6ES7134-4JD00-0AB0
ET200S, El-Mod., 4AI TC, +/-80MV, 15Bit

From SIEMENS

SIMATIC DP, Electronics module for ET 200S, 4 AI TC, +/-80 mV; 15 mm width, 15 bit+sign with SF LED (group fault)
Supply voltage
Load voltage L+
Rated value (DC)24 V; From power module
Reverse polarity protectionYes
Input current
from load voltage L+ (without load), max.30 mA
from backplane bus 3.3 V DC, max.10 mA
Power loss
Power loss, typ.0.6 W
Address area
Address space per module
Address space per module, max.8 byte
Analog inputs
Number of analog inputs4
permissible input voltage for voltage input (destruction limit), max.10 V; Permanent
Cycle time (all channels) max.Number of active channels per module x basic conversion time
Technical unit for temperature measurement adjustableNo; Celsius
Input ranges (rated values), voltages
-80 mV to +80 mVYes
Input resistance (-80 mV to +80 mV)1 MΩ
Input ranges (rated values), thermocouples
Type BYes
Input resistance (Type B)1 MΩ
Type EYes
Input resistance (Type E)1 MΩ
Type JYes
Input resistance (type J)1 MΩ
Type KYes
Input resistance (Type K)1 MΩ
Type LYes
Input resistance (Type L)1 MΩ
Type NYes
Input resistance (Type N)1 MΩ
Type RYes
Input resistance (Type R)1 MΩ
Type SYes
Input resistance (Type S)1 MΩ
Type TYes
Input resistance (Type T)1 MΩ
Thermocouple (TC)
Temperature compensation
— internal temperature compensationNot possible
— external temperature compensation with compensations socketYes; possible, one external compensating box per channel
Characteristic linearization
parameterizableYes; Type B, E, J, K, L, N, R, S, T to IEC 584
Cable length
shielded, max.50 m
Analog value generation for the inputs
Measurement principleintegrating
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.16 bit; 15 bit + sign
Integration time, parameterizableYes
Integration time (ms)16,7 / 20 ms
Interference voltage suppression for interference frequency f1 in Hz50 / 60 Hz
Conversion time (per channel)65 ms; 55 / 65 ms (additional 20 ms on activated wire-break test)
Smoothing of measured values
parameterizableYes; In four stages by means of digital filtering
Step: NoneYes; 1x cycle time
Step: lowYes; 4x cycle time
Step: MediumYes; 32x cycle time
Step: HighYes; 64x cycle time
Encoder
Connection of signal encoders
for voltage measurementYes
Errors/accuracies
Linearity error (relative to input range), (+/-)0.01 %
Temperature error (relative to input range), (+/-)0.005 %/K
Crosstalk between the inputs, min.-50 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)0.05 %
Operational error limit in overall temperature range
Voltage, relative to input range, (+/-)0.6 %
Basic error limit (operational limit at 25 °C)
Voltage, relative to input range, (+/-)0.4 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
Series mode interference (peak value of interference < rated value of input range), min.70 dB
Common mode interference (USS < 2.5 V) , min.90 dB
Isochronous mode
Isochronous operation (application synchronized up to terminal)No
Interrupts/diagnostics/status information
Diagnostic messages
Diagnostic information readableYes
Wire-breakYes; A break in the wire is only detected for thermocouples
Group errorYes
Overflow/underflowYes
Diagnostics indication LED
Group error SF (red)Yes
Parameter
Remark4 byte
Diagnostics wire breakDisable / enable (wire break is detected only in thermocouples)
Measurement type/rangeDeactivated/ ±80 mV/ TC-EL Type T (Cu-CuNi)/ TC-EL Type K (NiCr-Ni)/ TC-EL Type B (PtRh-PtRh)/ TC-EL Type c (Wer-Wer) TC-EL Type N (NiCrSi-NiSi)/ TC-EL Type E (NiCr-CuNi)/ TC-EL Type R (PtRh-Pt)/ TC-EL Type S (PtRh-Pt)/ TC-EL Type J (Fe-Cu-Ni)/ TC
Group diagnosticsDisable / enable
Overflow/underflowDisable / enable
Comparison pointnone / RTD
Comparison point numberNone / 1 / 2 / 3 / 4 / 5 / 6 / 7 / 8
Potential separation
Potential separation analog inputs
between the channelsNo
between the channels and backplane busYes
Between the channels and load voltage L+Yes
Permissible potential difference
Between the inputs and MANA (UCM)2 V AC PP
between MANA and M internally (UISO)75 V DC/60 V AC
Isolation
Isolation tested with500 V DC
Dimensions
Width15 mm
Height81 mm
Depth52 mm
Weights
Weight, approx.40 g
last modified:03/13/2019