6ES7134-4LB02-0AB0
ET200S, El-Mod., 2AI U HF, +/-10V, 1..5V

From SIEMENS

SIMATIC DP, Electronics module 2 AI U High Feature f. ET200S, 15 mm width, Cycle time per module: 0.5 ms, +/-10V; 15 bit+sign, +/-5 V; 15 bit+sign, 1..5 V; 15 bit, Operational limit +/-0.1% with SF LED (group fault)
Supply voltage
Load voltage L+
Rated value (DC)24 V
Reverse polarity protectionYes
Input current
from load voltage L+ (without load), max.55 mA
from backplane bus 3.3 V DC, max.10 mA
Output voltage
Power supply to the transmitters
presentNo
Power loss
Power loss, typ.0.85 W
Address area
Address space per module
Address space per module, max.4 byte
Analog inputs
Number of analog inputs2
permissible input voltage for voltage input (destruction limit), max.35 V; 35 V continuous; 75 V for max. 1 ms
Cycle time (all channels) max.0.5 ms; 0.5 ms for 2 channels without noise suppression, 18 / 21 ms per channel with noise suppression
Input ranges (rated values), voltages
1 V to 5 VYes
Input resistance (1 V to 5 V)800 kΩ
-10 V to +10 VYes
Input resistance (-10 V to +10 V)800 kΩ
-5 V to +5 VYes
Input resistance (-5 V to +5 V)800 kΩ
Cable length
shielded, max.200 m
Analog value generation for the inputs
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.16 bit; 0 to 5 V: 15 bit, ±10 V: 16 bit, ±5 V: 16 bit
Integration time, parameterizableYes
Interference voltage suppression for interference frequency f1 in Hz60 / 50 Hz / no
Conversion time (per channel)0.04 ms; Without noise suppression 17/20 ms per channel with error
Smoothing of measured values
parameterizableYes; In 4 stages: 1x, 4x, 16x, 32x cycle time
Step: NoneYes; 1x
Step: lowYes; 4x
Step: MediumYes; 16x
Step: HighYes; 32x
Encoder
Connection of signal encoders
for voltage measurementYes
Errors/accuracies
Linearity error (relative to input range), (+/-)0.01 %
Temperature error (relative to input range), (+/-)0.003 %/K
Crosstalk between the inputs, min.-100 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)0.01 %
Operational error limit in overall temperature range
Voltage, relative to input range, (+/-)0.1 %; 0.2% without interference frequency suppression
Basic error limit (operational limit at 25 °C)
Voltage, relative to input range, (+/-)0.05 %; 0.1% without interference frequency suppression
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
Series mode interference (peak value of interference < rated value of input range), min.90 dB
Common mode interference (USS < 2.5 V) , min.100 dB
Isochronous mode
Isochronous operation (application synchronized up to terminal)Yes
Interrupts/diagnostics/status information
Alarms
Hardware interruptYes
Diagnostic messages
Wire-breakYes; Measuring range 1 to 5 V only
Group errorYes
Overflow/underflowYes
Diagnostics indication LED
Group error SF (red)Yes
Parameter
Remark12 bytes, 4 bytes in compatibility mode
Measurement type/rangedeactivated / ±5 V / 1 to 5 V / ±10 V
Group diagnosticsDisable / enable
Overflow/underflowDisable / enable
Potential separation
Potential separation analog inputs
between the channelsNo; however, increased permissible potential difference between the inputs.
between the channels and backplane busYes
Between the channels and load voltage L+Yes
Permissible potential difference
between the inputs (UCM)140 V DC/100 V AC
Isolation
Isolation tested with500 V DC
Dimensions
Width15 mm
Height81 mm
Depth52 mm
Weights
Weight, approx.45 g
last modified:03/13/2019