6EP3344-0SB00-0AY0
SITOP PSU100E 48 V/5 A

From SIEMENS

SITOP PSU100E 48 V/5 A
SITOP PSU100E 48 V/5 A Stabilized power supply Input: 120 / 230 V AC Output: 48 V DC/5 A
Input
Input1-phase AC
Supply voltage
1 at AC Rated value100 V
2 at AC Rated value230 V
Input voltage
1 at AC85 ... 132 V
2 at AC170 ... 264 V
Wide-range inputNo
Mains bufferingat Vin = 120/230 V
Mains buffering at Iout rated, min.30 ms; at Vin = 120/230 V
Rated line frequency 150 Hz
Rated line frequency 260 Hz
Rated line range47 ... 63 Hz
Input current
at rated input voltage 120 V4.4 A
at rated input voltage 230 V2 A
Switch-on current limiting (+25 °C), max.58 A
I²t, max.1.5 A²·s
Built-in incoming fuseT 6.3 A (not accessible), soldered
Protection in the mains power input (IEC 898)Recommended miniature circuit breaker: from 10 A characteristic C
Output
OutputControlled, isolated DC voltage
Rated voltage Vout DC48 V
Total tolerance, static ±3 %
Static mains compensation, approx.0.2 %
Static load balancing, approx.0.5 %
Residual ripple peak-peak, max.50 mV
Residual ripple peak-peak, typ.30 mV
Spikes peak-peak, max. (bandwidth: 20 MHz)150 mV
Spikes peak-peak, typ. (bandwidth: 20 MHz)100 mV
Adjustment range48 ... 54 V
Product function Output voltage adjustableYes
Output voltage settingvia potentiometer; max. 240 W
Status displayGreen LED for 48 V OK
SignalingRelay contact (NO contact, rating 60 V DC/ 0.3 A) for 48 V OK
On/off behaviorOvershoot of Vout approx. 2 %
Startup delay, max.1.5 s
Voltage rise, typ.15 ms
Voltage increase time of the output voltage maximum500 ms
Rated current value Iout rated5 A
Current range0 ... 5 A
Note+60 ... +70 °C: Derating 5%/K
Supplied active power typical240 W
Parallel switching for enhanced performanceYes
Numbers of parallel switchable units for enhanced performance2
Efficiency
Efficiency at Vout rated, Iout rated, approx.92 %
Power loss at Vout rated, Iout rated, approx.12 W
Closed-loop control
Dynamic mains compensation (Vin rated ±15 %), max.0.3 %
Dynamic load smoothing (Iout: 10/90/10 %), Uout ± typ.1 %
Load step setting time 10 to 90%, typ.0.5 ms
Load step setting time 90 to 10%, typ.0.5 ms
Setting time maximum1 ms
Protection and monitoring
Output overvoltage protection< 60 V
Current limitation, typ.5.3 A
Property of the output Short-circuit proofYes
Short-circuit protectionElectronic shutdown, automatic restart
Enduring short circuit current RMS value
typical8.7 A
Safety
Primary/secondary isolationYes
Galvanic isolationSafety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178
Protection classClass I
Leakage current
maximum3.5 mA
typical1 mA
Degree of protection (EN 60529)IP20
Approvals
CE markYes
UL/cUL (CSA) approvalcULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259
Explosion protection-
FM approval-
CB approvalNo
Marine approval-
EMC
Emitted interferenceEN 61000-6-4
Supply harmonics limitationEN 61000-3-2
Noise immunityEN 61000-6-2
environmental conditions
Ambient temperature
during operation-25 ... +70 °C
— Notewith natural convection
during transport-40 ... +85 °C
during storage-40 ... +85 °C
Humidity class according to EN 60721Climate class 3K3, 5 … 95% no condensation
Mechanics
Connection technologyscrew-type terminals
Connections
Supply inputL, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm² single-core/finely stranded
Output+, -: 2 screw terminals each for 0.5 ... 2.5 mm²
Auxiliary13, 14 (alarm signal): 1 screw terminal each for 0.5 ... 2.5 mm²
Width of the enclosure42 mm
Height of the enclosure125 mm
Depth of the enclosure125 mm
Required spacing
top50 mm
bottom50 mm
left0 mm
right0 mm
Weight, approx.0.5 kg
Product feature of the enclosure housing for side-by-side mountingYes
InstallationSnaps onto DIN rail EN 60715 35x7.5/15
MTBF at 40 °C1 050 000 h
Other informationSpecifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)

External links