6ES7134-4LB00-0AB0
ET200S, EL-MOD., 2AI HF U, +/-10V, 1..5V

From SIEMENS

SIMATIC DP, ELECTRONIC MODULE 2 AI HIGH FEATURE U FOR ET 200S, 15 MM WIDE, +/-10V, 15 BI + SIGN, +/-5V,15BIT+SIGN, 1..5V, 15BIT, OPERATIONAL LIMITS +/-0.1% WITH LED SF (GROUP FAULT)
Supply voltage
Load voltage L+
Rated value (DC)24 V; From power module
Reverse polarity protectionYes
Input current
from load voltage L+ (without load), max.53 mA
from backplane bus 3.3 V DC, max.10 mA
Power loss
Power loss, typ.0.85 W
Address area
Address space per module
Address space per module, max.4 byte
Analog inputs
Number of analog inputs2
permissible input voltage for voltage input (destruction limit), max.35 V; 35 V continuous; 75 V for max. 1 ms
Cycle time (all channels) max.1 channel active per module: 75 / 90 / 30 ms; 2 channels active per module: 175 / 210 / 78 ms
Input ranges (rated values), voltages
1 V to 5 VYes
-10 V to +10 VYes
-5 V to +5 VYes
Cable length
shielded, max.200 m
Analog value generation for the inputs
Measurement principleintegrating
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.16 bit; 1 to 5 V: 15 bits, ±10 V: 16 bits, ±5 V: 16 bits
Integration time, parameterizableYes
Integration time (ms)16,67 / 20 / 7,5 ms
Interference voltage suppression for interference frequency f1 in Hz60 / 50 Hz / no
Conversion time (per channel)1 channel active per module: 25 / 30 / 10 ms; 2 channels active per module: 58.3 / 70 / 26 ms
Smoothing of measured values
parameterizableYes; In four stages by means of digital filtering
Step: NoneYes; 1x cycle time
Step: lowYes; 4x cycle time
Step: MediumYes; 32x cycle time
Step: HighYes; 64x cycle time
Errors/accuracies
Linearity error (relative to input range), (+/-)0.03 %
Temperature error (relative to input range), (+/-)0.003 %/K; ±0.003%: Calibration enabled; ±0.015%: Calibration disabled
Crosstalk between the inputs, min.-100 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)0.01 %
Operational error limit in overall temperature range
Voltage, relative to input range, (+/-)0.1 %; ±0,1 %: Calibration enabled; ±0.5%: calibration disabled
Basic error limit (operational limit at 25 °C)
Voltage, relative to input range, (+/-)0.05 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
Series mode interference (peak value of interference < rated value of input range), min.90 dB
Common mode interference (USS < 2.5 V) , min.100 dB
Isochronous mode
Isochronous operation (application synchronized up to terminal)No
Interrupts/diagnostics/status information
Diagnostic messages
Group errorYes
Overflow/underflowYes
Diagnostics indication LED
Group error SF (red)Yes
Parameter
Remark4 byte
Diagnostics wire breakDisable / enable
Measurement type/rangedeactivated / ±5 V / 1 to 5 V / ±10 V
Group diagnosticsDisable / enable
Overflow/underflowDisable / enable
Potential separation
Potential separation analog inputs
between the channelsNo
between the channels and backplane busYes
Between the channels and load voltage L+Yes
Permissible potential difference
between the inputs (UCM)140 V DC/100 V AC
Isolation
Isolation tested with500 V DC
Dimensions
Width15 mm
Height81 mm
Depth52 mm
Weights
Weight, approx.40 g