| *** Spare part *** SIMATIC Touch Panel TP 177A 5.7" blue mode STN display, MPI/PROFIBUS DP interface, configurable from WinCC flexible 2004 Compact HSP Contains open source software which is provided free of charge. See enclosed CD |
General information |
Product type designation | TP 177A |
Display |
Design of display | STN |
Screen diagonal | 5.7 in |
Color display | No |
Number of colors | 2; Blue levels |
Resolution (pixels) |
Horizontal image resolution | 320 Pixel |
Vertical image resolution | 240 Pixel |
Backlighting |
MTBF backlighting (at 25 °C) | 50 000 h |
Control elements |
Control elements | Touch screen |
Keyboard fonts |
Function keys | No |
System keys | No |
Numeric keyboard | Yes |
alphanumeric keyboard | Yes |
hexadecimal keyboard | Yes |
Multi-key operation | No |
Touch operation |
Design as touch screen | Yes; analog, resistive |
Connection type |
Type of connection for mouse/keyboard/barcode reader | - / - / - |
Installation type/mounting |
Mounting position | vertical |
maximum permissible angle of inclination without external ventilation | 35° |
Supply voltage |
Type of supply voltage | DC |
Input current |
Current consumption (rated value) | 0.24 A |
Starting current inrush I²t | 0.5 A²·s |
Power |
Active power input, typ. | 6 W |
Processor |
Processor type | ARM |
Memory |
Type of memory | Flash / RAM |
Memory available for user data | 512 kbyte |
Type of output |
Info LED | No |
Power LED | No |
Error LED | No |
Time of day |
Clock |
Type | Software clock, no battery backup |
retentive | No |
synchronizable | No |
Interfaces |
Interfaces/bus type | 1x RS 422, 1x RS 485 (max. 1.5 Mbit/s) |
Number of industrial Ethernet interfaces | 0 |
Number of RS 485 interfaces | 1 |
Number of RS 422 interfaces | 1 |
Number of USB interfaces | 0 |
PC card slot | No |
CF card slot | No |
Multimedia card/SD card slot | No |
Protocols |
Supports protocol for PROFINET IO | No |
PROFIsafe | No |
PROFIBUS | Yes |
Protocols (Ethernet) |
TCP/IP | No |
Further protocols |
EtherNet/IP | No |
MODBUS | No |
other bus systems | Yes |
Degree and class of protection |
IP (at the front) | IP65 |
NEMA (front) | NEMA 4x (when installed) |
IP (rear) | IP20 |
Standards, approvals, certificates |
Certifications | CE, GL, ABS, BV, DNV, LRS, FM Class I Div. 2, UL, CSA, cULus, EX-Zone 2 (in Vorbereitung), EX-Zone 22 (in Vorbereitung), C-TICK, NEMA 4x |
cULus | Yes |
EAC (formerly Gost-R) | No |
Suitable for safety functions | No |
Use in hazardous areas |
ATEX Zone 2 | Yes |
ATEX Zone 22 | Yes |
FM Class I Division 2 | Yes |
Marine approval |
Germanischer Lloyd (GL) | Yes |
American Bureau of Shipping (ABS) | Yes |
Bureau Veritas (BV) | Yes |
Det Norske Veritas (DNV) | Yes |
Lloyds Register of Shipping (LRS) | Yes |
Nippon Kaiji Kyokai (Class NK) | Yes |
Polski Rejestr Statkow (PRS) | No |
Ambient conditions |
Ambient temperature during operation |
min. | 0 °C |
max. | 50 °C |
Ambient temperature during storage/transportation |
min. | -20 °C |
max. | 60 °C |
Relative humidity |
Operation, max. | 90 % |
Operating systems |
pre-installed operating system | LINUX |
Configuration |
Message indicator | Yes |
Alarm system (incl. buffer and acknowledgment) | Yes |
Process value display (output) | Yes |
Process value default (input) possible | Yes |
Recipe management | Yes |
Configuration software |
Configuration tool | WinCC flexible Compact Version 2004 SP1 or higher (to be ordered separately) |
STEP 7 Basic (TIA Portal) | No |
STEP 7 Professional (TIA Portal) | No |
WinCC flexible Compact | Yes |
WinCC flexible Standard | Yes |
WinCC flexible Advanced | Yes |
WinCC Basic (TIA Portal) | No |
WinCC Comfort (TIA Portal) | Yes |
WinCC Advanced (TIA Portal) | Yes |
WinCC Professional (TIA Portal) | Yes |
