6ES7134-6HD01-0BA1
ET 200SP, AI 4xU/I 2-Wire ST, PU 1

From SIEMENS

SIMATIC ET 200SP, ANALOG INPUT MODULE, AI 4XU/I 2-WIRE STANDARD, PACKING UNIT: 1 PIECE, FITS TO BU-TYPE A0, A1, COLOR CODE CC03, MODULE DIAGNOSIS, 16BIT, +/-0,3%
General information
Product type designationAI 4x U/I 2-wire
HW functional statusFrom FS02
Firmware versionV2.0
FW update possibleYes
usable BaseUnitsBU type A0, A1
Color code for module-specific color identification plateCC03
Product function
I&M dataYes; I&M0 to I&M3
Measuring range scalableNo
Engineering with
STEP 7 TIA Portal configurable/integrated as of versionV14 / -
STEP 7 configurable/integrated as of versionV5.6 and higher
PCS 7 configurable/integrated as of versionV8.1 SP1
PROFIBUS as of GSD version/GSD revisionOne GSD file each, Revision 3 and 5 and higher
PROFINET as of GSD version/GSD revisionGSDML V2.3
Operating mode
OversamplingNo
MSINo
CiR – Configuration in RUN
Reparameterization possible in RUNYes
Calibration possible in RUNNo
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Input current
Current consumption, max.37 mA; without sensor supply
Encoder supply
24 V encoder supply
24 VYes
Short-circuit protectionYes
Output current, max.20 mA; max. 50 mA per channel for a duration < 10 s
Power loss
Power loss, typ.0.85 W; Without encoder supply voltage
Address area
Address space per module
Address space per module, max.8 byte; + 1 byte for QI information
Hardware configuration
Automatic encoding
Mechanical coding elementYes
Selection of BaseUnit for connection variants
2-wire connectionBU type A0, A1
Analog inputs
Number of analog inputs4; Differential inputs
permissible input voltage for voltage input (destruction limit), max.30 V
permissible input current for current input (destruction limit), max.50 mA
Cycle time (all channels), min.Sum of the basic conversion times and additional processing times (depending on the parameterization of the active channels)
Input ranges (rated values), voltages
0 to +10 VYes; 15 bit
Input resistance (0 to 10 V)120 kΩ
1 V to 5 VYes; 15 bit
Input resistance (1 V to 5 V)120 kΩ
-10 V to +10 VYes; 16 bit incl. sign
Input resistance (-10 V to +10 V)120 kΩ
-5 V to +5 VYes; 16 bit incl. sign
Input resistance (-5 V to +5 V)120 kΩ
Input ranges (rated values), currents
0 to 20 mAYes; 15 bit
Input resistance (0 to 20 mA)100 Ω; + approx. 0.7 V diode forward voltage
4 mA to 20 mAYes; 15 bit
Input resistance (4 mA to 20 mA)100 Ω; + approx. 0.7 V diode forward voltage
Cable length
shielded, max.1 000 m; 200 m for voltage measurement
Analog value generation for the inputs
Measurement principleintegrating (Sigma-Delta)
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.16 bit
Integration time, parameterizableYes
Interference voltage suppression for interference frequency f1 in Hz16.6 / 50 / 60 Hz
Conversion time (per channel)180 / 60 / 50 ms
Smoothing of measured values
Number of smoothing levels4; None; 4/8/16 times
parameterizableYes
Encoder
Connection of signal encoders
for voltage measurementYes
for current measurement as 2-wire transducerYes
— Burden of 2-wire transmitter, max.650 Ω
for current measurement as 4-wire transducerNo
Errors/accuracies
Linearity error (relative to input range), (+/-)0.01 %
Temperature error (relative to input range), (+/-)0.005 %/K
Crosstalk between the inputs, min.50 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)0.05 %
Operational error limit in overall temperature range
Voltage, relative to input range, (+/-)0.5 %
Current, relative to input range, (+/-)0.5 %
Basic error limit (operational limit at 25 °C)
Voltage, relative to input range, (+/-)0.3 %
Current, relative to input range, (+/-)0.3 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
Series mode interference (peak value of interference < rated value of input range), min.70 dB
Common mode voltage, max.10 V
Common mode interference, min.90 dB
Isochronous mode
Isochronous operation (application synchronized up to terminal)No
Interrupts/diagnostics/status information
Diagnostics functionYes
Alarms
Diagnostic alarmYes
Limit value alarmNo
Diagnostic messages
Monitoring the supply voltageYes
Wire-breakYes; at 4 to 20 mA
Short-circuitYes; with 1 to 5 V or 2-wire mode: Short-circuit of the encoder supply to ground or of an input to the encoder supply
Group errorYes
Overflow/underflowYes
Diagnostics indication LED
Monitoring of the supply voltage (PWR-LED)Yes; Green LED
Channel status displayYes; Green LED
for channel diagnosticsNo
for module diagnosticsYes; Green/red LED
Potential separation
Potential separation channels
between the channelsYes; channel group-specific between 2-wire current input group and voltage input group
between the channels and backplane busYes
between the channels and the power supply of the electronicsYes; only for voltage inputs
Permissible potential difference
between the inputs (UCM)10 V DC
Isolation
Isolation tested with707 V DC (type test)
Standards, approvals, certificates
Suitable for applications according to AMS 2750Yes; Declaration of Conformity, see online support entry 109757262
Suitable for applications according to CQI-9Yes
Ambient conditions
Ambient temperature during operation
horizontal installation, min.-30 °C
horizontal installation, max.60 °C
vertical installation, min.-30 °C
vertical installation, max.50 °C
Altitude during operation relating to sea level
Installation altitude above sea level, max.2 000 m; On request: Installation altitudes greater than 2 000 m
Dimensions
Width15 mm
Height73 mm
Depth58 mm
Weights
Weight, approx.31 g
last modified:03/13/2019