| SITOP PSU200M 24 V/5 A, VARNISHED PCB |
SITOP PSU200M plus 5 A Stabilized power supply input: AC 120-230/230-500 V output: 24 V DC/5 A Option for with protective varnish |
Input |
Input | 1-phase and 2-phase AC |
Note | Set by means of selector switch on the device; starting from Vin > 90/180 V |
Supply voltage | |
1 at AC | 120 ... 230 V |
2 at AC | 230 ... 500 V |
Input voltage | |
1 at AC | 85 ... 264 V |
2 at AC | 176 ... 550 V |
Wide-range input | Yes |
Overvoltage resistance | 1300 Vpeak, 1.3 ms |
Mains buffering at Iout rated, min. | 25 ms; at Vin = 120/230 V, typ. 150 ms at Vin = 400 V |
Rated line frequency 1 | 50 Hz |
Rated line frequency 2 | 60 Hz |
Rated line range | 47 ... 63 Hz |
Input current | |
at rated input voltage 120 V | 2.2 A |
at rated input voltage 230 V | 1.2 A |
at rated input voltage 500 V | 0.61 A |
Switch-on current limiting (+25 °C), max. | 35 A |
I²t, max. | 1.7 A²·s |
Built-in incoming fuse | T 3.15 A (not accessible) |
Protection in the mains power input (IEC 898) | Recommended miniature circuit breaker at 1-phase operation: from 6 A (10 A) characteristic C (B); required at 2-phase operation: circuit breaker 2-pole connected or circuit breaker 3RV2011-1EA10 (setting 3.8 A) or 3RV2711-1ED10 (UL 489) at 230 V; 3RV2011-1DA10 (setting 3 A) or 3RV2711-1DD10 (UL 489) at 400/500 V |
Output |
Output | Controlled, isolated DC voltage |
Rated voltage Vout DC | 24 V |
Total tolerance, static ± | 3 % |
Static mains compensation, approx. | 0.1 % |
Static load balancing, approx. | 0.1 % |
Residual ripple peak-peak, max. | 50 mV |
Spikes peak-peak, max. (bandwidth: 20 MHz) | 200 mV |
Adjustment range | 24 ... 28.8 V |
Product function Output voltage adjustable | Yes |
Output voltage setting | via potentiometer |
Status display | Green LED for 24 V OK |
Signaling | Relay contact (NO contact, rating 60 V DC/ 0.3 A) for "24 V OK" |
On/off behavior | Overshoot of Vout approx. 3 % |
Startup delay, max. | 1 s |
Voltage rise, typ. | 50 ms |
Rated current value Iout rated | 5 A |
Current range | 0 ... 5 A |
Supplied active power typical | 120 W |
Short-term overload current | |
at short-circuit during operation typical | 15 A |
Duration of overloading capability for excess current | |
at short-circuit during operation | 25 ms |
Constant overload current | |
on short-circuiting during the start-up typical | 6 A |
Parallel switching for enhanced performance | Yes; switchable characteristic |
Numbers of parallel switchable units for enhanced performance | 2 |
Efficiency |
Efficiency at Vout rated, Iout rated, approx. | 88 % |
Power loss at Vout rated, Iout rated, approx. | 17 W |
Power loss [W] during no-load operation maximum | 4 W |
Closed-loop control |
Dynamic mains compensation (Vin rated ±15 %), max. | 0.1 % |
Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ. | 3 % |
Load step setting time 50 to 100%, typ. | 2 ms |
Load step setting time 100 to 50%, typ. | 2 ms |
Setting time maximum | 5 ms |
Protection and monitoring |
Output overvoltage protection | < 35 V |
Current limitation, typ. | 6 A |
Property of the output Short-circuit proof | Yes |
Short-circuit protection | Alternatively, constant current characteristic approx. 5.5 A or latching shutdown |
Enduring short circuit current RMS value | |
typical | 6 A |
Overload/short-circuit indicator | LED yellow for "overload", LED red for "latching shutdown" |
Safety |
Primary/secondary isolation | Yes |
Galvanic isolation | Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 |
Protection class | Class I |
Leakage current | |
maximum | 3.5 mA |
typical | 0.25 mA |
CE mark | Yes |
UL/cUL (CSA) approval | cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259 |
Explosion protection | IECEx Ex nA nC IIC T4 Gc; ATEX (EX) II 3G Ex nA nC IIC T4 Gc; cCSAus (CSA C22.2 No. 213, ANSI/ISA-12.12.01) Class I, Div. 2, Group ABCD, T3 |
FM approval | - |
CB approval | No |
Marine approval | ABS, DNV GL |
Degree of protection (EN 60529) | IP20 |
EMC |
Emitted interference | EN 55022 Class B |
Supply harmonics limitation | EN 61000-3-2 |
Noise immunity | EN 61000-6-2 |
Operating data |
Ambient temperature | |
during operation | -25 ... +70 °C |
— Note | with natural convection |
during transport | -40 ... +85 °C |
during storage | -40 ... +85 °C |
Humidity class according to EN 60721 | Climate class 3K3, no condensation |
Mechanics |
Connection technology | screw-type terminals |
Connections | |
Supply input | L, N, PE: 1 screw terminal each for 0.2 ... 2.5 mm² single-core/finely stranded |
Output | +, -: 2 screw terminals each for 0.2 ... 2.5 mm² |
Auxiliary | 13, 14 (alarm signal): 1 screw terminal each for 0.14 ... 1.5 mm² |
Width of the enclosure | 70 mm |
Height of the enclosure | 125 mm |
Depth of the enclosure | 121 mm |
Required spacing | |
top | 50 mm |
bottom | 50 mm |
left | 0 mm |
right | 0 mm |
Weight, approx. | 0.6 kg |
Product feature of the enclosure housing for side-by-side mounting | Yes |
Installation | Snaps onto DIN rail EN 60715 35x7.5/15 |
Electrical accessories | Buffer module |
MTBF at 40 °C | 1 123 973 h |
Other information | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |
| |