROUP FAULT)
Supply voltage
Load voltage L+
Rated value (DC)24 V; From power module
Reverse polarity protectionYes
Input current
from load voltage L+ (without load), max.150 mA
from backplane bus 3.3 V DC, max.10 mA
Power loss
Power loss, max.2 W
Address area
Address space per module
Address space per module, max.4 byte
Analog outputs
Number of analog outputs2
Current output, no-load voltage, max.18 V
Cycle time (all channels) max.1.5 ms
Output ranges, current
-20 mA to +20 mAYes
4 mA to 20 mAYes
Connection of actuators
for current output two-wire connectionYes
for current output four-wire connectionNo
Load impedance (in rated range of output)
with current outputs, max.500 Ω
with current outputs, inductive load, max.1 mH
Destruction limits against externally applied voltages and currents
Voltages at the outputs towards MANA15 V; max. 15 V continuous; 75 V for max. 1 s (mark to space ratio 1:20)
Current, max.50 mA; DC
Cable length
shielded, max.200 m
Analog value generation for the outputs
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.14 bit; 4 to 20 mA: 13 bit, ±20 mA: 14 bit
Settling time
for resistive load0.1 ms
for capacitive load0.5 ms
for inductive load0.5 ms
Errors/accuracies
Output ripple (relative to output range, bandwidth 0 to 50 kHz), (+/-)0.02 %
Linearity error (relative to output range), (+/-)0.02 %
Temperature error (relative to output range), (+/-)0.01 %/K
Crosstalk between the outputs, min.-40 dB
Repeat accuracy in steady state at 25 °C (relative to output range), (+/-)0.05 %
Operational error limit in overall temperature range
Current, relative to output range, (+/-)0.5 %
Basic error limit (operational limit at 25 °C)
Current, relative to output range, (+/-)0.3 %
Isochronous mode
Isochronous operation (application synchronized up to terminal)No
Interrupts/diagnostics/status information
Substitute values connectableYes; 0 to 65535 (range of values must be within the rated range)
Diagnostic messages
Wire-breakYes
Group errorYes
Diagnostics indication LED
Group error SF (red)Yes
Parameter
Remark7 byte
Diagnostics wire breakDisable / enable
Output type/rangedeactivated / ±20 mA / 4 to 20 mA
Group diagnosticsDisable / enable
Response to CPU/master STOPOutput current and de-energized/substitute a value/keep last value
Potential separation
Potential separation analog outputs
between the channelsNo
between the channels and backplane busYes
Between the channels and load voltage L+Yes
Permissible potential difference
between MANA and M internally (UISO)75 V DC/60 V AC
Isolation
Isolation tested with500 V DC
Dimensions
Width15 mm
Height81 mm
Depth52 mm
Weights
Weight, approx.40 g
last modified:03/13/2019