6EP1234-1AA00
SITOP PSA100E, 300 W

From SIEMENS

SITOP PSA100E, 300 W
SITOP PSA100E Regulated power supply 300 W input: 230 V AC output: DC 24 V/12 A
Input
Input1-phase AC
Voltage range AC187 ... 264 V
Supply voltage
1 at AC Rated value230 V
Wide-range inputNo
Overvoltage resistance-
Mains buffering at Iout rated, min.10 ms
Rated line frequency 150 Hz
Rated line frequency 260 Hz
Rated line range47 ... 63 Hz
Input current
at rated input voltage 230 V2.5 A
Switch-on current limiting (+25 °C), max.50 A
I²t, max.3.3 A²·s
Built-in incoming fuseinternal
Protection in the mains power input (IEC 898)Recommended miniature circuit breaker: from 10 A characteristic C
Output
OutputControlled, isolated DC voltage
Rated voltage Vout DC24 V
Total tolerance, static ±3 %
Static mains compensation, approx.0.1 %
Static load balancing, approx.0.5 %
Residual ripple peak-peak, max.150 mV
Spikes peak-peak, max. (bandwidth: 20 MHz)250 mV
Adjustment range23 ... 26 V
Product function Output voltage adjustableYes
Output voltage settingvia potentiometer
Status displayGreen LED for 24 V OK
On/off behaviorOvershoot of Vout < 5 %
Startup delay, max.0.3 s
Voltage increase time of the output voltage maximum500 ms
Rated current value Iout rated12 A
Current range0 ... 12 A
Note12 A up to +45 °C, 6 A up to +70 °C
Supplied active power typical288 W
Parallel switching for enhanced performanceYes
Numbers of parallel switchable units for enhanced performance2
Efficiency
Efficiency at Vout rated, Iout rated, approx.88 %
Power loss at Vout rated, Iout rated, approx.39 W
Closed-loop control
Dynamic mains compensation (Vin rated ±15 %), max.0.3 %
Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ.3.5 %
Load step setting time 50 to 100%, typ.0.1 ms
Load step setting time 100 to 50%, typ.0.1 ms
Protection and monitoring
Output overvoltage protection< 35 V
Current limitation, typ.13.2 A
Property of the output Short-circuit proofYes
Short-circuit protectionElectronic shutdown, automatic restart
Enduring short circuit current RMS value
maximum7.5 A
Overload/short-circuit indicator-
Safety
Primary/secondary isolationYes
Galvanic isolationSafety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178
Protection classClass I
Leakage current
maximum3.5 mA
typical0.8 mA
CE markYes
UL/cUL (CSA) approvalcULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259
Explosion protection-
FM approval-
CB approvalYes
Marine approval-
Degree of protection (EN 60529)IP20
EMC
Emitted interferenceEN 55022 Class B
Supply harmonics limitation-
Noise immunityEN 61000-6-2
Operating data
Ambient temperature
during operation-10 ... +70 °C
— Notewith natural convection
during transport-40 ... +85 °C
during storage-40 ... +85 °C
Humidity class according to EN 60721Climate class 3K3, no condensation
Mechanics
Connection technologyscrew-type terminals
Connections
Supply inputL, N, PE: Removable screw terminal, each for 1 x 0.5 ... 2.5 mm²
Output+, -: Removable screw terminal each for 1 x 0.5 ... 2.5 mm²
Auxiliary-
Width of the enclosure52 mm
Height of the enclosure170 mm
Depth of the enclosure110 mm
Weight, approx.0.9 kg
Product feature of the enclosure housing for side-by-side mountingYes
InstallationSnaps onto DIN rail EN 60715 35x7.5/15, wall mounting
MTBF at 40 °C1 631 641 h
Other informationSpecifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)

External links