| SITOP POWER 24 V/5 A, FLAT DESIGN |
SITOP power 5 A, Special Line Stabilized power supply input: 120/230 V AC, output: 24 V DC/5 A |
Input |
Input | 1-phase AC |
Note | Set by means of selector switch on the device |
Supply voltage | |
1 at AC Rated value | 120 V |
2 at AC Rated value | 230 V |
Input voltage | |
1 at AC | 85 ... 132 V |
2 at AC | 170 ... 264 V |
Wide-range input | No |
Overvoltage resistance | 2.3 × Vin rated, 1.3 ms |
Mains buffering at Iout rated, min. | 20 ms; at Vin = 93/187 V |
Rated line frequency 1 | 50 Hz |
Rated line frequency 2 | 60 Hz |
Rated line range | 47 ... 63 Hz |
Input current | |
at rated input voltage 120 V | 2.2 A |
at rated input voltage 230 V | 1.2 A |
Switch-on current limiting (+25 °C), max. | 32 A |
Duration of inrush current limiting at 25 °C | |
maximum | 3 ms |
I²t, max. | 0.8 A²·s |
Built-in incoming fuse | T 3,15 A/250 V (not accessible) |
Protection in the mains power input (IEC 898) | Recommended miniature circuit breaker: from 6 A characteristic C |
Output |
Output | Controlled, isolated DC voltage |
Rated voltage Vout DC | 24 V |
Total tolerance, static ± | 1 % |
Static mains compensation, approx. | 0.1 % |
Static load balancing, approx. | 0.5 % |
Residual ripple peak-peak, max. | 150 mV |
Residual ripple peak-peak, typ. | 40 mV |
Spikes peak-peak, max. (bandwidth: 20 MHz) | 240 mV |
Spikes peak-peak, typ. (bandwidth: 20 MHz) | 100 mV |
Adjustment range | 22 ... 29 V |
Product function Output voltage adjustable | Yes |
Output voltage setting | via potentiometer |
Status display | Green LED for 24 V OK |
On/off behavior | No overshoot of Vout (soft start) |
Startup delay, max. | 2 s |
Voltage rise, typ. | 40 ms |
Rated current value Iout rated | 5 A |
Current range | 0 ... 5 A |
Supplied active power typical | 120 W |
Short-term overload current | |
on short-circuiting during the start-up typical | 20 A |
at short-circuit during operation typical | 20 A |
Duration of overloading capability for excess current | |
on short-circuiting during the start-up | 500 ms |
at short-circuit during operation | 500 ms |
Parallel switching for enhanced performance | Yes |
Numbers of parallel switchable units for enhanced performance | 2 |
Efficiency |
Efficiency at Vout rated, Iout rated, approx. | 88 % |
Power loss at Vout rated, Iout rated, approx. | 17 W |
Closed-loop control |
Dynamic mains compensation (Vin rated ±15 %), max. | 0.3 % |
Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ. | 0.5 % |
Load step setting time 50 to 100%, typ. | 0.1 ms |
Load step setting time 100 to 50%, typ. | 0.1 ms |
Protection and monitoring |
Output overvoltage protection | Additional control loop, shutdown at approx. 33 V, automatic restart |
Current limitation | 5.5 ... 6.5 A |
Property of the output Short-circuit proof | Yes |
Short-circuit protection | Electronic shutdown, automatic restart |
Enduring short circuit current RMS value | |
maximum | 5 A |
Overload/short-circuit indicator | - |
Safety |
Primary/secondary isolation | Yes |
Galvanic isolation | Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 |
Protection class | Class I |
Leakage current | |
maximum | 3.5 mA |
typical | 0.26 mA |
CE mark | Yes |
UL/cUL (CSA) approval | cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259 |
Explosion protection | - |
FM approval | - |
CB approval | No |
Marine approval | - |
Degree of protection (EN 60529) | IP20 |
EMC |
Emitted interference | EN 55022 Class B |
Supply harmonics limitation | - |
Noise immunity | EN 61000-6-2 |
Operating data |
Ambient temperature | |
during operation | 0 ... 60 °C |
— Note | with natural convection |
during transport | -40 ... +85 °C |
during storage | -40 ... +85 °C |
Humidity class according to EN 60721 | Climate class 3K3, no condensation |
Mechanics |
Connection technology | screw-type terminals |
Connections | |
Supply input | L, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm² single-core/finely stranded |
Output | L+, M: 3 screw terminals each for 0.5 ... 2.5 mm² |
Auxiliary | - |
Width of the enclosure | 160 mm |
Height of the enclosure | 130 mm |
Depth of the enclosure | 60 mm |
Required spacing | |
top | 50 mm |
bottom | 50 mm |
left | 0 mm |
right | 0 mm |
Weight, approx. | 0.6 kg |
Product feature of the enclosure housing for side-by-side mounting | Yes |
Installation | Snaps onto DIN rail EN 60715 35x7.5/15 |
MTBF at 40 °C | 1 250 000 h |
Other information | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |
| |