6EP1332-1SH31
SITOP POWER 24 V/3.5 A FOR S7-200

From SIEMENS

SITOP POWER 24 V/3.5 A FOR S7-200
SITOP power 3.5 A, Univ. Line Stabilized power supply input: 120/230 V AC, output: 24 V DC/3.5 A S7-200 Design
Input
Input1-phase AC
NoteSet via wire jumper
Supply voltage
1 at AC Rated value120 V
2 at AC Rated value230 V
Input voltage
1 at AC93 ... 132 V
2 at AC187 ... 264 V
Wide-range inputNo
Overvoltage resistance2.3 × Vin rated, 1.3 ms
Mains buffering at Iout rated, min.20 ms; at Vin = 187 V
Rated line frequency 150 Hz
Rated line frequency 260 Hz
Rated line range47 ... 63 Hz
Input current
at rated input voltage 120 V1.65 A
at rated input voltage 230 V0.95 A
Switch-on current limiting (+25 °C), max.33 A
Duration of inrush current limiting at 25 °C
maximum3 ms
I²t, max.1 A²·s
Built-in incoming fuseT 2.5 A/250 V (not accessible)
Protection in the mains power input (IEC 898)Recommended: 2-pole miniature circuit breaker from 10 A characteristic C or from 6 A characteristic D
Output
OutputControlled, isolated DC voltage
Rated voltage Vout DC24 V
Total tolerance, static ±5 %
Static mains compensation, approx.0.1 %
Static load balancing, approx.0.2 %
Residual ripple peak-peak, max.150 mV
Residual ripple peak-peak, typ.30 mV
Spikes peak-peak, max. (bandwidth: 20 MHz)240 mV
Spikes peak-peak, typ. (bandwidth: 20 MHz)110 mV
Product function Output voltage adjustableNo
Output voltage setting-
Status display-
On/off behaviorNo overshoot of Vout (soft start)
Startup delay, max.1 s
Voltage rise, typ.80 ms
Rated current value Iout rated3.5 A
Current range0 ... 3.5 A
Supplied active power typical84 W
Short-term overload current
on short-circuiting during the start-up typical5 A
at short-circuit during operation typical5 A
Duration of overloading capability for excess current
on short-circuiting during the start-up100 ms
at short-circuit during operation100 ms
Parallel switching for enhanced performanceYes
Numbers of parallel switchable units for enhanced performance5
Efficiency
Efficiency at Vout rated, Iout rated, approx.84 %
Power loss at Vout rated, Iout rated, approx.16 W
Closed-loop control
Dynamic mains compensation (Vin rated ±15 %), max.0.3 %
Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ.3 %
Setting time maximum5 ms
Protection and monitoring
Output overvoltage protectionYes, according to EN 60950-1
Current limitation, typ.3.8 A
Property of the output Short-circuit proofYes
Short-circuit protectionConstant current characteristic up to typ. 14 V, electronic shutdown below that, automatic restart
Enduring short circuit current RMS value
maximum4 A
Overload/short-circuit indicator-
Safety
Primary/secondary isolationYes
Galvanic isolationSafety extra low output voltage Vout according to EN 60950-1
Protection classClass I
Leakage current
maximum3.5 mA
CE markYes
UL/cUL (CSA) approvalcULus-Listed (UL 508, CSA C22.2 No. 142), File E143289
Explosion protection-
FM approval-
CB approvalNo
Marine approval-
Degree of protection (EN 60529)IP20
EMC
Emitted interferenceEN 55022 Class B
Supply harmonics limitationEN 61000-3-2
Noise immunityEN 61000-6-2
Operating data
Ambient temperature
during operation0 ... 60 °C
— Notewith natural convection
during transport-40 ... +85 °C
during storage-40 ... +85 °C
Humidity class according to EN 60721Climate class 3K3, no condensation
Mechanics
Connection technologyscrew-type terminals
Connections
Supply inputL, N, PE: 1 screw terminal each for 0.5 ... 1.5 mm² single-core/finely stranded
OutputL+: 1 screw terminal for 0.5 ... 1 mm²; M: 2 screw terminals for 0.5 ... 1 mm²
Auxiliary-
Width of the enclosure160 mm
Height of the enclosure80 mm
Depth of the enclosure62 mm
Required spacing
top100 mm
bottom100 mm
left0 mm
right0 mm
Weight, approx.0.5 kg
Product feature of the enclosure housing for side-by-side mountingYes
InstallationSnaps onto DIN rail EN 60715 35x7.5/15, wall mounting
MTBF at 40 °C714 286 h
Other informationSpecifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)