6BK1700-2AA10-0AA0
HCS 716 SUBRACK MOUNTING FRAME

From SIEMENS

SIEMENS ORDER NUMBER IS DISCONNECTED SINCE JUNE 6.2009 SUCCESSOR: 6BK1700-2AA10-0AA1
Installation type/mounting
Mounting typeControl cabinet backplane
Mounting positionHorizontal
Type of ventilationSelf ventilation or forced ventilation
Supply voltage
Type of supply voltageAC
Rated value (AC)230 V
Relative negative tolerance18 %
Relative positive tolerance15 %
Line frequency
Rated value 50 HzYes
Rated value 60 HzYes
Relative symmetrical tolerance5 %
Mains buffering
Mains/voltage failure stored energy time20 ms
Recovery time after power failure, typ.1 s
Connection method
Design of electrical connection for supply voltageConnector, 2-pole
— Connectable conductor cross-sections, solid1x (0.2 ... 2.5 mm²)
— Connectable conductor cross-sections, finely stranded with wire end processing1x (0.25 ... 2.5 mm²)
— Connectable conductor cross-sections for AWG cables24 ... 12
Power
Active power input15 W
Hardware configuration
Type of power output connectableLA716 / LA716I / LA716I HP
Power capacity per rack with fan, max.176 kW
Power capacity per rack without fan, max.67 kW
Slots
Number of slots12
Interfaces
Interfaces/bus typePROFIBUS DP
Protocols
PROFIBUS DPYes
Interrupts/diagnostics/status information
Number of status displays2
LED status displayLED green = status indicator, LED red = fault indicator
Isolation
Overvoltage categoryIII
Degree of pollution2
EMC
EMC interference emissionin accordance with EN 61000-6-4:2007 + A1:2011
Electrostatic discharge acc. to IEC 61000-4-24 kV contact discharge / 8 kV air discharge
Field-related interference acc. to IEC 61000-4-310 V/m (80 ... 1 000 MHz), 3 V/m (1.4 ... 2.0 GHz), 1 V/m (2.0 ... 2.7 GHz)
Conducted interference due to burst acc. to IEC 61000-4-42 kV voltage supply cables / 2 kV signal cables
Conducted interference due to surge acc. to IEC 61000-4-5On supply lines: 1 kV symmetrical, 2 kV asymmetrical, PROFIBUS cable asymmetrical 1 kV
Conducted interference due to high-frequency radiation acc. to IEC 61000-4-610 V in the frequency range 0.15 ... 80 MHz, Mmdulation 80 % AM at 1 kHz, evaluation criterion A
Degree and class of protection
IP degree of protectionIP00
Standards, approvals, certificates
Certificate of suitabilityCE, KCC
CE markYes
KC approvalYes
EAC (formerly Gost-R)Yes
China RoHS complianceYes
Reference designation according to DIN EN 81346-2K
Ambient conditions
Ambient temperature during operation
min.0 °C
max.55 °C
Ambient temperature during storage/transportation
Storage, min.-40 °C
Storage, max.70 °C
Transportation, min.-40 °C
Transportation, max.70 °C
Air pressure acc. to IEC 60068-2-13
Operation, min.860 hPa
Operation, max.1 080 hPa
Storage, min.660 hPa
Storage, max.1 080 hPa
Altitude during operation relating to sea level
Installation altitude above sea level, max.2 000 m
Relative humidity
Operation at 25 ℃, max.95 %
Shock testing
Shock resistance during operation acc. to IEC 60068-2-2715 g / 11 ms / 3 shocks/axis
Shock resistance during storage acc. to IEC 60068-2-2925 g / 6 ms / 1 000 shocks/axis
Dimensions
Width510 mm
Height310 mm
Depth330 mm