6EP1935-6MF01
SITOP BATTERY MODULE 24 V/12 AH

From SIEMENS

SITOP BATTERY MODULE 24 V/12 AH
SITOP rechargeable battery module 24 V/12 Ah with maintenance free Seaed lead batteries for SITOP DC-USV Module 6 A 15 A and 40 A
Charging current charging voltage
End-of-charge voltage at DC
at -10 °C recommended29 V
at 0 °C recommended28.4 MV
at 10 °C recommended27.8 V
at 20 °C recommended27.3 V
at 30 °C recommended26.8 V
at 40 °C recommended26.6 V
at 50 °C recommended26.3 V
Output
Permissible charging current, max.3 A
Rated voltage Vout DC24 V
Safety
Short-circuit protectionBattery fuse 20 A/32 V (solid-state circuitry blade-type fuse + support)
Design of the overload protectionValve control
Safety
Protection classClass III
Degree of protection (EN 60529)IP00
Approvals
CE markYes
UL/cUL (CSA) approvalcURus-Recognized (UL 1778, CSA C22.2 No. 107.1), File E219627
Marine approvalDNV GL, ABS
environmental conditions
Operating data noteFor storage, mounting and operation of lead-acid batteries, the relevant DIN/VDE regulations or country-specific regulations (e.g. VDE 0510 Part 2/EN 50272-2) must be observed. You must ensure that the battery site is sufficiently ventilated. Possible sources of ignition must be at least 50 cm away.
Ambient temperature
during operation-15 ... +50 °C
during transport-20 ... +50 °C
during storage-20 ... +50 °C
Relative temporary capacity loss at 20 °C in a month typical3 %
Service life
Service life of energy storage
typical Notecapacity falls to 50 % of original capacity
at 20 °C typical4 y
at 30 °C typical2 y
at 40 °C typical1 y
at 50 °C typical0.5 y
Ambient temperature during storage NoteAlong with the storage and operating temperature, other factors such as the duration of the storage period and the charge status during storage have a decisive influence on the possible useful life. Batteries should therefore be stored as briefly as possible, always fully charged, and within the temperature range 0 to +20 °C.
Mechanics
Connection technologyspring-loaded terminals
Connection for power supply unit1 screw terminal each for 0.08 ... 4 mm² for + BAT and - BAT
Product component belonging toAccessories pack with solid-state circuitry fuse 20 A and 30 A
Width of the enclosure253 mm
Height of the enclosure168 mm
Depth of the enclosure121 mm
Installation width273 mm
Installation height188 mm
Weight, approx.9 kg
Installationcan be screwed onto flat surface (keyhole mounting for hooking in to M4 screws)
Number of cells12
Battery12 A·h
Reference code acc. to DIN EN 81346-2G
Other informationSpecifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)