| SITOP UPS1100 BAT.MODUL 24V/5AH LIFEPO |
SITOP UPS1100 Battery module with warning not closed Lithium iron phophate batteries for SITOP DC-USV modules DC 24 V 5 Ah |
Charging current charging voltage |
End-of-charge voltage at DC | |
at -10 °C recommended | 28.8 V |
at 0 °C recommended | 28.8 V |
at 10 °C recommended | 28.8 V |
at 20 °C recommended | 28.8 V |
at 30 °C recommended | 28.8 V |
at 40 °C recommended | 28.8 V |
at 50 °C recommended | 28.8 V |
Output |
Rated current value Iout rated | 20 A |
Permissible charging current, max. | 2.1 A |
Rated voltage Vout DC | 24 V |
Safety |
Short-circuit protection | Battery fuse 25 A/32 V (FKS blade-type fuse + holder); overcurrent switch-off at 60 A > 30 ms/min and 24 A > 5 s/min |
Design of the overload protection | Valve control |
Status display | LED green: Battery OK; LED flashing green: Error or warning; OFF: No communication |
Safety |
Protection class | Class III |
Degree of protection (EN 60529) | IP20 |
Approvals |
CE mark | Yes |
UL/cUL (CSA) approval | cURus-Recognized (UL 1778, CSA C22.2 No. 107.1), File E219627 |
Explosion protection | - |
Approvals | Yes |
Marine approval | DNV GL, ABS |
environmental conditions |
Operating data note | For storage, mounting and operation of batteries, the relevant DIN/VDE regulations or country-specific regulations (e.g. VDE 0510 Part 2/EN 50272-2) must be observed. |
Ambient temperature | |
during operation | -20 ... +50 °C |
during transport | -40 ... +60 °C |
during storage | -40 ... +60 °C |
Relative temporary capacity loss at 20 °C in a month typical | 3 % |
Service life |
Service life of energy storage | |
typical Note | capacity falls to 50 % of original capacity |
at 20 °C typical | 15 y |
at 30 °C typical | 10 y |
at 40 °C typical | 9 y |
at 50 °C typical | 2 y |
Ambient temperature during storage Note | Along with the storage and operating temperature, other factors such as the duration of the storage period and the charge status during storage have a decisive influence on the possible useful life. Batteries should therefore be stored as briefly as possible, always fully charged, and within the temperature range 0 to +20 °C. |
Mechanics |
Connection technology | screw-type terminals |
Connection for power supply unit | 1 screw terminal each for 0.5 ... 16 mm² for + BAT and - BAT |
Type of electrical connection for control circuit and status message | 1 screw terminal each for 0.14 ... 4 mm² |
Product component belonging to | Accessories pack with solid-state circuitry fuse 25 A |
Width of the enclosure | 189 mm |
Height of the enclosure | 186 mm |
Depth of the enclosure | 113 mm |
Installation width | 189 mm |
Installation height | 201 mm |
Weight, approx. | 3.4 kg |
Installation | snaps onto DIN rail EN 60715 35x15 or keyhole mounting for hooking in to M4 screws |
Number of cells | 16 |
Battery | 5 A·h |
Reference code acc. to DIN EN 81346-2 | G |
Other information | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |
| |