Languages |
Online languages |
Number of online/runtime languages | 5 |
Project languages |
Languages per project | 32 |
Functionality under WinCC (TIA Portal) |
Libraries | Yes |
Number of Visual Basic Scripts | |
Debugging in the simulator | No |
Task planner | Yes |
Help system | Yes |
Number of characters per info text | 70 |
Number of tooltips | 0 |
Message system |
Number of alarm classes | 32 |
Number of messages | 1 000 |
Bit messages | Yes |
— Number of bit messages | 1 000 |
Analog messages | Yes |
— Number of analog messages | 20 |
Telegram message procedure Alarm S | No |
System messages HMI | Yes |
System messages PLC | Yes |
System messages, other (SIMATIC S7, Sinumerik, Simotion, etc.) | No |
Lines | 1 |
Number of characters per message | 80 |
Number of process values per message | 8 |
Acknowledgment groups | Yes |
Message indicator | Yes |
acoustic feedback | No |
First/last value | Yes |
Recipe management |
Number of recipes | 5 |
Data records per recipe | 20 |
Entries per data record | 20 |
Recipe memory | 32 KB integrated Flash |
Variables |
Number of variables per device | 500 |
Number of variables per screen | 30 |
Limit values | Yes |
Multiplexing | Yes |
Structures | No |
Images |
Number of configurable images | 250 |
Permanent window/default | Yes |
Start screen configurable | Yes |
Image selection by PLC | Yes |
Image number in the PLC | Yes |
Image objects |
Text objects | 1,000 text elements |
Number of I/O fields per image | 30 |
Index of screen context | No |
Return | No |
Graphics object | Bit maps, icons, icon (full-screen), vector graphics |
— Icons | 1 |
— Icon (full screen) | 1 |
Complex image objects |
Status/control | Not possible |
dynamic objects | Diagrams, bar graphs |
Bar graphs | |
— Number of bars per chart | 5 |
Limit value lines | Yes |
Attributes for dynamic objects |
Color change | No |
X/Y movement | No |
Hide | Yes |
Angle of rotation | No |
Lists |
Number of text lists per project | 300 |
Number of graphics lists per project | 100 |
Security |
Number of user groups | 50 |
Number of user rights | 32 |
Password export/import | Yes |
Data carrier support |
PC card | No |
CF card | No |
Transfer (upload/download) |
Transfer of configuration | MPI/PROFIBUS DP, serial, automatic transfer recognition |
Process coupling |
Connection to controller | S7-200, S7- 300/400, Win AC see section on "System interfaces" |
S7-200 | Yes |
— PPI (point-to-point) | Yes |
— PPI network | Yes |
— MPI | Yes |
— PROFIBUS DP | Yes |
— Ethernet | No |
S7-300/400 | Yes |
— MPI | Yes |
— PROFIBUS DP | Yes |
— PROFINET | No |
S5 | No |
— serial | No |
— PROFIBUS DP | No |
TI 505 | No |
Allen Bradley (DF1) | No |
Allen Bradley (DF485) | No |
Mitsubishi (FX) | No |
Mitsubishi (MP4) | No |
Telemecanique (ADJUST) | No |
Telemecanique (Uni-Telway) | No |
OMRON (LINK/Multilink) | No |
Modicon (Modbus) | No |
GE-Fanuc (SNP) | No |
Functions |
Key repeat | No |
TAB sequence | Yes |
Calculating functions | Yes |
Animate | No |
Menu tree editor | No |
Unit switchover | No |
Service tools/configuration aids |
Clean screen | Yes |
Touch calibration | Yes |
Backup/Restore manually | Yes |
Simulation | Yes |
Device switchover | Yes |
Delta transfer | No |
Monitoring function for battery and memory | No |
Trace (operation archive) | No |
Expandability/openness |
Open Platform Program | No |
Peripherals/Options |
Peripherals | |
SIMATIC HMI MM memory card: Multi Media Card | No |
Additional software components loadable | Yes |
Dimensions |
Width of the housing front | 212 mm |
Height of housing front | 156 mm |
Mounting cutout, width | 198 mm |
Mounting cutout, height | 142 mm |
Overall depth | 44 mm |
Weights |
Weight (without packaging) | 0.75 kg |
Other |
free hotline | Yes |