| PSU100D 12 V/3 A |
PSU100D 12 V/3 A Stabilized power supply input: 100-240 V AC output: 12 V DC/3 A |
Input |
Input | 1-phase AC |
Rated voltage value Vin rated | 100 ... 240 V |
Voltage range AC | 85 ... 264 V |
Wide-range input | Yes |
Mains buffering at Iout rated, min. | 15 ms; at Vin = 115/230 V |
Rated line frequency 1 | 50 Hz |
Rated line frequency 2 | 60 Hz |
Rated line range | 47 ... 63 Hz |
Input current | |
at rated input voltage 100 V | 0.75 A |
at rated input voltage 240 V | 0.5 A |
Switch-on current limiting (+25 °C), max. | 60 A |
I²t, max. | 1.2 A²·s |
Built-in incoming fuse | internal |
Protection in the mains power input (IEC 898) | Recommended miniature circuit breaker: from 10 A characteristic C or from 16 A characteristic B |
Output |
Output | Controlled, isolated DC voltage |
Rated voltage Vout DC | 12 V |
Total tolerance, static ± | 2 % |
Static mains compensation, approx. | 0.5 % |
Static load balancing, approx. | 1 % |
Residual ripple peak-peak, max. | 100 mV |
Spikes peak-peak, max. (bandwidth: 20 MHz) | 100 mV |
Adjustment range | 11 ... 14 V |
Product function Output voltage adjustable | Yes |
Output voltage setting | via potentiometer |
Status display | Green LED for 12 V OK |
On/off behavior | Overshoot of Vout < 2 % |
Startup delay, max. | 2.5 s |
Voltage increase time of the output voltage maximum | 30 ms |
Rated current value Iout rated | 3 A |
Current range | 0 ... 3 A |
Note | +50 ... +70 °C: Derating 2.5%/K |
Supplied active power typical | 36 W |
Parallel switching for enhanced performance | Yes |
Numbers of parallel switchable units for enhanced performance | 2 |
Efficiency |
Efficiency at Vout rated, Iout rated, approx. | 84 % |
Power loss at Vout rated, Iout rated, approx. | 6.5 W |
Closed-loop control |
Dynamic mains compensation (Vin rated ±15 %), max. | 0.5 % |
Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ. | 5 % |
Protection and monitoring |
Output overvoltage protection | < 17.6 V |
Current limitation, typ. | 3.6 A |
Property of the output Short-circuit proof | Yes |
Short-circuit protection | Electronic shutdown, automatic restart |
Enduring short circuit current RMS value | |
typical | 6 A |
Overload/short-circuit indicator | - |
Safety |
Primary/secondary isolation | Yes |
Galvanic isolation | Safety extra low output voltage Vout according to EN 60950-1 |
Protection class | Class I |
Leakage current | |
maximum | 3.5 mA |
typical | 1 mA |
CE mark | Yes |
UL/cUL (CSA) approval | cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus (UL 60950-1, CSA C22.2 No. 60950-1), File E151273 |
Explosion protection | - |
FM approval | - |
CB approval | Yes |
Marine approval | - |
Degree of protection (EN 60529) | IP20 |
EMC |
Emitted interference | EN 55022 Class B |
Supply harmonics limitation | not applicable |
Noise immunity | EN 61000-6-2 |
Operating data |
Ambient temperature | |
during operation | -10 ... +70 °C |
— Note | with natural convection |
during transport | -40 ... +85 °C |
during storage | -40 ... +85 °C |
Mechanics |
Connection technology | screw-type terminals |
Connections | |
Supply input | L, N, PE: 1 screw terminal each for 0.3 ... 1.3 mm² single-core/finely stranded |
Output | +, -: 1 screw terminal each for 0.3 ... 1.3 mm² |
Auxiliary | - |
Width of the enclosure | 97 mm |
Height of the enclosure | 98 mm |
Depth of the enclosure | 38 mm |
Required spacing | |
top | 20 mm |
bottom | 0 mm |
left | 20 mm |
right | 20 mm |
Weight, approx. | 0.37 kg |
Installation | Wall mounting |