| *** SPARE PART*** SIMATIC DP, ELECTRONIC MODULE DIGITAL, FOR ET 200B, W=235MM, 32DI 24V DC, 3MS INPUT DELAY |
General information |
Usable terminal block | TB2/DC, TB2-4/DC, TB4/DC, TB4-4/DC |
Supply voltage |
Rated value (DC) | 24 V; L5+; value at t < 0.5 s: 35 V |
permissible range, lower limit (DC) | 18.5 V |
permissible range, upper limit (DC) | 30.2 V |
Input current |
Current consumption, typ. | 70 mA; From L5+; logic |
Current consumption, max. | 1 000 mA; from L5+; sensor |
I²t | 0.05 A²·s; with starting current inrush |
Power loss |
Power loss, typ. | 4.8 W |
Digital inputs |
Number of digital inputs | 32 |
Input voltage |
Rated value (DC) | 24 V |
for signal "0" | -30 to +5V |
for signal "1" | 13 to 30V |
Input current |
for signal "1", typ. | 4 mA; At 24 V min. 2 mA |
Input delay (for rated value of input voltage) |
for standard inputs |
— at "0" to "1", max. | 3 ms |
Cable length |
unshielded, max. | 100 m |
Encoder |
Connectable encoders |
2-wire sensor | Yes |
— permissible quiescent current (2-wire sensor), max. | 1.5 mA |
Interfaces |
PROFIBUS DP |
Transmission rate, max. | 12 Mbit/s |
Protocols |
Bus protocol/transmission protocol | PROFIBUS DP |
PROFIBUS DP |
Services |
— FREEZE capability | Yes |
Interrupts/diagnostics/status information |
Diagnostics indication LED |
RUN LED | Yes |
Bus fault BF (red) | Yes |
Status indicator digital input (green) | Yes |
Potential separation |
between electronic block and PROFIBUS DP | Yes |
Potential separation digital inputs |
Potential separation digital inputs | No |
Degree and class of protection |
Degree of protection acc. to EN 60529 | IP20 |
Ambient conditions |
Ambient temperature during operation |
horizontal installation, min. | 0 °C |
horizontal installation, max. | 60 °C; 40°C for other mountings |
Air pressure acc. to IEC 60068-2-13 |
permissible range, lower limit | 795 hPa |
permissible range, upper limit | 1 080 hPa |
Relative humidity |
Operation, min. | 15 % |
Operation, max. | 95 %; RH class 2 in accordance with IEC 1131-2 |
Vibrations |
Operation, tested according to IEC 60068-2-6 | Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g) |
Shock testing |
tested according to IEC 60068-2-27 | Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms |
Connection method |
Design of electrical connection for the inputs and outputs | Screw-type and spring-loaded terminals, permanent wiring; 3 and 4-wire connection |
Dimensions |
Width | 235 mm; EB and TB |
Height | 130 mm; EB and TB |
Depth | 60 mm; EB and TB |
Weights |
Weight, approx. | 800 g; EB and TB |