| SITOP BATTERY MODULE 24 V/12 AH |
SITOP rechargeable battery module 24 V/12 Ah with maintenance free Seaed lead batteries for SITOP DC-USV Module 6 A 15 A and 40 A |
Charging current charging voltage |
End-of-charge voltage at DC | |
at -10 °C recommended | 29 V |
at 0 °C recommended | 28.4 MV |
at 10 °C recommended | 27.8 V |
at 20 °C recommended | 27.3 V |
at 30 °C recommended | 26.8 V |
at 40 °C recommended | 26.6 V |
at 50 °C recommended | 26.3 V |
Output |
Permissible charging current, max. | 3 A |
Rated voltage Vout DC | 24 V |
Safety |
Short-circuit protection | Battery fuse 20 A/32 V (solid-state circuitry blade-type fuse + support) |
Design of the overload protection | Valve control |
Safety |
Protection class | Class III |
Degree of protection (EN 60529) | IP00 |
Approvals |
CE mark | Yes |
UL/cUL (CSA) approval | cURus-Recognized (UL 1778, CSA C22.2 No. 107.1), File E219627 |
Marine approval | DNV GL, ABS |
environmental conditions |
Operating data note | For storage, mounting and operation of lead-acid batteries, the relevant DIN/VDE regulations or country-specific regulations (e.g. VDE 0510 Part 2/EN 50272-2) must be observed. You must ensure that the battery site is sufficiently ventilated. Possible sources of ignition must be at least 50 cm away. |
Ambient temperature | |
during operation | -15 ... +50 °C |
during transport | -20 ... +50 °C |
during storage | -20 ... +50 °C |
Relative temporary capacity loss at 20 °C in a month typical | 3 % |
Service life |
Service life of energy storage | |
typical Note | capacity falls to 50 % of original capacity |
at 20 °C typical | 4 y |
at 30 °C typical | 2 y |
at 40 °C typical | 1 y |
at 50 °C typical | 0.5 y |
Ambient temperature during storage Note | Along with the storage and operating temperature, other factors such as the duration of the storage period and the charge status during storage have a decisive influence on the possible useful life. Batteries should therefore be stored as briefly as possible, always fully charged, and within the temperature range 0 to +20 °C. |
Mechanics |
Connection technology | spring-loaded terminals |
Connection for power supply unit | 1 screw terminal each for 0.08 ... 4 mm² for + BAT and - BAT |
Product component belonging to | Accessories pack with solid-state circuitry fuse 20 A and 30 A |
Width of the enclosure | 253 mm |
Height of the enclosure | 168 mm |
Depth of the enclosure | 121 mm |
Installation width | 273 mm |
Installation height | 188 mm |
Weight, approx. | 9 kg |
Installation | can be screwed onto flat surface (keyhole mounting for hooking in to M4 screws) |
Number of cells | 12 |
Battery | 12 A·h |
Reference code acc. to DIN EN 81346-2 | G |
Other information | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |
| |