| SIMATIC DP, 5 electronic modules for ET 200S, 4 DO High Feature 24 V DC/2 A, 15 mm width, Short-circuit diagnostics, SF LED 5 units per packing unit |
Supply voltage |
Reverse voltage protection | Yes; when using the same load voltage as on the power module |
Load voltage L+ |
Rated value (DC) | 24 V; From power module |
Reverse polarity protection | Yes; polarity reversal can lead to the digital outputs being connected through |
Input current |
from load voltage L+ (without load), max. | 5 mA; Per channel |
from backplane bus 3.3 V DC, max. | 10 mA |
Power loss |
Power loss, typ. | 1.6 W |
Address area |
Address space per module |
Address space per module, max. | 1 byte |
with packing | 4 bit |
Digital outputs |
Number of digital outputs | 4 |
Short-circuit protection | Yes |
Response threshold, typ. | 5 to 10 A |
Limitation of inductive shutdown voltage to | L+ -(37 to 41V) |
Controlling a digital input | Yes |
Load resistance range |
lower limit | 12 Ω |
upper limit | 3 400 Ω |
Output voltage |
for signal "1", min. | L+ (-1.0 V) |
Output current |
for signal "1" rated value | 2 A |
for signal "1" permissible range, min. | 7 mA |
for signal "1" permissible range, max. | 2.4 A |
for signal "0" residual current, max. | 0.5 mA |
Output delay with resistive load |
"0" to "1", max. | 250 µs |
"1" to "0", max. | 400 µs |
Parallel switching of two outputs |
for uprating | No |
for redundant control of a load | Yes; per module |
Switching frequency |
with resistive load, max. | 100 Hz |
with inductive load, max. | 2 Hz |
on lamp load, max. | 10 Hz |
Total current of the outputs |
Current per module, max. | 4 A |
Cable length |
shielded, max. | 1 000 m |
unshielded, max. | 600 m |
Isochronous mode |
Isochronous operation (application synchronized up to terminal) | Yes |
Interrupts/diagnostics/status information |
Diagnostics function | Yes |
Diagnostic messages |
Short-circuit | Yes; Module-wise |
Diagnostics indication LED |
Group error SF (red) | Yes; SF-LED (red) |
Status indicator digital output (green) | Yes; Per channel |
Potential separation |
Potential separation digital outputs |
between the channels | No |
between the channels and backplane bus | Yes |
Isolation |
Isolation tested with | 500 V DC |
Dimensions |
Width | 15 mm |
Height | 81 mm |
Depth | 52 mm |
Weights |
Weight, approx. | 40 g |