6AG3111-1AH00-3AB0
SINVERT PVS500 600Series IEC 50Hz M

From SIEMENS

***SPARE PART*** SINVERT PVS500 PV-INVERTER, 600SERIES, IEC 50HZ, 3P NOM. ACTIVE POWER (AC): 500KVA GRID CONNECT. MV TRANS, MPP-RANGE: 450-750V, UMAX 820VDC, 3 DC-INPUTS, IP20, AIR COOLING, INVERTER UNIT AMOUNT: 1, OPTIONS AVAILABLE. FOR: 1000V-OPTION (UDC MAX 1000V), PV FIELD POSITIVE GROUNDING, PV FIELD MINUS GROUNDING, SYMMETRY MONITORING, CABINET HEATING, SINVERT PVS WARRANTY 5 YEARS,
General technical data:
Product type designationSINVERT PVS500
Product designationPhotovoltaic inverter
Performance class for PV inverters500
Efficiency
maximum possible%98.4
acc. to Euro%98.1
acc. to CEC%98.2
NoteData without internal power supply
Design of PV inverter unitsingle device
Number of PV inverter sub-units1
Type of installationindoor installation
Protection class IPIP20
Operating resource protection classI
Design of the interface for communicationEthernet
A-rated sound power level maximumdB80
Design of the displayLCD-TFT
National language on the display screen selectableEnglish, German
Connection method for PV inverterswithout transformer
Outputs:
Apparent power output on the AC side
Rated valuekV·A500
Notefor AC nominal voltage, supply air temperature ≤ 40°C
Supplied active power on the AC side
in permanent operation Rated valuekW500
maximumkW500
Notefor AC nominal voltage, supply air temperature ≤ 40°C, cos phi = 1
Inductive power factor0.8 ... 1
Capacitive power factor0.8 ... 1
Phase number3
Output voltage on the AC side
for infeed operation Rated valueV288
for infeed operationV244.8 ... 316.8
Line frequency 1
for infeed operation Rated valueHz50
for infeed operationHz47.5 ... 51.5
Current supplied on the AC side
maximumA1 002
Harmonic distortion factor maximum%2
Grounding concept on the AC sideIT
Design of the overvoltage protection on the AC sidetype 1/2
Inputs:
MPP voltageV450 ... 750
Consumed active power on the DC side Rated valuekW513
Input voltage on the DC side
for start of the infeed modeV600
for possible infeed operationV450 ... 750
Rated valueV465
maximum permissibleV820
Total consumed power on the DC side maximumA1 103
Number of inputs on the DC side3
Input current per DC input maximumA368
Product component on the DC side Overcurrent protection per DC inputYes
Overcurrent strength per DC input Rated valueA368
Design of the overvoltage protection on the DC sidetype 2
Auxiliary circuit:
Auxiliary voltage
Rated valueV400
minimumV340
maximumV440
Auxiliary voltage frequency
— 1 Rated valueHz50
Grounding concept for external auxiliary power supplyTN-S
Consumed active power from external auxiliary voltage
for infeed operation
— maximumW2 650
in night-time operating mode
— without cabinet heating maximumW190
— with cabinet heating maximumW440
Ambient conditions:
Installation altitude
at rated active powerm0 ... 1 000
minimumm0
maximumm2 000
Incoming air temperature at rated active power value maximum°C40
Ambient temperature
during operation°C0 ... 50
during storage°C-25 ... +70
during transport°C-25 ... +70
Relative humidity
during operation%0 ... 95
during storage%0 ... 95
during transport%0 ... 95
Environmental category3K3
Type of coolingForced-air cooling via fan
Cooling air flowm³/h6 500
Type of ventilationair intake cabinet front/air outlet cabinet top
Mechanical data:
Width of PV inverter subunitmm2 700
Height of PV inverter subunitmm2 100
Depth of PV inverter subunitmm730
Weight of the single devicekg2 085
Weight of PV inverter subunitkg2 085
Mounting typeFloor mounting installation

External links