6EP4333-0SB00-0AY0
SITOP PSU2600 24 V/5 A

From SIEMENS

SITOP PSU2600 24 V/5 A
SITOP PSU2600 24 V/5 A Stabilized power supply input: 230 V AC output: 24 V DC/5 A
Input
Input1-phase AC or DC
Rated voltage value Vin rated120 ... 230 V
Voltage range AC85 ... 264 V
Supply voltage
at DC110 ... 220 V
Input voltage
at DC88 ... 265 V
Wide-range inputYes
Mains buffering at Iout rated, min.30 ms; at Vin = 230 V
Rated line frequency 150 Hz
Rated line frequency 260 Hz
Rated line range47 ... 63 Hz
Input current
at rated input voltage 120 V2.5 A
at rated input voltage 230 V1.4 A
Switch-on current limiting (+25 °C), max.36 A
Built-in incoming fuse3.15 A
Protection in the mains power input (IEC 898)None required. Fuse protection starting from 6 A Char. C possible
Output
OutputControlled, isolated DC voltage
Rated voltage Vout DC24 V
Total tolerance, static ±3 %
Static mains compensation, approx.0.1 %
Static load balancing, approx.0.2 %
Residual ripple peak-peak, max.50 mV
Spikes peak-peak, max. (bandwidth: 20 MHz)200 mV
Adjustment range24 ... 28.8 V
Product function Output voltage adjustableYes
Output voltage settingvia potentiometer; max. 120 W
Status displayGreen LED for 24 V OK
SignalingRelay contact (NO contact, rating 60 V DC/ 0.3 A) for "24 V OK"
On/off behaviorNo overshoot of Vout (soft start)
Startup delay, max.1 s
Voltage increase time of the output voltage maximum500 ms
Rated current value Iout rated5 A
Current range0 ... 5 A
Note+60 °C
Supplied active power typical120 W
Constant overload current
on short-circuiting during the start-up typical6 A
Parallel switching for enhanced performanceNo
Efficiency
Efficiency at Vout rated, Iout rated, approx.89 %
Power loss at Vout rated, Iout rated, approx.15 W
Power loss [W] during no-load operation maximum1 W
Closed-loop control
Dynamic mains compensation (Vin rated ±15 %), max.0.1 %
Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ.1 %
Load step setting time 50 to 100%, typ.0.2 ms
Load step setting time 100 to 50%, typ.0.2 ms
Dynamic load smoothing (Iout: 10/90/10 %), Uout ± typ.2 %
Load step setting time 10 to 90%, typ.0.2 ms
Load step setting time 90 to 10%, typ.0.2 ms
Setting time maximum10 ms
Protection and monitoring
Output overvoltage protection< 32 V
Current limitation, typ.6 A
Property of the output Short-circuit proofYes
Short-circuit protectionShutdown and periodic restart attempts
Enduring short circuit current RMS value
typical6 A
Safety
Primary/secondary isolationYes
Galvanic isolationSafety extra low output voltage Vout according to EN 60950-1
Protection classClass I
Leakage current
maximum3.5 mA
typical1.1 mA
CE markYes
UL/cUL (CSA) approvalcULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259
Explosion protection-
FM approval-
CB approvalYes
Marine approval-
Degree of protection (EN 60529)IP20
EMC
Emitted interferenceEN 55022 Class B
Supply harmonics limitationEN 61000-3-2
Noise immunityEN 61000-6-2
Operating data
Ambient temperature
during operation0 ... 60 °C
— Notewith natural convection
during transport-40 ... +85 °C
during storage-40 ... +85 °C
Humidity class according to EN 60721Climate class 3K3, no condensation
Mechanics
Connection technologyscrew-type terminals
Connections
Supply inputL1, N, PE: 1 screw terminal each for 0.2 ... 2.5 mm² single-core/finely stranded
Output+, -: 2 screw terminals each for 0.2 ... 2.5 mm²
AuxiliarySignal: 1 screw terminal each for 0.14 ... 1.5 mm²
Width of the enclosure42 mm
Height of the enclosure125 mm
Depth of the enclosure125 mm
Required spacing
top50 mm
bottom50 mm
left0 mm
right0 mm
Weight, approx.0.6 kg
Product feature of the enclosure housing for side-by-side mountingYes
InstallationSnaps onto DIN rail EN 60715 35x7.5/15
Other informationSpecifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)

External links