6EP3333-7LB00-0AX0
SITOP PSU6200 24 V3,7 A NEC CLASS II

From SIEMENS

SITOP PSU6200 24 V3,7 A NEC CLASS II
SITOP PSU6200 3.7 A NEC class II Stabilized power supply Input: 120 - 230 V AC, (120 - 240 V DC) Output: 24 V DC/3.7 A
Input
Input1-phase AC or DC
Rated voltage value Vin rated120 ... 230 V
Voltage range AC85 ... 264 V
Supply voltage
at DC120 ... 240 V
Input voltage
at DC99 ... 275 V
Wide-range inputYes
Overvoltage resistance300 V AC for 30 s
Mains buffering at Iout rated, min.90 ms; at Vin = 230 V
Rated line frequency 150 Hz
Rated line frequency 260 Hz
Rated line range47 ... 63 Hz
Input current
at rated input voltage 120 V1.5 A
at rated input voltage 230 V0.9 A
Switch-on current limiting (+25 °C), max.29 A
Built-in incoming fuse3.15 A
Output
OutputControlled, isolated DC voltage
Number of outputs1
Rated voltage Vout DC24 V
Total tolerance, static ±3 %
Static mains compensation, approx.0.2 %
Static load balancing, approx.0.3 %
Residual ripple peak-peak, max.30 mV
Residual ripple peak-peak, typ.20 mV
Spikes peak-peak, max. (bandwidth: 20 MHz)100 mV
Spikes peak-peak, typ. (bandwidth: 20 MHz)60 mV
Adjustment range24 ... 28 V
Product function Output voltage adjustableYes
Output voltage settingvia potentiometer; max. 89 W (106 W up to 45°C)
Status displayGreen LED for 24 V OK
SignalingElectronic contact (NO contact, contact rating 60 V DC/0.1 A) for 24 V O.K. or diagnostic interface
On/off behaviorOvershoot of Vout < 2 %
Startup delay, max.0.5 s
Voltage rise, typ.100 ms
Rated current value Iout rated3.7 A
Current range0 ... 3.7 A
Supplied active power typical89 W
Short-term overload current
on short-circuiting during the start-up typical3.7 A
at short-circuit during operation typical3.7 A
Efficiency
Efficiency at Vout rated, Iout rated, approx.89.3 %
Power loss at Vout rated, Iout rated, approx.11 W
Power loss [W] during no-load operation maximum2.2 W
Closed-loop control
Dynamic load smoothing (Iout: 10/90/10 %), Uout ± typ.2 %
Load step setting time 10 to 90%, typ.2 ms
Load step setting time 90 to 10%, typ.2 ms
Setting time maximum3 ms
Protection and monitoring
Output overvoltage protection< 32 V
Current limitation, typ.3.7 A
Property of the output Short-circuit proofYes
Short-circuit protectionShutdown and periodic restart attempts
Safety
Primary/secondary isolationYes
Galvanic isolationSafety extra low output voltage Vout according to EN 60950-1
Protection classClass I
Leakage current
maximum3.5 mA
CE markYes
UL/cUL (CSA) approvalcULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)
Explosion protection-
FM approval-
CB approvalYes
Regulatory Compliance Mark (RCM)No
Marine approvalin process: DNV GL, ABS
Degree of protection (EN 60529)IP20
EMC
Emitted interferenceEN 55022 Class B
Supply harmonics limitationEN 61000-3-2
Noise immunityEN 61000-6-2
Operating data
Ambient temperature
during operation-25 ... +70 °C
— Notewith natural convection
during transport-40 ... +85 °C
during storage-40 ... +85 °C
Humidity class according to EN 60721Climate class 3K3, no condensation
Mechanics
Connection technologyPush-in terminals
Connections
Supply inputL1/+, L2/N/-; PE PushIn for 0.5 ... 4 mm² single-core/finely stranded
Output+1, +2, -1, -2, -3: PushIn for 0.5 ... 2.5 mm²
Auxiliary13, 14 (alarm signal): 1 push-in terminal each for 0.2 ... 1.5 mm²
Width of the enclosure35 mm
Height of the enclosure135 mm
Depth of the enclosure125 mm
Required spacing
top45 mm
bottom45 mm
left0 mm
right0 mm
Product feature of the enclosure housing for side-by-side mountingYes
InstallationSnaps onto DIN rail EN 60715 35x7.5/15
Electrical accessoriesBuffer module, redundancy module
Mechanical accessoriesDevice identification label 20 mm × 7 mm, TI-grey 3RT2900-1SB20
Other informationSpecifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)