6ES7134-4GB51-0AB0
ET200S, El-Mod., 2AI HS I-2DMU, 0-20mA,

From SIEMENS

***Spare part*** SIMATIC DP, Electronics module ET200S: 2AI High Speed I-2-wire 4-20 mA; 14 bit, 15 mm width, for 2-wire transducer Cycle time of module: 1 ms, with SF LED (group fault)
Supply voltage
Load voltage L+
Rated value (DC)24 V; From power module
Short-circuit protectionYes; Destruction limit 35 mA per channel
Reverse polarity protectionYes
Input current
from load voltage L+ (without load), max.35 mA; Without encoder supply voltage
from backplane bus 3.3 V DC, max.10 mA
Encoder supply
Number of outputs2
Type of output voltageL+ (-2.5 V), under load
Short-circuit protectionYes; Electronic
Output current
Rated value90 mA; both channels
permissible range, lower limit0 mA
permissible range, upper limit90 mA
Power loss
Power loss, typ.0.8 W
Address area
Address space per module
Address space per module, max.4 byte
Analog inputs
Number of analog inputs2
permissible input current for current input (destruction limit), max.60 mA
Cycle time (all channels) max.1 ms; Per module
Input ranges (rated values), currents
Input resistance (0 to 20 mA)0.05 kΩ
4 mA to 20 mAYes; on 50 ohms
Cable length
shielded, max.200 m
Analog value generation for the inputs
Measurement principleActual value encryption
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.13 bit; 4 to 20 mA: 13 bit, 0 to 20 mA: 13 bit
Conversion time (per channel)0.1 ms
Smoothing of measured values
parameterizableYes; In four stages by means of digital filtering
Step: NoneYes; 1x cycle time
Step: lowYes; 64x cycle time
Step: MediumYes; 128x cycle time
Step: HighYes; 512x cycle time
Encoder
Connection of signal encoders
for current measurement as 2-wire transducerYes
— Burden of 2-wire transmitter, max.670 Ω
Errors/accuracies
Linearity error (relative to input range), (+/-)0.01 %
Temperature error (relative to input range), (+/-)0.01 %/K
Crosstalk between the inputs, min.50 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)0.05 %
Operational error limit in overall temperature range
Current, relative to input range, (+/-)0.3 %
Basic error limit (operational limit at 25 °C)
Current, relative to input range, (+/-)0.2 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
Series mode interference (peak value of interference < rated value of input range), min.70 dB
Isochronous mode
Isochronous operation (application synchronized up to terminal)Yes
Interrupts/diagnostics/status information
Alarms
Hardware interruptYes; Parameterizable
Diagnostic messages
Wire-breakYes
Group errorYes
Overflow/underflowYes
Diagnostics indication LED
Group error SF (red)Yes
Parameter
Remark12 byte
Diagnostics wire breakDisable / enable
Measurement type/rangeDeactivated / 0 to 20 mA / 4 to 20 mA
Group diagnosticsDisable / enable
Overflow/underflowDisable / enable
Potential separation
Potential separation analog inputs
between the channelsNo
between the channels and backplane busYes
Between the channels and load voltage L+No
Permissible potential difference
between MANA and M internally (UISO)75 V DC/60 V AC
Isolation
Isolation tested with500 V DC
Dimensions
Width15 mm
Height81 mm
Depth52 mm
Weights
Weight, approx.40 g