6AG1640-0AA00-2AX1
SIPLUS_TD400C

From SIEMENS

***Spare part*** SIPLUS S7-200 TD400C -10...+60°C based on 6AV6640-0AA00-0AX1
General information
Product type designationTD 400C
Display
Design of displaySTN, black/white
Screen diagonal3.7 in; 4-line
Line display
Number of lines4
Number of characters per line24
Resolution (pixels)
Horizontal image resolution192 Pixel
Vertical image resolution64 Pixel
Backlighting
MTBF backlighting (at 25 °C)20 000 h
Control elements
Control elementsMembrane keyboard
Keyboard fonts
Membrane keyboardYes
System keysYes
— Number of configurable system keys15
Supply voltage
Type of supply voltageDC
Interfaces
Interfaces/bus type1x RS 485 (max. 187.5 Mbit/s)
Protocols
MPIYes
AS-InterfaceNo
Degree and class of protection
IP (at the front)IP65
NEMA (front)NEMA 4, NEMA 4x, NEMA 12 (when installed)
IP (rear)IP20
Standards, approvals, certificates
CertificationsCE, KC, Gost R, NEMA 4, NEMA 4x, NEMA 12
RCM (formerly C-TICK)No
KC approvalYes
Ambient conditions
Ambient temperature during operation
min.-10 °C
max.60 °C
Ambient temperature during storage/transportation
min.-20 °C
max.60 °C
Altitude during operation relating to sea level
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 080 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax - 20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost permitted (no commissioning in bedewed state)
Resistance
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Configuration
Configuration software
Configuration toolMicroWin (to be ordered separately)
Dimensions
Overall depth31 mm
Weights
Weight (without packaging)0.33 kg
last modified:03/25/2019