6DL1132-6HD50-0PK0
ET 200SP HA, RQ 4X120VDC-230VAC/5A CO

From SIEMENS

SIMATIC ET 200SP HA, Signal relay module changeover contact, RQ 4x120VDC-230VAC/5A CO HA suitable for terminal block K0, color code CC40, module diagnostics
General information
Product type designationRQ 4x120 V UC ... 230 V AC/5 A CO HA
Firmware versionV1.0
FW update possibleYes
Usable terminal blockTB type K0
Color code for module-specific color identification plateCC40
Product function
I&M dataYes; I&M0 to I&M3
Engineering with
PCS 7 configurable/integrated as of versionV9.0
Redundancy
Redundancy capabilityNo
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Input current
Current consumption (rated value)50 mA; At 24 V and energized changeover coils
Current consumption, max.60 mA; At 19.2 V and energized changeover coils
Power loss
Power loss, typ.2.8 W; At 24 V, energized changeover coils and 5 A current across each changeover contact
Address area
Address space per module
Address space per module, max.1 byte; + 1 byte for QI information
Digital outputs
Number of digital outputs4
Switching frequency
with resistive load, max.2 Hz
with inductive load, max.0.5 Hz
on lamp load, max.2 Hz
Total current of the outputs
Current per channel, max.5 A
Current per module, max.20 A
Total current of the outputs (per module)
horizontal installation
— up to 70 °C, max.20 A
vertical installation
— up to 60 °C, max.20 A
Relay outputs
Number of relay outputs4
external protection for relay outputsyes; 6 A, see data in manual
Switching capacity of contacts
— with inductive load, max.2 A; 2 A (24 V DC), 0.5 A (60 V DC), 0.1 A (120 V DC)
— with resistive load, max.5 A; 5 A (30 V DC), 5 A (230 V AC)
— Switching current, min.8 mA
— Rated switching voltage (DC)24 V; 24 V DC to 120 V DC
— Rated switching voltage (AC)230 V; 24V AC to 230V AC
Cable length
shielded, max.1 000 m
unshielded, max.200 m
Interrupts/diagnostics/status information
Diagnostics functionYes
Substitute values connectableYes
Alarms
Diagnostic alarmYes
Diagnostic messages
Monitoring the supply voltageYes
— parameterizableYes
Diagnostics indication LED
MAINT LEDYes; yellow LED
Monitoring of the supply voltage (PWR-LED)Yes; green PWR LED
Channel status displayYes; Green LED
for module diagnosticsYes; green/red DIAG LED
Potential separation
Potential separation channels
between the channelsYes
between the channels and backplane busYes
Between the channels and load voltage L+Yes
Permissible potential difference
between different circuitsBetween channels: 230 V AC (different system phase)
between channels and backplane bus/supply voltage230 V AC
Isolation
tested with
between channels and backplane bus/supply voltage4 200 V DC/1 min, type test
between backplane bus and supply voltage1 500 V DC/1 min, type test
Between channels1 500 V AC/1 min, type test
Ambient conditions
Ambient temperature during operation
horizontal installation, min.-40 °C; No icing
horizontal installation, max.70 °C
vertical installation, min.-40 °C; No icing
vertical installation, max.60 °C
Altitude during operation relating to sea level
Ambient air temperature-barometric pressure-altitude3 000 m due to converter type used
Dimensions
Width22.5 mm
Height115 mm
Depth138 mm
Weights
Weight, approx.162 g
last modified:03/08/2019